POWER-LITE E-B40W 40W LED Batten Installation Guide

June 13, 2024
POWER-LITE

POWER-LITE E-B40W 40W LED Batten

Product Information

  • Product Name: MULTI-WATT LED BATTEN
  • Model Numbers: E-B40W, E-B40W-E
  • Sensor Specifications: Detection area: 90 degree wide detective beam angle with 2-3 meters distance
  • Driver Specifications (Emergency): Every 4 seconds: Check for battery disconnection, charger board fault, lamp failure and transformer failure. Every month: Perform a 3 minute duration test. Every year: Perform a 1 Hour or 3 Hour duration test. All test functions are factory preset and do not need field adjustment.

Product Usage Instructions

  1. Switch off the power supply before starting any installation.
  2. Read the instructions and ensure you have all the tools and accessories required for the installation.
  3. For surface mount installation:
  4. Select the preferred color temperature for the product in the CCT change function.
  5. Follow the hole spacing specifications for your specific product size.
  6. If applicable, strip the neutral wire to a length of 8-10mm.
  7. Complete the installation as per the provided diagram.
  8. For suspended installation:
  9. Select the preferred color temperature for the product in the CCT change function.
  10. Follow the hole spacing specifications for your specific product size.
  11. Adjust the length of the suspension wire as needed.
  12. If applicable, strip the neutral wire to a length of 8-10mm.
  13. Complete the installation as per the provided diagram.
  14. Ensure the power supply is turned off before connecting the power.
  15. Keep the instructions for future reference.
  16. Refer to the IP (Ingress Protection) rating of the luminaire when deciding the location of installation.
  17. If using an emergency product, charge and discharge the battery every six months for optimal performance.
  18. The battery in this luminaire should only be replaced by the manufacturer or a qualified person.
  19. Note that this luminaire is not suitable for Functional Safety as an Emergency luminaire under the Australian Building Code.

Important Safety Instructions

To ensure correct function and safety, please read and follow all instructions carefully before using the product:

  1. Turn off power supply before installation or before doing any maintenance work.
  2. Do not install any luminaire near the heat source.
  3. Do not exceed the nominal supply voltage or amperage ratings.
  4. All wiring and installation of the light fitting must adhere to local and national wiring rules.
  5. Take care not to pull any electrical wires during unpacking as this may damage the connection.
  6. Lay out all the components on a smooth surface and make sure there are no components missing before assembling.
  7. To avoid injury or damage to the fitting, please ensure that power leads and screws are secure before connecting the power.
  8. Please keep instructions for future reference.
  9. Please refer to IP(Ingress Protection) rating of this luminaire when deciding the location of installation.
  10. To achieve the best using effect, the battery should be charged and discharged every six months (for Emergency products only).
  11. The battery in this luminaire shall only be replaced by the manufacture or a qualified person.
  12. Not suitable for Functional Safety as an Emergency luminaire under the Australian Building Code.

Installation Procedure

WARNING

  1. Switch off before installation.
  2. Switch on only after complete installation and examination of the circuit.
  3. Qualified electrician for installation and maintenance only

Turn off power supply before starting any installation.
Read instructions & check you have all the tools & accessories to complete the installation correctly.

Surface Mount Installation

POWER-LITE E-B40W-40W-LED-Batten-FIG-2 POWER-
LITE E-B40W-40W-LED-Batten-FIG-3

Suspended Installation

POWER-LITE E-B40W-40W-LED-Batten-FIG-4 POWER-
LITE E-B40W-40W-LED-Batten-FIG-5

POWER-LITE E-B40W-40W-LED-Batten-FIG-6

Function Instructions (For specific function, please refer to actual model)

Emergency
Emergency function switches automatically between power cut and power restoration.

  • Li battery, high efficiency
  • Battery duration: 3 hours
  • Charge period: 24 hours

Sensor
Detection area: 90
degree wide detective beam angle with 2-3 meters distance

Driver Specifications (Emergency)

POWER-LITE E-B40W-40W-LED-Batten-FIG-9

Instructions for automatic test option

  • On the unt the ered up ol automated into an eat and distie as colos:

  • Every month: Perform a 3 minute duration test.

  • Every year: Perform a 1 Hour or 3 Hour duration test.
    All test functions are factory preset and do not need field adjustment.
    2.Dual Colour Indicator LED Status Meanings

  • Green Solid On Ready/Normal Operation

  • Red Requires Service

POWER-LITE E-B40W-40W-LED-Batten-FIG-10
NOTE: After repairing a service fault, press and hold the test button for 2 seconds to reset the flashing indicator light to green.

Manual Test

POWER-LITE E-B40W-40W-LED-Batten-FIG-11

Note: DALI & 1-10V driver specification, please refer to individual driver datasheet.

Sensor Specifications (For Sensor Version)

POWER-LITE E-B40W-40W-LED-Batten-FIG-12

Sensor Settings

POWER-LITE E-B40W-40W-LED-Batten-FIG-13

Detection area:
The detection area can be adjusted by the knob, clockwise adjustment increases the sensitivity, counterclockwise adjustment reduces the sensitivity, the maximum detection distance is 6 meters, the minimum detection distance is 2 meters. Notice 1:The distance test is carried out under Ta25°C, 1.8 meters wall mounting installation height. The test result is based on the movement along the tangential direction of the sensor, and the detect distance can be adjusted by the dial switch. Notice 2:Infrared sensor will be affected by temperature. Too high or too low temperature may affect the detect distance or even cause failure to sensor.

Hold time:
The hold time can be adjusted by the knob. Clockwise adjustment increases the hold time, counterclockwise adjustment reduces the hold time, the maximum hold time is 7min, and the minimum hold time is 105. Notice 1:The hold time counting should be started after the sensor is powered on and initialized.

Daylight sensor:
The light threshold can be selected through the Knob. Clockwise adjustment increases the light threshold, counterclockwise adjustment reduces the light threshold, the maximum light threshold is 2000lux, and the minimum light threshold is 10lux. Notice 1:The light threshold may cause a large deviation in different lamps.

Detection Range Diagram

POWER-LITE E-B40W-40W-LED-Batten-FIG-15

1800 909 306
nedlandsgroup.com.au
sales@nedlandsgroup.com.au

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>