VALENT Microprocessor Controller for Dedicated Outdoor Air System
Supplement Microprocessor Controller
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Overview
This document is to be used in conjunction with the Microprocessor Controller for Dedicated Outdoor Air System Installation, Operation and Maintenance Manual (IOM). All safety information provided in that IOM pertains to Heat- Cool Only controls also.
Heat-Cool Only Overview
Heat-Cool Only is designed to allow third-party control of a packaged DX,
split DX with remote condensers, or Heat Pump unit while maintaining the
safeties
of the refrigeration system and heating devices. To achieve this, the Heat-
Cool Only controller is factory installed and factory commissioned. This
controller is responsible for the operation of the refrigeration and heating
components installed in the unit. The safety
of the refrigeration system is assured by monitoring pressures and
temperatures contained within the refrigeration circuit(s). The third party is
required to control the following: supply and exhaust airflow, cooling or
heating operation selection, dehumidification enable, temperature setpoints,
and emergency shutdown.
Additionally, a third-party device that is field supplied and installed
provides occupancy, temperature, and airflow monitoring. This third-party
device interfaces to the Heat-Cool Only controller via a terminal strip in the
control cabinet, as represented in the image below.
END DEVICES: End devices required for Heat-Cool Only operation are
provided and installed in the unit for the sole purpose of operating the
heat/cooling control system. Sensors required for the third-party controller
operation are to be provided and installed by the third party. Additionally,
the third-party control system may use additional end devices not provided by
the factory. Please refer to the unit’s submittal information for the exact
unit configuration and selected options to determine factory provided end
devices.
WARNING Powering the third-party controller is the responsibility of the third party. The third party will supply and install a transformer to power their controller. This power cannot be taken from the control panel. The third-party device cannot be mounted in the electrical control panel of the unit.
Third Party Responsibilities
Occupancy, temperature, airflow, and third-party device power with Heat-Cool Only are the responsibility of the third party through a third-party device. This control not only includes the timing of each occupied mode, but logic for enabling and modulating all non-refrigeration or heating components.
Occupancy
Scheduling and occupancy mode control are the responsibility of the third
party.
Airflow
Maintaining the proper airflow by enabling and modulating the fans and dampers
is the responsibility of the third-party controller.
During normal operation, airflow should continue over the unit’s heat
exchangers after removing the remote start command to the Heat-Cool Only
controller.
For units with variable speed compressors, the compressors may take up to two
minutes to completely stop. Additionally, in heating mode, supply airflow
should continue until the supply air temperatures drop below 80ºF to dissipate
the heat remaining in the heating devices and prevent excessive component
temperatures.
DAMPER POSITIONING: Dampers will need to be powered and a position signal provided, when the dampers are modulating. Prior to starting fans in the unit, the third party will ensure that there is an open path for airflow by confirming that the damper end switch is closed, when installed.
FAN MODULATION: The enable and modulation signals are the responsibility of the third-party controller.
-
Supply Fan : Supply fan modulation will need to follow these guidelines. The end switch signal must be received prior to the start of any fans in the unit when installed.
-
Cooling or Heat Pump Heating: When the unit is operating in cooling mode or heat pump heating, the fan turndown must be limited to a minimum of 50% of the designed airflow to ensure the refrigeration system can adequately modulate
to meet the desired temperature setpoints. Modulating below 50% of the designed airflow may result in loss of space temperature control and have a negative impact on the refrigeration and heating components. -
Electric Heat: Supply fan modulation must be limited to the minimum airflow requirements of the electric heater manufacturer. The minimum air flow required through a duct heater depends on the KW per square foot of face area for the highest capacity ON-OFF stage. In general, 500 FPM is adequate in most applications.
Please contact technical support to get more information regarding specific products.
WARNING When modulating the gas furnace heating capacity, it is
recommended to maintain a maximum temperature rise and a minimum airflow for
all units. The criteria must be met when controlling the staging and modu-
lation of the gas furnaces in order to prevent improper combustion and damage
to the unit.
Please see Appendix B – Heat-Cool Only Heating Limitations for minimum airflow
specific to the unit size and furnace installed. Please refer to the unit’s
submittal information for the exact gas furnace performance data.
-
Gas Furnace Heat: When the unit is heating with a gas furnace, limit turndown to the minimum airflow based on the unit size or 50.0% of design airflow, whichever value is greater.
Please see Appendix B – Heat-Cool Only Heating Limitations for minimum airflow specific to the unit size and furnace installed. -
Exhaust fan: Exhaust fan modulation will need to maintain the building requirements.
Energy Recovery
Control of energy recovery equipment installed in the unit is the responsibility of the third party. A heat wheel with or without a VFD, or a face/bypass damper for a flat plate heat exchanger must be controlled to a third-party provided sensor.
ENERGY WHEEL BYPASS DAMPER: When provided, the energy wheel bypass damper
needs to be opened when exceeding design outdoor airflow rate in economizer
mode by turning off the energy recovery wheel.
ENERGY RECOVERY DEFROST : Both forms of energy recovery must have a
defrost sequence provided via the third-party controller.
-
Energy Recovery Wheel: The third party will provide either an exhaust air temperature sensor or heat wheel pressure differential sensor/switch when
pre-heat is not installed in the unit and the energy recovery device is used for exhaust air energy recovery. The exhaust air temperature must remain above 36°F or the differential pressure is less than 1.5”wc when the outside air temperature is below 10°F. -
Energy Core: The third party will provide an exhaust air temperature sensor when pre-heat is not installed in the unit and the energy recovery device is used for exhaust air energy recovery. The exhaust air temperature must remain above 36°F.
Third Party Responsibilities
- Electric Preheat: When a preheat device is installed for energy recovery defrost, the third-party controller needs to ensure that the following conditions are met prior to enabling the preheat device.
- Outside Air Damper >=30% open; AND
- Supply Fan enabled; AND
- Outdoor Air Temp < 10°F.
NOTE: Please see manufacturer’s information for suggested minimum cfm for pre-heat.
Temperature
Heat-Cool Only Control requires the third party to make decisions based on
operating conditions and setpoints to heat, cool, dehumidify, or economize.
The third-party controller will communicate setpoints, via hard-wired 2-10 VDC
signals, based on the operating mode:
- Cooling – Cooling Coil Setpoint
- Dehumidifying – Cooling Coil and Supply Air Setpoints
- Heat Pump Heating – Supply Air Setpoint
- Heating – Supply Air Setpoint
The third-party controller needs to control the amount of economizer and
energy recovery capacity necessary to meet the current requirements, depending
on the equipment installed in the unit. Analog output signals are sent via the
terminal strip that interfaces with the controller or directly to the end
devices.
Please refer to the unit wiring schematics or see Appendix A – Terminal Strip
Wiring for further information regarding control input types and terminal
strip wiring.
-
Cold Coil Temperature Control: The third- party controller will send a signal to control the compressors in the unit. This setpoint will range between 50ºF and 75ºF in cooling and dehumidification modes of operation.
-
Supply Air Temperature Control: When the unit has a HGRH coil or heating, there will be a Supply Air Temperature Setpoint input for the third-party controller. This setpoint will range between 50°F and 95°F in all modes of operation. The HGRH valve and heating devices will control to this setpoint.
NOTE: A minimum setpoint of 60.0°F is advised in heating mode of a heat pump. -
Supply Temperature Limits: The heat-cool only controller also has high and low temperature limits. These limits are adjustable at the controller and
will cause cooling or heating to be disabled. It is the responsibility of the third party to maintain the following conditions: -
Minimum Low Supply Temp Limit: 35°F
-
Maximum High Supply Temp Limit: 120°F
-
Mode Switching – Cooling vs Heating: When heating and cooling are both installed in the unit, the third party is responsible for determining which mode of operation is required at any given time. The Cooling/Heating Control Mode input will be open for cooling or closed for heating. When the input changes state, the unit will shut down the current operation of the cooling or heating devices and switch to the other mode of operation after the mode switch timer expires.
-
Mode Switching – Cooling vs Dehumidification: When a hot gas reheat coil is installed in the unit, the third party is responsible for determining when the hot gas reheat will control to the Supply Air Temperature Setpoint. The Cooling/Dehumidification Control Mode input will be open for cooling only or closed when reheat is desired.
Digital Status
The Heat-Cool Only terminal strip provides the third-party controller with
information from devices installed in the unit. The following information is
available through those digital statuses.
OUTSIDE AIR DAMPER ACTUATOR END SWITCH: When installed, this status
provides an indication that the outside air damper actuator has reached a
specific open position.
CONDENSATE OVERFLOW SWITCH: This device, when installed, indicates when
the condensate drain pan is full and further operation of the refrigeration
system could cause an overflow of water in the pan.
ENERGY RECOVERY STATUS : When installed, the energy recovery device may
have an indication back to the terminal strip that the device is rotating, or
the bypass is open.
FILTER PRESSURE SWITCH: If a filter pressure switch or switches is
installed, an indication back to the third-party indicates that the filters
are dirty.
GLOBAL ALARM OUTPUT: The global alarm output is available on all Heat-
Cool Only units. This status indicates that there is an alarm condition in the
Heat-Cool Only controller.
Third Party Responsibilities
Digital Commands
EMERGENCY SHUTDOWN: This input is to remotely shutdown the unit during a
fault condition. All heating or cooling operation will stop when this input is
open. This input affects the Global Alarm status.
REMOTE START/STOP: This input is to remotely start or stop the
refrigeration and heating control of the unit. This input will be closed for
the unit to provide cooling or heating.
COOLING/DEHUMIDIFICATION CONTROL MODE: This input determines whether the
unit is in cooling mode or dehumidification mode.
COOLING/HEATING CONTROL MODE: This input determines whether the unit is
in cooling or heating mode.
Operation of Unit
All Modes
The following conditions are required for the third party to enable the unit
to operate in any mode:
- Remote Start Input: Closed
- Shutdown Input: Closed
- Damper Positioning: OAD/RAD End Switch Closed (when installed)**
- Supply Fan Status: Closed
- Supply Fan Control: Not below 50.0% of the full-load airflow for the unit NOTE: These safety checks are the responsibility of the third-party controller and do NOT input to the controller.
Cooling
The following conditions are required for the third party to enable the unit
and start compressors in cooling mode:
- Cooling/Dehumidification Control Input: Cooling mode (Open)
- Cooling/Heating Control Input: Cooling mode (Open)
- Outside Air Temperature: > Cooling Ambient Lockout (55.0°F) (adj.)
- Cooling Coil Leaving Air Temp: Coil Low Temp Limit (42.0°F) (adj.)
- Refrigerant Pressure Switches: Closed (Both High and Low)
- Supply Air Temperature: Minimum Low Supply Temp Limit (35.0°F)
- Cooling Coil Setpoint: 50 – 75°F scaled from 2-10vdc (Compressor staging)
Dehumidifying
NOTE: Hot Gas Reheat must be installed in the unit to utilize this functionality. The following conditions are required for the controller to enable a unit in dehumidification mode:
- Cooling/Dehumidification Control Input: Dehumidification mode (Closed)
- Cooling/Heating Control Input: Cooling mode (Open)
- Outside Air Temperature: > Cooling Ambient Lockout (55.0°F) (adj.)
- Cooling Coil Leaving Air Temp: Coil Low Temp Limit (42.0°F) (adj.)
- Refrigerant Pressure Switches: Closed (High and Low)
- Supply Air Temperature: Minimum Low Supply Temp Limit (35.0°F)
- Supply Air Setpoint: 50 – 95°F scaled from 2-10vdc (HGRH valve modulation)
- Cooling Coil Setpoint: 50 – 75°F scaled from 2-10vdc (Compressor staging)
Heating
The following conditions are required for the controller to enable a unit in
heating mode:
- Heating/Cooling Control Mode: Heating mode (Closed)
- Outside Air Temperature: < Heating Ambient Lockout (80.0°F) (adj.)
- Supply Air Temperature: < Maximum High Supply Temp Limit (120.0°F)
- Supply Air Setpoint Request: 50 – 95°F scaled from 2-10vdc
Heating – Heat Pump
The following conditions are required for the controller to enable a unit and
start compressors in heating mode.
- Heating/Cooling Control Mode: Heating mode (closed) (Heat Pumps Only)
- Outside Air Temperature: < Heating Ambient Lockout (80.0°F) (adj.)
- Outside Air Temperature: ASHP Low Ambient Lockout (17ºF) (adj.) (ASHP only)
- Refrigerant Pressure Switches: Closed (High and low)
- Supply Air Temperature: < Maximum High Supply Temp Limit (120.0°F)
- Supply Air Setpoint Request: 50-95°F scaled from 2-10vdc
Appendix A: Terminal Strip Wiring
Third-Party Wiring
The following table/diagram is the terminal strip wiring of the terminal strip
for Heat-Cool Only operation. This terminal strip is the wiring point for the
third-party control’s device. Please refer to the unit schematics for
additional information.
Terminal | Terminal Type | Description/Device | Third Party IO Type |
---|---|---|---|
50C (2) | Common | Common | |
501 | 0.0-10.0 VDC | Supply Fan Speed Input | Analog Command |
502 | 0.0-10.0 VDC | Exhaust Fan Speed Input | Analog Command |
503 | 0.0-10.0 VDC | Energy Recovery Capacity Input | Analog Command |
51C | Common from Controller | ||
511 | 2.0-10.0 VDC | Cooling Coil Temperature Setpoint Input | Analog Command |
512 | 2.0-10.0 VDC | Supply Air Temperature Setpoint Input | Analog Command |
60C (2) | Common | Common | |
601 | 2.0-10.0 VDC | OA/RA Modulating Damper Signal | Analog Command |
602 | 24 VAC | Damper Actuator Power | Digital Command |
603 | 24 VAC | Supply Fan Start | Digital Command |
604 | 24 VAC | Exhaust Fan Start | Digital Command |
605 | 24 VAC | Energy Recovery Wheel Start | Digital Command |
606 | 24 VAC | Pre-Heater Enable | Digital Command |
70P (2) | 24 VAC Power from Unit | ||
701 | 24 VAC | Remote Start Input | Digital Command |
702 | 24 VAC | Shutdown Input | Digital Command |
703 | 24 VAC | Cooling(0)/Dehumidification(1) Control Mode | Digital Command |
704 | 24 VAC | Cooling(0)/Heating(1) Control Mode | Digital Command |
80C (3) | Common | Common | |
801 | Global Alarm Output (Heat/Cool Alarms Only) | Digital Status | |
802 | OA Damper End Switch (100% OA Units) | Digital Status | |
803 | Condensate Overflow Switch | Digital Status | |
804 | Energy Recovery Status | Digital Status | |
805 | Filter Pressure Switch | Digital Status | |
90C (2) | Common | Common | |
901 (2) | 24 VAC | AFMS Power | 24 VAC |
902 | 0.0-10.0 VDC | Supply Airflow Measuring Station | Analog Feedback |
903 | 0.0-10.0 VDC | Exhaust Airflow Measuring Station | Analog Feedback |
904 | 0.0-10.0 VDC | Outdoor Airflow Measuring Station | Analog Feedback |
Appendix B: Gas Furnace Limitations
Supply fan modulation must be limited to the minimum airflow based on the unit size or 50% of design airflow, whichever value is greater. When modulating the gas furnace heating capacity, it is recommended to maintain a maximum temperature rise and a minimum airflow for all units.
WARNING The following criteria must be met when controlling the staging and modulation of the gas furnaces to prevent improper combustion and damage to the unit. The airflow reduction is only allowed if the supply air temperature does not exceed the max temp rise listed below. The supply air temp must be monitored, and the furnace must be modulated to prevent over- firing of the furnace at low airflows.
- In the table below, locate the unit casing size, the correct furnace MBH, and the airflow supply direction for the minimum airflow in CFM.
- All gas furnaces must be limited to the greater of the following:
- minimum airflow in CFM; OR
- 50% of design airflow.
- The third-party controls will send a 2-10VDC signal to control to a supply air temperature setpoint between 50.0°F (10.0°C) and 95.0°F (35.0°C) during all modes of operation.
- The third-party controls must have a high supply temperature limit of 120.0°F (48.8°C) that shuts down all heating sources within the unit when the supply air temperature is greater than or equal to this high supply temp limit.
- Minimum Temp Rise of 20.0°F for all furnaces.
Unit | Furnace | Bottom Discharge | Side Discharge |
---|---|---|---|
CASING SIZE | MBH | MAX TEMP RISE | MIN AIRFLOW CFM |
CFM
VPR-110
| 100| 100.0°F| 741| 60.0°F| 1,235
150| 100.0°F| 1,111| 60.0°F| 1,852
200| 100.0°F| 1,481| 60.0°F| 2,469
VPR-210
| 200| 100.0°F| 1,481| 60.0°F| 2,469
250| 100.0°F| 1,852| 60.0°F| 3,086
300| 100.0°F| 2,222| 60.0°F| 3,704
350| 100.0°F| 2,593| 60.0°F| 4,321
400| 100.0°F| 2,963| 60.0°F| 4,938
VPR-310
| 400| 100.0°F| 2,963| 60.0°F| 4,938
500| 100.0°F| 3,704| 60.0°F| 6,173
600| 100.0°F| 4,444| 60.0°F| 7,407
700| 100.0°F| 5,186| 60.0°F| 8,642
800| 100.0°F| 5,926| 60.0°F| 9,877
VPR-352 VX-352 VXE-352
| 600| 100.0°F| 4,444| 60.0°F| 7,407
800| 100.0°F| 5,926| 60.0°F| 9,877
1000| 100.0°F| 7,407| 60.0°F| 12,346
1200| 100.0°F| 8,889| 60.0°F| 14,815
VX-12
| 75| 100.0°F| 556| 100.0°F| 556
100| 100.0°F| 741| 100.0°F| 741
150| 100.0°F| 1,111| 100.0°F| 1,111
200| 100.0°F| 1,481| 100.0°F| 1,481
VX-112
| 100| 100.0°F| 741| 100.0°F| 741
200| 100.0°F| 1,481| 100.0°F| 1,481
300| 100.0°F| 2,222| 100.0°F| 2,222
VX-212
| 300| 100.0°F| 2,222| 100.0°F| 2,222
400| 100.0°F| 2,963| 100.0°F| 2,963
500| 100.0°F| 3,704| 100.0°F| 3,704
VX-312
| 600| 100.0°F| 4,444| 100.0°F| 4,444
800| 100.0°F| 5,926| 100.0°F| 5,926
1000| 100.0°F| 7,407| 100.0°F| 7,407
1200| 100.0°F| 8,889| 100.0°F| 8,889
Appendix C: Supply and Exhaust Airflow Calculations
If airflow monitoring for the outside air damper is installed it could be one of two types of airflow. Each type has their own calculations and/or setup.
Supply and Exhaust Fan Models
The following table shows the available models for the supply and exhaust fan
blades installed in a unit and the corresponding K Factor for the fan blade.
The third party needs to know the model number of the fan, how many fans are
installed, and whether the airflow monitoring station was purchased with the
supply and/or exhaust fans.
Supply and Exhaust Fan Models
Manufacturer| Model Number| Fan Blade Material| Fan Blade
Diameter| K Factor
Greenheck| QEP/APM15| Aluminum| 15”| 1296
Greenheck| QEP/APM16| Aluminum| 16”| 1537
Greenheck| QEP/APM 18| Aluminum| 18”| 1888
Greenheck| QEP/APM 20| Aluminum| 20”| 2253
Greenheck| QEP/APM 24| Aluminum| 24”| 3334
Greenheck| APD280| Aluminum| 280mm/11”| 739
Greenheck| APD315| Aluminum| 315mm/12.5”| 936
Greenheck| APD355| Aluminum| 355mm/14”| 1198
Greenheck| APD400| Aluminum| 400mm/16”| 1479
Greenheck| APD450| Aluminum| 450mm/18”| 1956
Greenheck| APD500| Aluminum| 500mm/20”| 2377
Greenheck| APD560| Aluminum| 560mm/22”| 3089
Greenheck| APD630| Aluminum| 630mm/25”| 3838
Greenheck| PRM-450| Aluminum| 450mm/18”| 1899
Greenheck| PRM-560| Aluminum| 560mm/22”| 2975
Greenheck| PDL-355| Aluminum| 355mm/14”| 1160
Ziehl-Abegg| ER35C| Steel| 350mm/14”| 1133
Ziehl-Abegg| ER45C| Steel| 450mm/18”| 1844
Ziehl-Abegg| ER50C| Steel| 500mm/20”| 2359
Ziehl-Abegg| ER56C| Steel| 560mm/22”| 2883
Supply and Exhaust Fan Airflow Measurement
The third-party controller can use the transducer’s signal from the supply fan
and/or from the exhaust fan and the airflow formula to determine the amount of
current airflow.
FORMULA: CFM = k * √(ΔP)
- ΔP = Differential Pressure (0.0-30.0 in. wc scaled from 0.0 to 10.0 VDC reading from transducer)
- k = K Factor (from table) * # of Fans
- √= Square Root
NOTE: The supply and exhaust airflow will be calculated separately. Only include the fans of the same type in the calculation.
Appendix D: Outside Air Damper Airflow Calculations
If airflow monitoring for the outside air damper is installed it could be one of two types of airflow. Each type has their own calculations and/or setup.
Outside AMD
The following table shows the unit casing and tonnage along with the model of
the AMD-23 that would be used with the optional purchase of airflow monitoring
of OAD. Select the proper Supply CFM Range to determine the values to use in
the calculation. The values are also available on the AMD.
NOTE: The operating range for the AMD damper is 300 to 2000 fpm. Airflows
outside of the operating range may not properly register
Outside AMD
Unit Casing| 110| 110| 210| 210| 310| 310|
352| 352
Supply CFM Range| < 2700| > 2700| < 5100| > 5100|
< 8300| > 8300| < 13700| > 13700
Area| 1.75 ft2| 2.33 ft2| 3.33 ft2| 4.72 ft2| 5.43 ft2| 7.67 ft2| 9.17 ft2|
12.22 ft2
K Factor| 2699| 2697| 2716| 2714| 2748| 2747| 2813| 2812
M Value| 0.477| 0.477| 0.477| 0.477| 0.477| 0.477| 0.477| 0.477
Transducer Range| 0 – 0.5”wc| 0 – 1”wc| 0 – 0.5”wc| 0 – 1”wc| 0 – 0.5”wc| 0 –
1”wc| 0 – 0.5”wc| 0 – 0.5”wc
Outside Air Damper Airflow Measurement
The third-party controller can use the transducer’s signal from the AMD for
the airflow formula to determine the amount of current airflow through the
OAD.
FORMULA: CFM = A K (P)M
- A = Area
- K = K Value
- P = Pressure
- M = M Value
GreenTrol Airflow Monitoring
The GreenTrol® airflow monitoring station measures airflow using advanced
thermal dispersion technology. An integral LCD display provides a local
indication of airflow measurement and device configuration. The GreenTrol also
accepts up to two airflow probes for averaging.
GreenTrol Airflow Monitor functions:
- LCD readout of measured airflow
- Dual airflow probe averaging
ANALOG OUTPUTS: The airflow monitoring controller has two configurable
analog outputs that transmit airflow, temperature, or PID control. They can be
configured for one of three analog output ranges: 0-10VDC, 0-5VDC, and
2-10VDC. The controller has been factory configured to use analog output 1 for
transmitting outdoor airflow rate and analog output 2 for outdoor air
temperature. The airflow monitoring output is wired to the customer terminal
strip for Heat-Cool Only controls. See the technical manual for the airflow
controller provided with the unit for instructions on configuring the analog
outputs and using the Field Calibration Wizard.
FORMULA : Calculating airflow based on the analog output signal:
Contact Us / More Information
Technical Support and Service
800-789-8550
support@doas.com
Valent Dedicated Outdoor Air Systems
60–28th Avenue North
Minneapolis, MN 55411
Main: 612-877-4800
More Information
Unit Schematics
For configuration and connection questions, see the schematics that shipped
with your unit. They can typically be found attached to the main control panel
door.
© 2021 Valent
Continuous product improvement is a policy of Valent; therefore, product
functionality and specifications are subject to change without notice. For the
most recent product information visit the product website.
Valent Heat-Cool Controller Part number: 484755 Rev. 3
December 2021