VALENT VX Series Remote Condensing Instruction Manual
- June 3, 2024
- VALENT
Table of Contents
- General Safety Information
- Product Overview
- Installation
- Typical Unit Weights and Dimensions
- Electrical and Refrigerant Entry Locations
- Piping and Refrigeration Information
- Control Center Components
- Controller Overview
- Start-Up Procedure
- Start-Up Checklist
- Troubleshooting
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
VALENT VX Series Remote Condensing
Please read and save these instructions for future reference. Read carefully before attempting to assemble, install, operate or maintain the product described. Protect yourself and others by observing all safety information. Failure to comply with these instructions will result in voiding of the product warranty and may result in personal injury and/or property damage.
Technical Support
Call: 1-800-789-8550
Email: support@doas.com
General Safety Information
Only qualified personnel should install and maintain this system. Personnel should have a clear understanding of these instructions and should be aware of general safety precautions. Improper installation can result in electric shock, possible injury due to coming in contact with moving parts, as well as other potential hazards. Other considerations may be required if high winds or seismic activity are present. If more information is needed, contact a licensed professional engineer before moving forward.
- Follow all local electrical and safety codes, as well as the National Electrical Code (NEC), the National Fire Protection Agency (NFPA), where applicable. Follow the Canadian Electrical Code (CEC) in Canada.
- All moving parts must be free to rotate without striking or rubbing any stationary objects.
- Unit must be securely and adequately grounded.
- Verify that the power source is compatible with the equipment.
- Never open access doors to the unit while it is running.
WARNING
To prevent electrocution, do not puncture the interior or exterior panels of
the roof.
DANGER
Always disconnect power before working on or near this equipment. Lock and tag
the disconnect switch or breaker to prevent accidental power up.
CAUTION
This unit is equipped with a compressed refrigerant system. If a leak in the
system should occur, immediately evacuate the area. An EPA Certified
Technician must be engaged to make repairs or corrections. Refrigerant leaks
may also cause bodily harm.
CAUTION
When servicing the unit, the internal components may be hot enough to cause
pain or injury. Allow time for cooling before servicing.
CAUTION
Condensing fans may operate when rooftop ventilator is not operating.
Product Overview
A remote condensing unit is configured to only be paired with a rooftop ventilator (model VX or VXE). The VX/VXE unit provides stand-alone control for the PDX operation. Remote condensing units have stand alone control of the condensing fans. The condensing fan controller will modulate the lead Electronically Commutated (EC) condensing fan and stage additional fan(s) to maintain head pressure. All units are designed for R410A refrigerant. Do not use tools or parts designed for other refrigerants.
Safety Listing
Models are ETL Listed.
Models and Capacities
Model
|
Cooling Capacity
---|---
RC-112
|
5 to 15 tons
RC-212
|
15 to 30 tons
Receiving
This product may have been subject to road salt during transit. If so, immediately wash off all visible white residue from all exterior surfaces. Upon receiving the product, check to ensure all line items are accounted for by referencing the delivery receipt or packing list. Inspect each crate or carton for shipping damage before accepting delivery. Alert the carrier if any damage is detected, do not refuse shipment. The customer shall make notation of damage (or shortage of items) on the delivery receipt and all copies of the bill of lading which should be countersigned by the delivering carrier. If damaged, immediately contact your manufacturer’s representative. Any physical damage to the unit after acceptance is not the responsibility of the manufacturer.
Handling
Units are to be rigged and moved by the lifting brackets provided. Location of brackets varies by model and size. Handle in such a manner as to keep from scratching or chipping the coating. Damaged finish may reduce ability of unit to resist corrosion.
Unpacking
Verify that all required parts and the correct quantity of each item have been received. If any items are missing, report shortages to your local representative to arrange for obtaining missing parts. Sometimes it is not possible that all items for the unit be shipped together due to availability of transportation and truck space. Confirmation of shipment(s) must be limited to only items on the bill of lading.
Storage
Units are protected against damage during shipment. If the unit cannot be
installed and operated immediately, precautions need to be taken to prevent
deterioration of the unit during storage. The user assumes responsibility of
the unit and accessories while in storage. The manufacturer will not be
responsible for damage during storage.
These suggestions are provided solely as a convenience to the user.
The ideal environment for the storage of units and accessories is indoors,
above grade, in a low humidity atmosphere which is sealed to prevent the entry
of blowing dust, rain, or snow. Units designed for outdoor applications may be
stored outdoors. All accessories must be stored indoors in a clean, dry
atmosphere.
Indoor
Maintain temperatures evenly to prevent condensation. Remove any accumulations
of dirt, water, ice, or snow and wipe dry before moving to indoor storage. To
avoid condensation, allow cold parts to reach room temperature. Leave
coverings loose to permit air circulation and to allow for periodic
inspection.
The unit should be stored at least 3½ in. (89 mm) off the floor. Clearance
should be provided to permit air circulation and space for inspection.
Outdoor
The unit should be placed on a level surface to prevent water from leaking into the unit. The unit should be elevated so that it is above water and snow levels. Ensure sufficient support to prevent unit from settling into soft ground. Locate parts far enough apart to permit air circulation, sunlight, and space for periodic inspection. To minimize water accumulation, place all unit parts on blocking supports so that rain water will run off. Do not cover parts with plastic film or tarps as these cause condensation of moisture from the air passing through heating and cooling cycles.
Inspection and Maintenance
While in storage, inspect units once per month. Keep a record of inspection and maintenance performed. If moisture or dirt accumulations are found on parts, the source should be located and eliminated. At each inspection, rotate the fan wheel by hand ten to fifteen revolutions to distribute lubricant on motor. If paint deterioration begins, consideration should be given to touch- up or repainting. Units with special coatings may require special techniques for touch-up or repair. Machined parts coated with rust preventive should be restored to good condition promptly if signs of rust occur. Immediately remove the original rust preventive coating with petroleum solvent and clean with lint-free cloths. Polish any remaining rust from surface with crocus cloth or fine emery paper and oil. Do not destroy the continuity of the surfaces. Wipe thoroughly clean with Tectyl® 506 (Ashland Inc.) or the equivalent. For hard to reach internal surfaces or for occasional use, consider using Tectyl® 511M Rust Preventive, WD-40® or the equivalent.
Removing from Storage
As units are removed from storage to be installed in their final location, they should be protected and maintained in a similar fashion until the equipment goes into operation. Prior to installing the unit and system components, inspect the unit assembly to make sure it is in working order.
- Check all fasteners, set screws on the fan, wheel, bearings, drive, motor base, and accessories for tightness.
- Rotate the fan wheel(s) by hand and assure no parts are rubbing.
Installation
Typical Unit Weights and Dimensions
Unit Size
|
L
|
W
|
H
|
Unit Weight (lbs.)
---|---|---|---|---
RC-112
|
115
|
46
|
67
|
815
RC-212| 121| 50|
71
|
905
All dimensions are shown in inches.
Service Clearances
A minimum of 48 inches above the condenser fans is acceptable, but unobstructed is strongly recommended.
Minimum Pad Dimensions
Unit Size
|
A
|
B
---|---|---
RC-112
|
120
|
50
RC-212
|
125
|
54
.
All dimensions are shown in inches
Lifting
WARNING
Spreader bars are required to prevent damage to the cabinet, failure to do so
can result in damage that is the installer’s responsibility.
-
Preparation of mounting location should be completed prior to lifting unit.
-
Before lifting, be sure that all shipping materials have been removed from unit.
-
To assist in determining rigging requirements, weights are provided in the Installation, Unit Typical Unit Weights and Dimensions section of this manual.
-
Unit must be lifted by all lifting lugs provided at top of unit.
-
Spreader bars must span the unit to prevent damage to the cabinet by the lift cables.
-
. Always test-lift the unit to check for proper balance and rigging before hoisting to desired location.
-
Never lift units in windy conditions.
Electrical and Refrigerant Entry Locations
Manufacturer recommends the electrical service be brought into the control center cabinet through the bottom, as shown.
-
Piping Locations RC-112
All dimensions shown are in inches. -
Piping Locations RC-212
Piping and Refrigeration Information
Both the remote condenser and the associated units are shipped with a nitrogen
holding charge of at least 5 psig. Relieve pressure prior to working on
unit.
Piping should be in accordance with accepted industry standards. Pipe work
should be supported independently of the coils. Undue stress should not be
applied at the connection to coil headers. Manufacturer is not responsible for
interconnecting piping.
Refrigerant lines shall be sized based on the Recommended Line Sizes table.
Consult the factory before changing line sizes. The vertical rise between the
unit and condensing unit must be less than 25 feet. The maximum equivalent
length of piping is 100 feet. Equivalent length must account for the combined
length of piping, elbows and fittings. Equivalent line lengths of common
elbows are shown in the Equivalent Lines Lengths table.
Piping Procedure
- Relieve nitrogen holding charge. If this charge is not present, check the system for leaks.
- Run interconnecting piping between main unit and condensing unit. Discharge line piping to be pitched in the direction of flow (1/2-inch per 10 feet of horizontal piping). Interconnected piping should be sized according to the Recommended Line Sizes table.
- Braze all connections under nitrogen purge.
- When the unit is located at a lower elevation than the condenser and the piping rise is over 20 feet, an oil drip leg must be field provided and installed at the bottom of the first rise in the discharge line. Install drip legs at the bottom of each rise over 10 feet.
- The discharge line must be insulated for safety due to high piping temperatures.
- The liquid line must be insulated if routed through areas where the temperatures are above the design outdoor air temperature to avoid a reduction in subcooling.
- The system must be pressure checked with a nitrogen charge of 475 psig. Hot gas reheat (optional) to be at 100% during pressure check. System must hold 475 psig for at least 30 minutes.
- The system must be evacuated to 500 microns or less. Hot gas reheat (optional) to be at 100% during evacuation. The pressure may increase a small amount, but must stabilize at a pressure below 500 microns.
- Charge the system to 10-12°F subcooling and adjust thermal expansion valve to maintain 7-9°F superheat. (Approximate charges are listed in the Approximate Charge table). Subcooling must be measured at the inlet of the expansion valve. Superheat must be measured at the outlet of the DX coil. Unit must be charged with the compressor(s) at 100% at the highest ambient possible. Hot gas reheat (optional) to be at 0% during charging.
- If the unit has hot gas reheat, cycle hot gas reheat valve to 100% for 5 minutes and then back to 0% and recharge the system to 10°F-12°F subcooling and adjust thermal expansion valve to maintain 7°F-9°F superheat.
- Additional oil may be needed dependent on interconnecting piping length. If the system contains more than 20 lbs. of refrigerant, an ounce of oil should be added for every 5 lbs. of refrigerant over 20 lbs. Use POE oil only.
Recommended Line Sizes
Tonnage
| Number of Circuits| Liquid Line| Discharge Line
---|---|---|---
Over 50 ft.| Under 50 ft.| Over 50 ft.| Under 50 ft.
RC-112| 5| 1| 1/2| 5/8
7.5| 1| 5/8| 3/4
10| 2| 1/2| 5/8
12.5| 2| 1/2| 3/4| 5/8
15| 2| 5/8| 3/4
RC-212| 15| 2| 5/8| 3/4
17.5| 2| 5/8| 3/4
20| 2| 5/8| 7/8| 3/4
25| 2| 3/4| 7/8| 3/4
30| 2| 3/4| 7/8| 3/4
All line sizes shown in inches.
Equivalent Line Lengths
Line Size
| Elbows| Tees
---|---|---
90º Long Radius| 45º Standard| Flow Through Branch
1/2| 1| 0.8| 3
5/8| 1.2| 0.85| 3.5
3/4| 1.4| 0.9| 4
7/8| 1.6| 1.1| 4.5
All equivalent lengths shown in feet.
Approximate Charge
Tonnage
|
Units with HGRH
|
Units without HGRH
|
Refrigerant Add/ Ft of Line
---|---|---|---
Circuit A (lbs.)
|
Circuit B (lbs.)
|
Circuit A (lbs.)
|
Circuit B (lbs.)
|
Circuit A (oz.)
|
Circuit B (oz.)
RC-112| 5| 23.0| –| 20.6| –| 1.1| –
7.5| 24.0| –| 21.6| –| 1.8| –
10| 13.4| 10.6| 11.0| 10.6| 1.1| 1.1
12.5| 14.6| 11.8| 12.2| 11.8| 1.1| 1.1
15| 18.3| 15.5| 15.9| 15.5| 1.8| 1.8
RC-212| 15| 22.5| 14.3| 14.7| 14.3| 1.8| 1.8
17.5| 22.5| 14.3| 14.7| 14.3| 1.8| 1.8
20| 29.0| 21.2| 21.2| 21.2| 1.8| 1.8
25| 29.0| 21.2| 21.2| 21.2| 2.6| 2.6
30| 30.8| 23.3| 23.0| 23.3| 2.6| 2.6
Factory-Installed Refrigeration System Components
Split DX Cooling with Three-Way Hot Gas Reheat and Hot Gas Bypass
-
Compressor
-
High Limit Pressure Switch
The switch opens when refrigerant pressure increases above the set point in the discharge line. A manual reset is then required. -
Service Access Ports
-
Hot Gas Reheat Valve (optional)
Units equipped with a reheat coil use a threeway valve with actuator to control the supply air discharge temperature of the unit during dehumidification mode. The unit controller provides a 0-10 VDC signal to control the amount of reheat to meet the supply temperature set point -
Hot Gas Reheat Coil (Optional)
-
Hot Gas Reheat Check Valve (Optional)
-
Discharge Line Check Valve
-
Condenser Fans
-
Condensing Coil
-
Liquid Receiver (Optional)
-
Pressure Sensor
-
Liquid Line Filter Drier
-
Liquid Line Solenoid Valve/Coil
-
Sight Glass
-
Thermostatic Expansion Valve (TXV)
Each unit is equipped with a TXV on each refrigerant circuit. The valve controls the flow of liquid refrigerant entering the evaporator coil by maintaining a constant, factory-set superheat of 10°F. The valve is adjustable and is located on the side of the evaporator coil and can be accessed through the coil access panel. -
Evaporator Coil
-
Low Limit Pressure Switch
The switch is installed on the suction line and disables the DX system when the suction pressure drops below the set point. The switch will auto reset when the pressure rises above the auto-reset set point. -
Hot Gas Bypass Manual Shut Off Valve (Optional )
Used to disable hot gas bypass for service and troubleshooting procedures. -
Hot Gas Bypass Valve (Optional)
On units equipped with hot gas bypass, hot gas from the compressor is injected into the liquid line of the evaporator coil after the TXV.
Valve Adjustment – To adjust the valve, connect a pressure gauge to the suction line and block the entering air to the evaporator coil. The valve should begin to open when the suction pressure drops to approximately 115 psig for R-410A (the valve will feel warm to the touch). Adjustments are made by first removing the cap on the bottom of the valve and then turning the adjusting stem clockwise to increase the setting pressure (counterclockwise to decrease). Allow several minutes between adjustments for the system to stabilize. When adjustment is complete, replace the cap on the valve.
Control Center Components
Main Control Center Components
Represents a typical installation for remote condenser.
Low Voltage Side
-
Head pressure control (see Appendix A: Condenser Controller)
-
Low voltage terminal strip
High Voltage Side -
Condenser fan motor contractors
-
Unit disconnect
-
Transformer
Controller Overview
See Appendix A: Condenser Controller on pages 14-15
Start-Up Procedure
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform
any service or maintenance, turn the electrical power to unit to OFF at
disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially
while standing on a ladder or other potentially unsteady base. Access panels
and unit components can be heavy and serious injury may occur.
CAUTION
Do not run unit during construction phase. Damage to internal components may
result and void warranty.
WARNING
- Unit was factory tested. All fans are set-up to run correctly when supplied power. If any one fan is running backwards immediately turn off the power. Switch two leads on the incoming power to the disconnect. This will ensure proper operation of the unit.
- Do not jumper any safety devices when operating the unit. This may damage components within or cause serious injury or death.
- DX system is charged with refrigerant. Start-up must be performed by EPA Certified Technician.
SPECIAL TOOLS REQUIRED
- Voltage Meter (with wire probes)
- Amperage Meter
- Pressure Gauges – refrigerant
- Tachometer
- Thermometer
Every installation requires a comprehensive start-up to ensure proper
operation of the unit. As part of that process, the following checklist must
be completed and information recorded. Starting up the unit in accordance with
this checklist will not only ensure proper operation, but will also provide
valuable information to personnel performing future maintenance. Should an
issue arise which requires factory assistance, this completed document will
allow unit experts to provide quicker resolve. Qualified personnel should
perform start-up to ensure safe and proper practices are followed.
Unit Model No. _____
Unit Serial No. ____
Compressor 1 Model No. __
Compressor 1 Serial No. _
Compressor 2 Model No. __
Compressor 2 Serial No. _
RC Model No. ____
RC Serial No. ___
Start-Up Date
Start-Up Personnel Name ____
Start-Up Company ____
Phone Number
Pre-Start-Up Checklist
- Disconnect and lock-out and tag all power switches.
- Check condensing fans for any damage or misalignment. Spin the blades to ensure they are free turning without any resistance and are not coming in contact with any parts.
- Check the tightness of all factory wiring connections.
- Check for proper mounting. o Look over the piping system. o Inspect condensing coil. Fins may get damaged in transit or during construction. Carefully straighten fins with a fin comb.
Start-Up Procedure
The unit will be in operational mode during start-up. Use necessary precautions to avoid injury. All data for the Start-Up Checklist must be collected while the unit is running.
- Make sure the Pre-Start-Up checklist is complete.
- Turn the disconnect on. Make sure all fans are rotating in the correct direction. The condensing fans will stage on based on pressure.
Voltage Imbalance
In a 3-phase system, excessive voltage imbalance between phases will cause motors to overheat and eventually fail. Maximum allowable imbalance is 2%. To determine voltage imbalance, use recorded voltage measurements in this formula.
Key :| V1, V2, V3 = line voltages as measured
VA (average) = (V1 + V2 + V3) / 3
VD = Line voltage (V1, V2 or V3) that
deviates farthest from average (VA)
---|---
Formula :| % Voltage Imbalance = [100 x (VA-VD)] /VA
Start-Up Checklist
Troubleshooting
Symptom
|
Possible Cause
|
Corrective Action
---|---|---
Motor over amps
| Motor voltage incorrect| Check motor wiring. Check motor nameplate versus
supplied voltage.
Shorted windings in motor| Replace motor.
Condensing fan not operating
| Low pressure in system| Check pressure in system.
Condensing fan relay not pulling in.
| Possible cause: Head pressure is low enough to only operate lead condensing fan. Connect gauges and verify pressure. Check coil voltage. Check relay for bent pin.
Replace.
Condenser fan motor defective.| Check fan motor.
Controller resets itself or is not on.| Check the supply voltage to the
controller at terminals G-G0. The board requires 24VAC.| ****
Check the 24VAC transformer in the control center.
Routine Maintenance
DANGER
Electric shock hazard. Can cause injury or death. Before attempting to perform
any service or maintenance, turn the electrical power to the unit to OFF at
disconnect switch(es). Unit may have multiple power supplies.
CAUTION
Use caution when removing access panels or other unit components, especially
while standing on a ladder or other potentially unsteady base. Access panels
and unit components can be heavy and serious injury may occur.
This unit requires minimal maintenance to operate properly. Maintenance
requirements for this model vary for each installation and depend greatly on
how much the system is used and the cleanliness of the air. Proper maintenance
will increase the life of the system and maintain its efficiency. Maintenance
must be performed by experienced technicians and in the case of refrigeration
systems, must be done by an EPA Certified Technician.
Maintenance frequency is based on a presumed nominal use of the system. If the
system is being run constantly, the frequency should be adjusted accordingly.
If there is seasonal debris in the air which can be drawn into the filters and
the coils, they should be checked more frequently. If the system is being used
for only a few hours per day, the frequency may be reduced. Use the
Maintenance Log at the end of this manual to record each maintenance session
and observations and then establish a maintenance schedule that is appropriate
for the installation.
Maintenance Frequency:
Semiannually
It is recommended that the annual inspection and maintenance occur at the
start of the cooling season. After completing the checklist, follow the unit
startup checklist provided in the manual to ensure the refrigeration system
operates in the intended manner.
-
Condensing Coils
Inspect for cleanliness clean as required -
Condensing Fan Blades and Motors
Inspect for cleanliness
Check all fasteners for tightness
Check for fatigue, corrosion and wear
Annually
-
Wiring Connections
Check all connections for tightness -
Cabinet
Check entire cabinet, inside and out, for dirt buildup or corrosion. Remove accumulated dirt, remove any surface corrosion and coat the area with appropriate finish.
Maintenance Procedures:
Coil Maintenance – Coils must be cleaned to maintain maximum performance.
Check coils once per year under normal operating conditions and if dirty,
brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand
more energy from the fan and create an environment for odor and bacteria to
grow and spread through the conditioned zone.
For coils with fragile fins or high fin density, foaming chemical sprays and
washes are available. Many coil cleaners use harsh chemicals, so they must be
used with caution by qualified personnel only. Care must be taken not to
damage the coils, including the fins, while cleaning. Caution: Fin edges are
sharp!
Appendix A: Condenser Controller
RC v1.03
Revision Date: 11/30/2021
The condenser controller offers improved control of the condenser pressure by
modulating the lead condensing fan and staging the additional condensing
fan(s).
Sequence of Operation
The condensing fans will be controlled to maintain the head pressure set point
based on the highest circuit pressure.
As the head pressure approaches the set point (325 psig) from the lower side,
the lead condensing fan will ramp up. Once the lead condensing fan has reached
100%, the next available condensing fan will be staged on and the lead
condensing fan will ramp down. If the lead condensing fan reaches 100% after
the second fan is on, the third condensing fan (optional) will stage on.
As the head pressure approaches the set point (325 psig) from the high side, the lead condensing fan will begin to ramp down. Once the lead condensing fan has reached minimum speed, the third condensing fan (optional) will be staged off and the lead condensing fan will ramp up. If the lead condensing fan reaches minimum speed after the third condensing fan is off, the second condensing fan will stage off.
Display Use
The condenser controller is located on the control panel of the condenser. The face of the controller has six keys, allowing the user to view condenser conditions and alter parameters. The condenser controller is pre-programmed with easy to use menus. To change the display contrast, hold the Enter and Escape button while pressing the Up and Down arrows.
Keypad Description
| Alarm| Button will blink red, indicating an alarm condition. Press to
review current alarms. To review previous alarms, access the DATA LOGGER
through the main menu.
| Down Arrow|
The arrow keys allow the user to scroll through different screens and adjust parameters.
| Up Arrow
| Enter| A. In screens with adjustable parameters, pressing the Enter key
moves the cursor from the upper left corner of the screen to the parameter.
The arrow keys can then be used to adjust the parameter.
B. To move to the next parameter on the same screen, press the Enter
button.
C. To save the change, press the Enter button until the cursor moves back
to the upper left corner of the screen.
| Escape| Allows the user to exit the current menu, jumping to the Main Menu.
| Program| Pressing the Prg (Program) button allows the user to enter the Main
Program Menu.
Main Menu Overview
The condenser controller will revert to the default main menu screen. This screen includes basic information on the configuration of the controller as well as a series of shortcuts in the bottom right corner. The shortcuts include Monitoring Menu “Monitor”, Setpoint menu “Set”, Info Menu “Info” and Condenser On/Off “On/Off”. Scroll through the shortcuts by using the Up and Down keys. Enter the menu by pressing the Enter key.
THE INITIAL M ENU SCREEN DISPLAYS THE PROGRAM VERSION, CONFIGURATION CODE AND STATUS LINE. THE STATUS LINE DISPLAYS WHICH M ODE THE CONDENSER IS IN.
Possible modes include:
- Off by Keypad
- Condenser On
- Remote Off
- Active Alarm
- Override Enabled
Note : Scroll up and down on the main menu to access quick menu options. Options include: monitoring, set point, information and on/off.
A. On/Off
The On/Off menu allows the user to view the detailed On/Off status of the
controller.
The condenser ships from the factory in a disabled state. To allow the
condenser to operate, the condenser must be enabled in the condenser On/Off
menu. Actual State: The controller may be in following On/Off states:
a. Condenser On
b. Off by Keypad
c. Remote Off
Change to (Switch Off/Switch On): Enables the user manually turn the
condenser On/Off via display.
Note : Unit terminal R and G must be jumpered in order to enable the
condenser.
B. Monitor
The Monitor menu allows the user to view the current status of the unit.
The Status screen displays real time conditions from the sensors located in
the unit.
C. Setpoint
The Setpoint menu allows the user to view and adjust parameters.
This screen displays the active pressure set point.
When operating, the controller will control the condensing fans to maintain
the active pressure set point.
D. Information
The Information menu allows the user to view the current program in the controller
The information menu allows the user to view all pertinent information on the
current program that is in the controller
Code : The controller setup code determines functionality of program.
When contacting the factory, please reference this code.
Ver : Displays the current program version and data code of the current
program.
Manual : The manufacturer part number for the corresponding Installation,
Operation and Maintenance (IOM) Manual.
OS : Indicates to the user which Operating System/Firmware has been
installed on the controller.
Contact Us
Technical Support and Service
800-789-8550
support@doas.com
Valent Dedicated Outdoor Air Systems
60–28th Avenue North
Minneapolis, MN 55411
Main: 612-877-4800
More Information
Unit Schematics
For configuration and connection questions, see the schematics that shipped
with your unit. They can typically be found attached to the main control panel
door.
Mechanical and Controls Manuals
Find current mechanical and controls manuals here:
www.valentair.com/resources
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>