LG LMU303HV 30000 BTU Multi F Inverter Heat Pump Owner’s Manual
- June 13, 2024
- LG
Table of Contents
Air Conditioning Technologies
SERNICE TECHNOTE
LMU303HV 30000 BTU Multi F Inverter Heat Pump
STN Number: | 64 |
---|---|
Date Issued: | October 16, 2023 |
Action: | Service |
Distribution:
☒ LG Applied Representatives ☒ LG Distributors ☒ Contractor/Installers
Subject:
Multi F Software Update (Drain pan heater operation)
Affected Product(s): | Multi Zone Outdoor (Multi F) |
---|---|
Applicable Models: | LMU303HV |
LMU363HV
Affected Date(s):| 05/2022 (SN 205) through 11/2022 (SN 211)
Description:
Drain pan heater function logic update.
Information:
In the event that the optional drain pain heater does not consistently provide
heat, follow the steps below to update the software.
Multi F outdoor software update procedure:
- Confirm equipment information matches affected models
- Program software instructions
Confirm affected outdoor unit model number, including inverter printed circuit board part number, are correct before updating software.
Outdoor Unit Model Number | Inverter Printed Circuit board Part Number |
---|---|
A4UW30GFA3 (LMV303HV) | EBR30300203 |
A4UW36GFA3 (LMU363HV) | EBR84691034 |
Software File Name (Software file is the same for all listed outdoor models)
4_5kW_A4UW36GFA3_A4UW30GFA3_225B_9196040B_221207.hex
Prepare all necessary equipment and tools to upload software
a. Stickwriter
b. Short Key
c. Onboarding software
d. Screwdriver
ODU PCBA Location
Remove side panel
Short key on PCBA (CN_FLASH)
Stickwriter connection on PCBA (CN_LGMV port)
1. Stick Writer
No. | Name | Explanation |
---|---|---|
1 | Power Switch | Power On/Off Switch (up — power on, down — power off) |
2 | 4Pin dip s/w | Setting of comm. Speed, Verifying or not |
3 | Confirm button | onboarding SW selection and onboarding start |
4 | 5Pin recharging | 5Pin charging terminal for internal battery charging |
5 | Micro SD card Slot | Micro SD card slot for storing onboarding files and |
settings files
6| USB 2.0 port| USB 2.0 port is charging terminal for internal battery
charging
After checking firmware Update message, press select button to scroll through firmware options.
Select Model [4_5kW_A4UW36GFA3A4UW30GFA3 225B_9196040B_221207] Press the select button for 5 seconds, the “Model” changes to “Selected”
-
Power Off Air conditioning unit to be updated
(※ If the power is not cut off, the PCB and onboarding JIG can be damaged) -
Insert Short key on PCBA (CN_FLASH)
-
Connect Stickwriter Connection cable on PCBA (CN_LGMV port)
-
Press the select button once in the selected file of the onboarding stickwriter
-
The stickwriter displays the onboarding progress status. Confirm the word ”Complete” is displayed after successful onboarding.
-
Remove Short key and stickwriter Connection cable
-
Reassemble outdoor unit side panel
-
Power up outdoor unit
-
Check the PCB Software version (Using LGMV)
-
Onboarding process is now complete.
STN 644 – Multi F Software Update (Drain pan heater operation)
©2023 LG Electronics U.S.A., Inc. All rights reserved.
Documents / Resources
| LG
LMU303HV 30000 BTU Multi F Inverter Heat
Pump
[pdf] Owner's Manual
LMU303HV 30000 BTU Multi F Inverter Heat Pump, LMU303HV, 30000 BTU Multi F
Inverter Heat Pump, Multi F Inverter Heat Pump, Inverter Heat Pump, Heat Pump,
Pump
---|---
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>