NIBE F2050 Air Water Heat Pump Instruction Manual

June 13, 2024
NIBE

NIBE F2050 Air Water Heat Pump

NIBE-F2050-Air-Water-Heat-Pump

Product Information

  • Product Name: Air/water heat pump NIBE F2050
  • Model Number: IHB EN 2318-2 631411

Table of Contents

  • Important information
  • Safety information
  • Symbols and Marking  Service
  • Temperature sensor data
  • Serial number
  • Disturbances in comfort
  • Inspection of the installation
  • Troubleshooting
    • Compatible indoor modules and control modules
    • Alarm list
    • Accessories
    • Technical data
    • Dimensions
    • Delivery and handling
    • Sound level
    • Transport
    • Technical specifications
    • Assembly
    • Energy labelling
    • Condensation
    • Electrical circuit diagram
    • Supplied components
    • Dismantling panels
    • Item register
    • The heat pump design
    • Contact information
    • General
    • Electrical connection
    • Sensor placement
    • Pipe connections
    • Electrical connections
    • Commissioning and adjusting
    • Control
    • Heat pump EB101

Product Usage Instructions

  1. Safety information: This product should be installed and serviced by specialists. The user manual must be kept with the customer for reference.

  2. Marking: The product’s label may contain important symbols. Make sure to read the user manual for proper usage.

  3. Serial number: The serial number for the F2050 can be found on the side of the foot.

  4. Inspection of the installation:
    Before commissioning the heating installation, it should be inspected by a qualified person. Fill in the installation data in the user manual.

  5. Compatible indoor modules and control modules:
    The NIBE F2050 is compatible with various indoor modules and control modules. Refer to the table for compatibility details.

  6. Troubleshooting:
    In case of disturbances in comfort, refer to the troubleshooting section for assistance.

  7. Accessories:
    Check the accessories section for additional components that can be used with the product.

  8. Technical data:
    Detailed technical specifications and dimensions can be found in the technical data section.

  9. Delivery and handling:
    Follow the instructions for proper handling and transport of the product.

  10. Assembly:
    Refer to the assembly section for step-by-step instructions on how to assemble the product.

  11. Electrical connections:
    Follow the guidelines for proper electrical connections and ensure accessibility for maintenance.

  12. Commissioning and adjusting:
    Prepare the product for startup by filling and venting. Follow the instructions for compressor heater, start-up, inspection, readjusting, and charge flow adjustment.

  13. Control
    Heat pump EB101:
    Refer to the control section for information on operating the heat pump using the EB101 control module. Please refer to the user manual for detailed instructions and further information on
    specific topics.

Installer manual

Air/water heat pump NIBE F2050
IHB EN 2318-2 631411

Table of Contents

1 Important information

4

F-series ­ VVM / SMO

33

Safety information Symbols Marking

4

4 8 Service

34

4

Temperature sensor data

34

Serial number

4 9 Disturbances in comfort

35

Inspection of the installation

5

Troubleshooting

35

Compatible indoor modules and control mod-

ules

6

Alarm list

36

Indoor module Hydrobox

6 10 Accessories

38

6

Control module

6 11 Technical data

39

Dimensions

39

2 Delivery and handling

7

Sound levels

40

Transport

7

Technical specifications

41

Assembly

7

Energy labelling

44

Condensation

9

Electrical circuit diagram

47

Supplied components

10

Dismantling panels

11 Item register

51

3 The heat pump design

13 Contact information

55

General

13

Electrical connection

17

Sensor placement

19

4 Pipe connections

22

General

22

Symbol key

22

Pipe coupling heating medium circuit

22

Installation alternative

23

5 Electrical connections

24

General

24

Accessibility, electrical connection

24

Connections

25

6 Commissioning and adjusting

30

Preparations

30

Filling and venting

30

Compressor heater

30

Start-up and inspection

31

Readjusting, heating medium side

31

Adjustment, charge flow

31

7 Control – Heat pump EB101

32

S-series ­ VVM S / SMO S

32

NIBE F2050

Table of Contents 3

Important information

Safety information
This manual describes installation and service procedures for implementation by specialists. The manual must be left with the customer.
Symbols
Explanation of symbols that may be present in this manual.
NOTE
This symbol indicates danger to person or machine.

Marking
Explanation of symbols that may be present on the product’s label(s).
Fire hazard!
Read the User Manual.
Read the User Manual.
Read the Installer Manual.

Caution
This symbol indicates important information about what you should consider when installing or servicing the installation.

Serial number
The serial number for F2050 can be found on the side of the
foot.

TIP
This symbol indicates tips on how to facilitate using the product.

DATA

Caution
You need the product’s (14 digit) serial number for servicing and support.

4 Chapter 1 | Important information

NIBE F2050

Inspection of the installation
Current regulations require the heating installation to be inspected before it is commissioned. The inspection must be
carried out by a suitably qualified person. Fill in the page for information about installation data in the User manual.

Description

Notes

Signature Date

Heating medium (page 22) System flushed System vented Particle filter Shut-off and drain valve Charge flow set
Electricity (page 24) Fuses property Safety breaker Earth circuit-breaker Heating cable type/effect Fuse size, heating cable (F3) Communication cable connected F2050 addressed (only when cascade connection) Connections Main voltage Phase voltage When installing F2050-6, check that the software version of the indoor module/control module is at least v8320.
Miscellaneous

NIBE F2050

Chapter 1 | Important information 5

Compatible indoor modules and control modules

F2050-6 F2050-10

SMO S40 X X

VVM S320 X X

VVM S330 X X

F2050-6 F2050-10

VVM 225 X X

VVM 310 X X

VVM 500 X X

SMO 20 X X

SMO 40 X X

Indoor module

VVM S320
Stainless steel, 3×230 V Part no. 069 201

VVM S320
Enamel, 3×400 V Part no. 069 206

VVM S320
Stainless steel, 3×400 V Part no. 069 196

VVM S330
Stainless steel, 1 x 230 V Part no. 069 249

VVM S330
Stainless steel, 3 x 400 V Part no. 069 250

Control module
SMO S40
Control module Part no. 067 654
SMO 20
Control module Part no. 067 224
SMO 40
Control module Part no. 067 225

MHB 05 X X

VVM 225
Enamel (DK), 3×400 V Part no. 069 228
VVM 225
Stainless steel, 3×400 V Part no. 069 229
VVM 310
Stainless steel, 3×400 V With integrated EMK 310 Part no. 069 084

VVM 225
Enamel, 3×400 V Part no. 069 227
VVM 310
Stainless steel, 3×400 V Part no. 069 430
VVM 500
Stainless steel, 3×400 V Part no. 069 400

Hydrobox
MHB 05
Part no. 067 942

6 Chapter 1 | Important information

NIBE F2050

Delivery and handling

Transport
F2050 should be transported and stored vertically in a dry place.
NOTE
Ensure that the heat pump cannot fall over during transport.
Check that F2050 has not been damaged during transport.
LIFT FROM THE STREET TO THE SET UP LOCATION
If the surface allows, the easiest method is to use a pallet truck to move the heat pump to the installation area.
If the heat pump needs to be transported across soft ground, such as a lawn, we recommend using a crane truck that can lift it to the installation location. When the heat pump is lifted with a crane, the packaging must be intact. If a crane truck cannot be used, the heat pump can be transported on an extended sack truck. The heat pump must be taken hold of from its heaviest side and two people are required to lift it.
LIFT FROM THE PALLET TO FINAL POSITIONING
Before lifting remove the packaging and the securing strap to the pallet. Place lifting straps around each foot. It is recommended that two people perform the lift from the pallet to the base.
SCRAPPING
When scrapping, remove the heat pump in reverse order. In this case, lift by the base plate rather than the pallet!
Assembly
· Place the heat pump in a suitable location outdoors to prevent any risk of the refrigerant flowing in through ventilation openings, doors or similar openings in the event of a leak. It must also not constitute a hazard to people or property in any other way.
· If the heat pump is placed in a location where any refrigerant leak could accumulate, for example below ground level (in a dip or low-lying recess), the installation must satisfy

the same requirements that apply for gas detection and the ventilation of engineering rooms. Requirements regarding sources of ignition must be applied where appropriate.
· Place F2050 outdoors on a solid level base that can take the weight, preferably a concrete foundation. If concrete slabs are used they must rest on asphalt or shingle.
· The lower edge of the evaporator must not be lower than the level of the average local snow depth, or at least 300 mm above ground level. The base should be at least 70 mm tall.
· F2050 should not be positioned next to noise sensitive walls, for example, next to a bedroom.
· Also ensure that the placement does not inconvenience the neighbours.
· F2050 must not be placed so that recirculation of the outdoor air is possible. Recirculation entails reduced power and impaired efficiency.
· The evaporator must be sheltered from direct wind / , which negatively affects the defrosting function. Place F2050 protected from wind / against the evaporator.
· Large amounts of condensation, as well as melt water from defrosting, may be produced. Condensation must be led off to a drain or similar (see section “Condensation water”).
· Care must be exercised so that the heat pump is not scratched during installation.

Min. 30m0inm3m00 mm

LEK

LEK

Do not place F2050 directly on the lawn or other non solid surface.

NIBE F2050

Chapter 2 | Delivery and handling 7

If there is a risk of snow slip from roof, a protective roof or cover must be erected to protect the heat pump, pipes and wiring.

8 Chapter 2 | Delivery and handling

NIBE F2050

INSTALLATION AREA
The distance between F2050 and the house wall must be at least 150 mm, but not more than 500 mm in locations that are exposed to the wind. The free space above F2050 must be at least 1,000 mm. The free space in front must be at least 1,000 mm for any future servicing.
FFrrietteustrpymacmeebbeahkoinmd*

150 mm

400 mm

600 mm

600 mm

3000 mm

FMreineimsapltace fritt utrymme

FFfrrraeitmteufsötrrpyamfcrmeoenint 1000 mm

Min. dMiisnt. aanvscteånwdhen using sevevraidl aFn2v0ä5nd0ning
av flera F2040

FMreineimsapltace fritt utrymme

  • The space behind must not exceed 500 mm in locations that are exposed to the wind.

Condensation
The condensate drain pan collects and leads away the condensation water.
NOTE
It is important to the heat pump function that condensation water is led away and that the drain for the condensation water run off is not positioned so that it can cause damage to the house.
Condensation run-off should be checked regularly, especially during the autumn. Clean if necessary.
· The condensation water (up to 50 litres / 24 hrs) must be routed away by a pipe to an appropriate drain, it is recommended that the shortest outdoor length possible is used.
· The section of the pipe that can be affected by frost must be heated by the heating cable to prevent freezing.

DRAIN PAN HEATER, CONTROL
The drain pan heater is supplied with power when one of the following conditions is met: 1. The compressor has been in operation for at least 30
minutes after last start. 2. The ambient temperature is lower than 1 °C.
DRAINAGE OF CONDENSATION
Caution
If none of the following recommended alternatives is used, good drainage of condensation must be provided.
Stone caisson

TIP
Pipe with heating cable for draining the condensation water trough is not included.

TIP
To ensure this function, the accessory KVR should be used.

Frost proof Frostfridttedpjtuhp

· Route the pipe downward from the heat pump.
· The outlet of the condensation water pipe must be at frost free depth.
· Use a water trap for installations where air circulation may occur in the condensation water pipe.
· The insulation must seal against the bottom of the condensation water trough.

LEK
If the house has a cellar the stone caisson must be positioned so that condensation water does not affect the house. Otherwise the stone caisson can be positioned directly under the heat pump.

NIBE F2050

Chapter 2 | Delivery and handling 9

Gutter drainage

LEK

FroFsrotstpfrritot of dedjpupth

Water seal

Route the pipe sloping downward from the heat pump. The condensation water pipe must have a water seal to prevent air circulation in the pipe.
Supplied components

1 x filterball (G1″) (QZ2)

LEK
2 x flexible pipes (DN25, G1″) with 4 x gaskets

10 Chapter 2 | Delivery and handling

NIBE F2050

Dismantling panels
DISMANTLING TOP PANEL F2050-6
UN
F2050-10

LEK

NIBE F2050

Chapter 2 | Delivery and handling 11

REMOVING THE FRONT PANEL F2050-6
UN
F2050-10

LEK

12 Chapter 2 | Delivery and handling

NIBE F2050

The heat pump design

General
F2050-6

QA40

PWB1

F

TB

AA23

QN2 20S

EP1 GQ1 FM01

DH EB11

UN

BT12
HS1 EP2 BT15 RF2 QM36 QM37 PF3 RF3

GQ10 CM

UB3

DATA

PF3 PF1

BT16 Tho-R1

BT16 Tho-R1

BT28 Tho-A

UB1

UB2

XELCB1H10

QN1 SM2

XL2

W1

DATA

UB3

NIBE F2050

Chapter 3 | The heat pump design 13

BT14 Tho-D

BT12

GQ10 CM

BT28 Tho-A

EB10 QN1 CH SM2

BP4 QN2 20S
QN1 HS1 BT15 EP2
BT3 QM36 QM37

QN3 BT17

UB3

14 Chapter 3 | The heat pump design

NIBE F2050

LEK LEK

F2050-10
QA40 EP1 GQ1 FM01
DH EB11

DATA

BT16

PF3

PF1 Tho-R1 Tho-R2

PWB2 BT14 Tho-D PWB3 PWB1

F

TB

QN2 20S

AA23

BT12

BP1 X1 BP2

63H1 LPT

BP4

EP2 BT17 Tho-S

BT3

QN3 SM1

BT15

HS1

QM36 QM37

PF3

GQ10 CM

QN1 SM2

EB10 CH

BT28 Tho-A

UB1 UB2 XL1

UB3 W1

XL2

DATA

UB3 LEK

NIBE F2050

Chapter 3 | The heat pump design 15

Pipe connections

XL1

Heating medium connection, supply (from F2050)

XL2

Heating medium connection, return (to F2050)

Sensors etc.

BF1

Flow meter

BP1 (63H1) High pressure pressostat

BP2 (LPT)

Low pressure transmitter

BP8

Low pressure transmitter

BP9

High pressure sensor

BT3 (Tho-W1) Temperature sensor, return

BT12 (Tho-W2) Temperature sensor, condenser supply line

BT14 (Tho-D) Temperature sensor, hot gas

BT15 (Tho-L) Temperature sensor, fluid pipe

BT16 (Tho-R1) Temperature sensor 1, evaporator

BT16 (Tho-R2) Temperature sensor 2, evaporator

BT17 (Tho-S) Temperature sensor, suction gas

BT28 (Tho-A) Temperature sensor, ambient

Miscellaneous

PZ1

Type plate

PZ3

Serial number

UB1

Cable gland, incoming supply

UB2

Cable grommet, communication

UB3

Cable gland, heating cable (EB14)

UB4

Cable grommet, fan

Designations according to standard EN 81346-2. Designations within brackets according to the supplier’s standard.

Electrical components

AA23

Communication board

AA23-F3

Fuse for external heating cable

AA23-S3

DIP switch, addressing of outdoor module

AA23-X1

Terminal block, KVR

AA23-X4

Terminal block, communication from indoor module

AA23-X100 Terminal block, communication outdoor module

EB10 (CH)

Compressor heater

EB11 (DH)

Drip tray heater

F

Main fuse compressor unit

GQ1 (FM01) Fan

(PWB1)

Control board

(PWB2)

Inverter board

(PWB3)

Filter board

QA40

Inverter

RF2

EMC filter for inverter

(TB)

Terminal block, incoming supply and communica-

tion with board AA23

X1

Terminal block, incoming supply

Cooling components

EP1

Evaporator

EP2

Condenser

GQ10 (CM) Compressor

HS1

Drying filter

QM36

Shut-off valve, liquid line

QM37

Shut-off valve, gas line

QN1 (SM2)

Expansion valve, heating and cooling

QN2 (20S)

4-way valve

QN3 (SM1)

Expansion valve, cooling

16 Chapter 3 | The heat pump design

NIBE F2050

Electrical connection
F2050-6
AA23-X100 AA23
AA23-S3 AA23-X4
AA23-F3
LEK
AA23-X1

F2050-10
AA23-X100

AA23

AA23-S3 AA23-X4
AA23-F3 AA23-X1
LEK

RF2 PWB2
PWB1
UN

LEK

PWB3

TB PWB3

PWB2

PWB1

TB

NIBE F2050

Chapter 3 | The heat pump design 17

Electrical components

AA23

Communication board

AA23-F3

Fuse for external heating cable (250 mA), max 45 W.

AA23-S3

DIP switch, addressing of outdoor unit

AA23-X1

Terminal block, KVR

AA23-X4

Terminal block, communication from indoor module

AA23-X100 Communication with TB

EB10 (CH)

Compressor heater

EB11 (DH)

Drip tray heater

F

Main fuse compressor unit

GQ1 (FM01) Fan

(PWB1)

Control board

(PWB2)

Inverter board

(PWB3)

Filter board

RF2

EMC-filter

(TB)

Terminal block, incoming supply and communica-

tion with board AA23

X1 (TB1)

Terminal block, incoming supply

X2 (TB2)

Terminal block, communications

X1

Terminal block, power supply

Designations according to standard EN 81346-2. Designations within brackets according to the supplier’s standard.

18 Chapter 3 | The heat pump design

NIBE F2050

Sensor placement
CONNECTION TO BOARD (PWB1)

F2050-6

GQ1

QN1

QN2

FM01 EEV

20S

BT16 BT14 BT28 Tho-R1 Tho-D Tho-A

EB11 DH

UN

NIBE F2050

Chapter 3 | The heat pump design 19

F2050-10
PWB1

BP1 63H1

EB10 CH

QN2 20S

EB11 DH

GQ1

QN3 QN1

BP2

FM01 SM1 SM2 LPT

LEK
CONNECTION TO BOARD (AA23)
BP4 BT15 BT12 BT3
AA23-S3

20 Chapter 3 | The heat pump design

NIBE F2050

SENSOR PLACEMENT IN F2050 Outdoor module F2050-6
Incoming supply

Outdoor module F2050-10
kW
InkcW oming supply
Defrost/Cooling

BE1 (CT) BF1 BP1 (63H1) BP2 (LPT) BT3 (Tho-W1)
BT12 (Tho-W2) BT14 (Tho-D) BT15 (Tho-L) BT16 (Tho-R1) BT16 (Tho-R2) BT17 (Tho-S) BT28 (Tho-A) EB10 (CH) EB11 (DH) EP2 GQ1 (FM01) GQ10 (CM) HS1 QN1 (SM2) QN2 (20S) QN3 (SM1)

Current sensor Flow meter High pressure pressostat Low pressure transmitter Temperature sensor, heating medium return line Temperature sensor, condenser supply line Temperature sensor, hot gas Temperature sensor, fluid pipe Temperature sensor, heat exchanger, 1 Temperature sensor, heat exchanger, 2 Temperature sensor, suction gas Temperature sensor, ambient Compressor heater Drip tray heater Condenser Fan Compressor Drying filter Expansion valve, heating 4-way valve Expansion valve, cooling

Designations according to standard EN 81346-2. Designations within brackets according to the supplier’s standard.

NIBE F2050

Chapter 3 | The heat pump design 21

Pipe connections

General
Pipe installation must be carried out in accordance with current norms and directives.
MINIMUM SYSTEM FLOWS
NOTE
An undersized climate system can result in damage to the product and lead to malfunctions.

SYSTEM DIAGRAM
System principles with hot water and heating system.

– EB1 0 1 – FL1 0

XL1

– EB1 0 1 – QM 4 0

XL2

– EB1 0-1E-BR1M011 – QZ2

– EB1 0 1 – QM1

Each climate system must be dimensioned individually to provide the recommended system flows.

The installation must be dimensioned to provide at least the minimum defrosting flow at 100 % circulation pump operation.

Air/water heat Minimum flow

pump

during defrost-

ing

100% circula-

tion pump op-

eration (l/s)

F2050-6 0.19
F2050-10

Minimum recommended pipe dimen-
sion (DN) 20

Minimum recommended pipe dimen-
sion (mm) 22

F2050 can only operate up to a return temperature of about 55 °C and an outgoing temperature of about 58 °C from the heat pump.

F2050 is not equipped with shut-off valves on the heating medium side, rather these must be installed to facilitate any future servicing. The return temperature is limited by the return line sensor.

WATER VOLUMES
When docking with F2050 free flow in the climate system is recommended for correct heat transfer. This can be achieved by use of a bypass valve. If free flow cannot be ensured, it is recommended that a buffer tank (NIBE UKV) is installed.

Following water volumes are recommended

F2050

-6

-10

Minimum volume, climate system during 20 l

50 l

heating/cooling

Minimum volume, climate system during 50 l

80 l

under floor cooling

NOTE
The pipe installation must be flushed out before the heat pump is connected so debris cannot damage component parts.

XL1

Heating medium connection, supply (from F2050)

XL2

Heating medium connection, return (to F2050)

Symbol key
Symbol Meaning Shut-off valve

Tapping valve

Non-return valve Circulation pump Expansion vessel

Filterball

P

Pressure gauge

Safety valve

Reversing valve/shunt

Control module

Domestic hot water

Outdoor module

Water heater

Heating system

Pipe coupling heating medium circuit
You can find a list of compatible products in the section
“Compatible indoor modules and control modules”.

22 Chapter 4 | Pipe connections

NIBE F2050

Caution
There is a difference between connection to a control module compared with connection to an indoor module. See the Installer Manual for the indoor module/control module.
Vent the heat pump by the “heating medium supply” connection (XL1) using the venting nipple on the enclosed flexible hose. Install as follows: · expansion vessel · pressure gauge · safety valves · drain valve
For draining the heat pump during prolonged power failures. · non-return valve Installations with only one heat pump: a non-return valve is only required in those cases where the placement of the products in relation to each other can cause self-circulation. Cascade installations: each heat pump must be fitted with a non-return valve. · charge pump · shut-off valve To facilitate any future servicing. · enclosed filterball (QZ2) Installed before connection “heating medium return” (XL2) (the lower connection) on the vacuum pump. · reversing valve. When connecting to the control module, and if the system is to be able to work with both the climate system and the hot water heater.
XL1
P
XL2

CHARGE PUMP
The charge pump (not included in the product) is powered and controlled from the indoor module/control module. It has a built-in frost protection function and, for this reason, must not be switched off when there is a risk of freezing.

At temperatures below +2 °C the charge pump runs periodically, to prevent the water from freezing in the charge circuit. The function also protects against excess temperatures in the charge circuit.

PRESSURE DROP, HEATING MEDIUM SIDE

Pressure drop (kPa) 30
25

1100

66

20

15

10

5
0 0,0 0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8
Flow l/s

PIPE CONNECTIONS FLEX HOSE
All outdoor pipes must be insulated with at least 19 mm thick pipe insulation.
The supplied flexible hoses act as vibration dampers. The flexible pipes are fitted so an elbow is created, thus acting as vibration damping.
Installation alternative
F2050 can be installed with indoor module or control module. The necessary safety equipment must be installed in accordance with current regulations for all docking options.
The necessary safety equipment must be installed in accordance with current regulations for all of the installation options.
See nibe.eu for more installation options.
CONNECTING ACCESSORIES
Instructions for connecting accessories can be found in the installation instructions provided for each accessory. See section Accessories for a list of the accessories that can be used with F2050.

The image shows connection to the control module.

NIBE F2050

Chapter 4 | Pipe connections 23

Electrical connections

General
· Electrical installation and wiring must be carried out in accordance with national provisions.
· Prior to insulation testing the house wiring, disconnect the air/water heat pump installation.
· If a miniature circuit breaker is used, this must have at least triggering characteristic “C”. See section “Technical specifications” for fuse size.
· If the building is equipped with an RCD, F2050 must be equipped with a separate one.
· F2050 must be installed via an isolator switch. The cable area has to be dimensioned based on the fuse rating used.
· The RCD should have a nominal tripping current of no more than 30 mA. The incoming supply must be 230V~ 50Hz via an electrical distribution unit with fuses.
· The routing of cables for heavy current and signals should be made out through the cable glands on the heat pump’s right-hand side, seen from the front.
· The communication cable must be a screened cable with three conductors.
· Connect the charge pump to the control module. See where the charge pump is to be connected in the Installer Manual for your control module.

NOTE
Do not start the system before filling up with water. Components in the system could be damaged.
NOTE
To prevent interference, sensor cables to external connections must not be laid close to high voltage cables.
Accessibility, electrical connection
See section “Dismantling panels”.

NOTE
Electrical installation and any servicing must be carried out under the supervision of a qualified electrician. Disconnect the current using the circuit breaker before carrying out any servicing.

NOTE
Check the connections, main voltage and phase voltage before the product is started, to prevent damage to the heat pump electronics.

NOTE
The live external control must be taken into consideration when connecting.

NOTE
If the supply cable is damaged, only NIBE, its service representative or similar authorised person may replace it to prevent any danger and damage.

24 Chapter 5 | Electrical connections

NIBE F2050

Connections

POWER CONNECTION
Incoming supply cable (W1) is enclosed and connected to terminal block X1 at the factory. Outside the heat pump there is approx. 1.8 m of cable available.

Connection 1 x 230 V Connection 2 x 230 V

X1

X1

N PE L1 L2 L3

N PE L1 L2 L3

List of components

UB1

Cable grommet, cascade connection

UB2

Cable grommet, communication

UB3

Cable gland, heating cable (EB14)

XL1

Heating medium connection, supply (from F2050)

XL2

Heating medium connection, return (to F2050)

Incoming supply W1

Power connection W1
UB1 UB2 XL1
XL2
DATA

LEK

UB3 LEK
Communication cable (provided by installer) must be routed through cable grommet, communication (UB2), connected to terminal block AA23-X4 and secured with two cable ties. For connection of accessory KVR, heating cable (EB14) is connected via cable grommet UB3, see section “External heating cable KVR (Accessory)”.

NIBE F2050

Chapter 5 | Electrical connections 25

F2050-6
LEK
UN

F2050-10

Cables for communication (W2) are threaded two turns through ferrite beads/EMI filters.

LEK

LEK

26 Chapter 5 | Electrical connections

NIBE F2050

EXTERNAL HEATING CABLE KVR (ACCESSORY)
F2050-6 / -10
F2050 is equipped with a terminal block for external heating cable (EB14, not enclosed). The connection is fused with 250 mA (F3 on the communication board AA23). If another cable is to be used, the fuse must be replaced with a suitable one (see table).
NOTE
Self regulating heating cables must not be connected.

Length, heating cable (m)
1 3 6

Ptot (W)
15 45 90

Fuse (F3)
T100mA/250V T250mA/250V T500mA/250V

Part No.
718 085 518 900 1 718 086

1 Fitted at the factory.
Connect external heating cable (EB14) to terminal block X1:4­6 as illustrated below:

External F2050

AA23

Cable routing
The following images show recommended cable routing from the electrical connection to the condensation pipe. Route the heating cable (EB14) through the gland on the underside and secure with two cable ties at the electrical connection. The transition between the electrical cable and the heating cable must occur after the gland to the condensation pipe.
F2050-6
Secure the heating cable (EB14) here using two cable ties.

123456

External heat cable
EB14

F3 X1

NOTE
The pipe must be able to withstand the heat from the heating cable.
To ensure this function, the accessory KVR should be used.

UN
F2050-10

Heating cable (EB14)
Secure the heating cable (EB14) here using two cable ties.

LEK

NIBE F2050

Heating cable (EB14)
AMBIENT TEMPERATURE SENSOR
An ambient temperature sensor BT28 (Tho-A) is located on the rear of F2050.
Chapter 5 | Electrical connections 27

COMMUNICATION
For connection of indoor module / control module, see relevant manual on nibe.eu.
Software version
To allow F2050 to communicate with indoor module/control module, you may need to update to a more recent software version.
Connection to indoor module
Communication cable (W2) is inserted from the rear through “cable grommet, communication” (UB2).
F2050 can communicate with indoor modules, by connecting the indoor module to the terminal block AA23-X4:1­3.
VVM S
IInnodmoohrusmmoodduulle
AA2-X30

Connection to control module SMO 20
F2050 can communicate with control module (SMO 20), by connecting the terminal block for communication (AA23X4:1, 2, 3) in F2050 to the terminal block for communication in SMO 20, X2-19(A), -20(B), -21(GND). Stripped length of conductor is 6 mm. FF22004500, F2050
AA23-X4
GND 6 B5 A4
GND 3 B2 A1
CSMonOtr2o0l module

A B +12V GND

1234
FF22004500, F2050

X2

18

A

19

B

20

GND

21

AA23-X4
GND 6 B5 A4
GND 3 B2 A1
VVM
IInnodmohoursmmoodduul le
AA3-X4
A 15 B 14 GND 13
12 11 10

Connecting to hydrobox
F2050 can communicate with mini hydrobox (MHB 05), by connecting the terminal block for communication (AA23X4:1, 2, 3) in F2050 to the terminal block for communication in MHB 05, AA5:X4-1(A), -2(B), -3(GND).
FF22004500, F2050
AA23-X4
GND 6 B5 A4
GND 3 B2 A1

FF2200X500
AA23-X4
GND 6 B5 A4
GND 3 B2 A1

MMHHBB 0055
54321

A B GND

AA5:X4

28 Chapter 5 | Electrical connections

NIBE F2050

Cascade connection

SMO S40
F2050 (one or more) can communicate with control module (SMO S40), by connecting the terminal block for communication (AA23-X4:1, 2, 3) in F2050 to the terminal block for communication in SMO S40, AA100:X9-4(A), -5(B), -6(GND).

FF22004500, F2050

FF22004500, F2050

AA23-X4
GND 6 B5 A4
GND 3 B2 A1

AA23-X4
GND 6 B5 A4
GND 3 B2 A1

Addressing via cascade connection
On the communication board (AA23-S3), the communication address is selected for F2050 to the control module. The default address for F2050 is 1. In a cascade connection, all F2050 must have a unique address. The address is coded in binary.

Address 1 2 3 4 5 6 7 8

S3:1 OFF On OFF On OFF On OFF On

S3:2 OFF OFF On On OFF OFF On On

S3:3 OFF OFF OFF OFF On On On On

SSMMOO SS4400
AA100:X9
1 2 3 4A 5B 6 GND 7 8 9 10 11 12

SMO 40
F2050 (one or more) can communicate with control module (SMO 40), by connecting the terminal block for communication (AA23-X4:1, 2, 3) in F2050 to the terminal block for communication in SMO 40, AA5:X4-1(A), -2(B), -3(GND).

Stripped length of conductor is 6 mm.

F2050

F2050

AA23-X4
GND 6 B5 A4
GND 3 B2 A1

AA23-X4
GND 6 B5 A4
GND 3 B2 A1

SSMMOO 4400

54321
AA5:X4
NIBE F2050

A B GND

Chapter 5 | Electrical connections 29

Commissioning and adjusting
Preparations
· Before commissioning, check that the charge circuit and climate system are filled and well vented.
· Check the pipe system for leaks.
Filling and venting
Filling and venting the heating medium system. 1. The heating medium system is filled with water to the
required pressure. 2. Vent the system using the venting nipple (QM20) on the
enclosed flexible hose and possibly the circulation pump.
QM20

Compressor heater
F2050 (does not apply to F2050-6) is equipped with a compressor heater that heats the compressor before startup and when the compressor is cold.
NOTE
The compressor heater must have been connected for 6 ­ 8 hours before the first start, see the section “Start-up and inspection” in the Installer Manual for the indoor section
30 Chapter 6 | Commissioning and adjusting

NIBE F2050

Start-up and inspection
1. The compressor heater (CH) must have been operational for at least 6 – 8 hours before the compressor start can be initiated. This is done by switching on the control voltage and disconnecting the communication cable.
2. F2050 must be addressed, if it is to have an address other than 1. See chapter “Addressing via cascade connection”.
3. The communication cable on the terminal block AA23X4 must not be connected.
4. Turn the isolator switch on.
5. Ensure that the F2050 is connected to the power source.
6. After 6 ­ 8 hours, connect the communication cable (W2) to the terminal block AA23-X4.
7. Restart the indoor module. Follow the instructions for “Start-up and inspection” in the installation manual for the indoor module.
The heat pump starts 30 minutes after the outdoor unit has been powered up and the communication cable (W2) has been connected, if necessary.
If scheduled silent operationis required, it must be scheduled in the inner section or control unit.
NOTE
Do not start any electrical work until at least two minutes after cutting the power.
Caution
Silent mode should only be scheduled periodically because the maximum output is limited to approx. the nominal values.

F2050-6 / -10

AA23
AA23-S3 AA23-X4

LEK
Readjusting, heating medium side
Air is initially released from the hot water and venting may be necessary. If bubbling sounds can be heard from the heat pump, the circulation pump and radiators the entire system will require further venting. When the system is stable (correct pressure and all air eliminated) the automatic heating control system can be set as required.
Adjustment, charge flow
Instructions for adjusting hot water charging are in the Installer Manual for the relevant indoor module. See section Accessories for a list of the indoor units and accessories that can be connected to F2050.

NIBE F2050

Chapter 6 | Commissioning and adjusting 31

Control – Heat pump EB101

S-series ­ VVM S / SMO S
These settings are made on the display on the indoor module/control module.
MENU 7.3.2 – INSTALLED HEAT PUMP
Here, you make specific settings for the installed heat pump.
Cooling permitted
Alternative: on/off
Silent mode permitted
Alternative: on/off
Max. frequency 1
Setting range: 25 ­ 120 Hz
Max. frequency 2
Setting range: 25 ­ 120 Hz
Compressor phase
Setting range F2050 1 x 230 V: L1, L2, L3
Detect compressor phase
Alternative F2050 1 x 230 V: on/off
Current limit
Alternative F2050 1 x 230 V: on/off
Max. current
Setting range F2050 1 x 230 V: 6 ­ 32 A
Stop temperature compressor
Setting range -20 ­ -2 °C
blockFreq 1
Alternative: on/off
From frequency
Setting range: 25 ­ 117 Hz
To frequency
Setting range: 28 ­ 120 Hz
blockFreq 2
Alternative: on/off
From frequency
Setting range, cooling, F2050-6: 20 ­ 106 Hz
Setting range, cooling, F2050-10: 12 ­ 90 Hz
To frequency
Setting range, heating, F2050-6: 20 ­ 110 Hz
Setting range, heating, F2050-10: 20 ­ 120 Hz

Silent mode permitted: Here, you set whether silent mode will be activated for the heat pump. Note, it is now possible to schedule when silent mode will be active. The function should only be used for limited periods, because F2050 might not reach its dimensioned power.
Detect compressor phase: This shows in which phase the heat pump detected that you have F2050 230V~50Hz. Phase detection normally occurs automatically in connection with start-up of the indoor module/control module. This setting can be changed manually.
Current limitation: Here, you set whether the current limitation function will be activated for the heat pump, if you have F2050 230V~50Hz. During active function, you can limit the value of the maximum current.
BlockFreq 1: Here, you can select a frequency range within which the heat pump is not permitted to work. This function can be used if certain compressor speeds cause disturbing noise in the house.
BlockFreq 2: Here, you can select a frequency range within which the heat pump is not permitted to work.

Cooling permitted: Here, you can set whether the cooling function will be activated for the heat pump.

32 Chapter 7 | Control – Heat pump EB101

NIBE F2050

F-series ­ VVM / SMO
These settings are made on the display on the indoor module/control module.
MENU 5.11.1.1 – HEAT PUMP
Here, you make specific settings for the installed heat pump.
Cooling permitted
Setting range: off / on
Silent mode permitted
Setting range: yes / no
Detect compressor phase
Setting range F2050 1 x 230 V: off/on
Current limit
Setting range: 6 ­ 32 A
Factory setting: 32 A
blockFreq 1
Setting range: yes / no
blockFreq 2
Setting range: yes / no
Cooling permitted: Here, you can set whether the cooling function will be activated for the heat pump.
Silent mode permitted: Here, you set whether silent mode will be activated for the heat pump. Please note that you now have the option to schedule when silent mode will be active.
The function should only be used for limited periods, because F2050 possibly may not reach its dimensioned output.
Detect compressor phase: This shows in which phase the heat pump detected that you have F2050 230V~50Hz. Phase detection normally occurs automatically in connection with start-up of the indoor module/control module. This setting can be changed manually.
Current limitation: Here, you set whether the current limitation function will be activated for the heat pump, if you have F2050 230V~50Hz. During active function, you can limit the value of the maximum current.
BlockFreq 1: Here, you can select a frequency range within which the heat pump is not permitted to work. This function can be used if certain compressor speeds cause disturbing noise in the house.
BlockFreq 2: Here, you can select a frequency range within which the heat pump is not permitted to work.

NIBE F2050

Chapter 7 | Control – Heat pump EB101 33

Service

Temperature sensor data

DATA FOR TEMPERATURE SENSOR IN F2050-6

Tho-D

RReessisittaannsce (k(k) )
160

140

120

100

80

60

40

20

0

0

20 40 60 80 90 110 130 150

TeTmepmepreartauturer

((°°CC))

Tho-A, R

RReessisittaannsce (k(k))
18

16 14

12

10

8

6

4

2

0

0

20

40

60

80

100

TemTepmepreartautruer ((°°CC))

DATA FOR TEMPERATURE SENSOR IN F2050-10

Tho-D

RReessisittaannsce (k(k))
210

180

150

120

90

60

30

0

0

20 40 60 80 100 120 140 160

TemTepmepreartauturer (°°CC))

Tho-S, Tho-R1, Tho-R2
RReessisittaannsce (k(k))
20

15

10

5

0

0

20

40

60

80

100

TemTepmepreartauturer ((°C))

BT28 (Tho-A)

RReessisittaannsce (k(k))
35

30

25

20

15

10

5

0

0

10

20

30

40

50

TemTepmepreartauturer ((°°CC))

DATA FOR TEMPERATURE SENSOR BT3, BT12, BT15

Temperature (°C) -10 0 10 20 30 40 50 60 70 80

Resistance (kOhm) Voltage (VDC)

56.20

3.047

33.02

2.889

20.02

2.673

12.51

2.399

8.045

2.083

5.306

1.752

3.583

1.426

2.467

1.136

1.739

0.891

1.246

0.691

34 Chapter 8 | Service

NIBE F2050

Disturbances in comfort

In most cases, the indoor module/control module notes a malfunction (a malfunction can lead to disturbance in comfort) and indicates this with alarms and action instructions in the display.
Troubleshooting
NOTE
In the event of action to rectify malfunctions that require work within screwed hatches, the incoming supply electricity must be isolated at the safety switch by or under the supervision of a qualified electrician.
Caution
Alarms are acknowledged on the indoor module / control module.
If the operational interference is not shown in the display the following tips can be used:
BASIC ACTIONS
Start by checking the following: · All supply cables to the heat pump are connected. · Group and main fuses of the accommodation. · The property’s earth circuit breaker. · The heat pump’s fuse / automatic protection. (FC1 / FB1,
FB1 only if KVR is installed.) · The indoor module’s/control module’s fuses. · The indoor module’s/control module’s temperature lim-
iters. · That the air flow to F2050 is not blocked by foreign ob-
jects. · That F2050 does not have any external damage.
F2050 DOES NOT START
· There is no demand. ­ The indoor module/control module does not call on heating, cooling or hot water.
· Compressor blocked due to the temperature conditions. ­ Wait until the temperature is within the product’s working range.
· Minimum time between compressor starts has not been reached. ­ Wait for at least 30 minutes and then check if the compressor has started.
· Alarm tripped. ­ Follow the display instructions.

F2050 NOT COMMUNICATING
· Check that the addressing of F2050 is correct. · Check that the communication cable is correctly connec-
ted and working.
LOW HOT WATER TEMPERATURE OR A LACK OF HOT WATER
Caution
The setting for the hot water is always performed on the indoor module or the control module.
This part of the fault-tracing chapter only applies if the heat pump is docked to the hot water heater. · Large hot water consumption.
­ Wait until the hot water has heated up. · Incorrect hot water settings in indoor module or control
module. ­ See the Installer Manual for the indoor module/control
module. · Clogged filterball.
­ Switch off the system. Check and clean the filterball.
LOW ROOM TEMPERATURE
· Closed thermostats in several rooms. ­ Set the thermostats to max in as many rooms as possible.
· Incorrect settings in indoor module or control module. ­ See the Installer Manual for the indoor module/control module.
· Air-filled radiators/underfloor heating coils. ­ Bleed the system.
HIGH ROOM TEMPERATURE
· Incorrect settings in indoor module or control module. ­ See the Installer Manual for the indoor module/control module.
LARGE AMOUNT OF WATER BELOW F2050
· The accessory KVR 10 is required. · If KVR 10 is installed, check that the water drainage can
flow freely.

NIBE F2050

Chapter 9 | Disturbances in comfort 35

Alarm list

Alarm 3 12 15 162 163 183 220
221
223 224 230
254 261
262 263

Alarm text on the display Description

May be due to

Sensor fault BT3

Sensor fault, Sensor incoming water in F2050 · Open circuit or short circuit on sensor input

(BT3).

· Sensor does not work (see section “Disturb-

ances in comfort”)

· Defective control board AA23 in F2050

Sensor fault BT12

Sensor fault, Sensor outgoing water in F2050 (BT12).

· Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturb-
ances in comfort”) · Defective control board AA23 in F2050

Sensor fault BT15

Sensor fault, Sensor fluid pipe in F2050 (BT15). · Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturbances in comfort”) · Defective control board AA23 in F2050

High condenser out

Too high temperature out from the condenser. · Low flow during heating operation

Self-resetting.

· Too high set temperatures

High condenser in

Too high temperature into the condenser. Self- · Temperature generated by another heat

resetting.

source

Defrosting in progress

not an alarm, but an operating status instead. · Set when the heat pump runs the defrosting procedure

HP alarm

The high pressure switch (63H1) deployed 5 · Insufficient air circulation or blocked heat

times within 60 minutes or for 60 minutes con- exchanger

tinuously.

· Open circuit or short circuit on input for high

pressure switch (63H1)

· Defective high pressure switch

· Expansion valve not connected correctly

· Service valve closed

· Defective control board in F2050

· Low or no flow during heating operation

· Defective circulation pump

· Defective fuse, F(4A)

LP alarm

Too low value on the low pressure sensor 3 times within 60 minutes.

· Open circuit or short circuit on input for low pressure sensor
· Defective low pressure sensor · Defective control board in F2050 · Open circuit or short circuit on input for suc-
tion gas sensor (Tho-S) · Defective suction gas sensor (Tho-S)

OU Com. error

Communication between the control board and · Any circuit breakers for F2050 off the communication board is interrupted. There · Incorrect cable routing must be 22 volt direct current (DC) at the switch CNW2 on the control board (PWB1).

Fan alarm

Deviations in the fan speed in F2050.

· The fan cannot rotate freely · Defective control board in F2050 · Defective fan motor · Control board in F2050 dirty · Fuse (F2) blown

Continuously high hot gas

Temperature deviation on the hot gas sensor (Tho-D) twice within 60 minutes or for 60 minutes continuously.

· Sensor does not work (see section “Ambient temperature sensor”)
· Insufficient air circulation or heat exchanger · Blocked · If the fault persists during cooling, there may
be an insufficient amount of refrigerant. · Defective control board in F2050

Communication error

Communication fault with accessory board

· F2050 not powered · Fault in the communication cable.

High temperature in heat ex- Temperature deviation on the heat exchanger · Sensor does not work (see section “Disturb-

changer

sensor (Tho-R1/R2) five times within 60 minutes ances in comfort”)

or for 60 minutes continuously.

· Insufficient air circulation or blocked heat

exchanger

· Defective control board in F2050

· Too much refrigerant

Power transistor too hot

When IPM (Intelligent power module) displays · Can occur when 15V power supply to the inFO-signal (Fault Output) five times during a 60- verter PCB is unstable. minute period.

Inverter error

Voltage from the inverter outside the paramet- · Incoming power supply interference

ers four times within 30 minutes.

· Service valve closed

· Insufficient amount of refrigerant

· Compressor fault

· Defective circuit board for inverter in F2050

36 Chapter 9 | Disturbances in comfort

NIBE F2050

Alarm 264 265 266
267 268 271 272 277
278
279
280
281
294 404

Alarm text on the display Inverter error Inverter error Not enough refrigerant
Inverter error Inverter error Cold outdoor air Hot outdoor air Sensor fault Tho-R
Sensor fault Tho-A
Sensor fault Tho-D
Sensor fault Tho-S
Sensor fault LPT
Non-compatible air/water heat pump Sensor fault BP4

Description

May be due to

Communication between circuit board for invert- · Open circuit in connection between boards

er and control board broken.

· Defective circuit board for inverter in F2050

· Defective control board in F2050

Continuous deviation on power transistor for · Defective fan motor

15 minutes.

· Defective circuit board for inverter in F2050

Not enough refrigerant is detected on start-up · Service valve closed

in cooling mode.

· Loose connection sensor (BT15, BT3)

· Defective sensor (BT15, BT3)

· Too little refrigerant

Failed start for compressor

· Defective circuit board for inverter in F2050 · Defective control board in F2050 · Compressor fault

Overcurrent, Inverter A/F module

· Sudden power failure

Temperature of BT28 below the value that per- · Cold weather conditions

mits operation

· Sensor fault

Temperature of BT28 above the value that permits operation

· Warm weather conditions · Sensor fault

Sensor fault, heat exchanger in F2050(Tho-R). · Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturbances in comfort”) · Defective control board in F2050

Sensor fault, outdoor temperature sensor in F2050 (Tho-A).

· Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturb-
ances in comfort”) · Defective control board in F2050

Sensor fault, hot gas in F2050 (Tho-D).

· Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturb-
ances in comfort”) · Defective control board in F2050

Sensor fault, suction gas in F2050 (Tho-S).

· Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturb-
ances in comfort”) · Defective control board in F2050

Sensor fault, low pressure transmitter in F2050. · Open circuit or short circuit on sensor input · Sensor does not work (see section “Disturbances in comfort”) · Defective control board in F2050 · Fault in the refrigerant circuit

Heat pump and indoor module do not function · Outdoor module and indoor module are not together properly due to technical parameters. compatible.

Sensor fault, Sensor high pressure heating/low Open circuit or short circuit on sensor input

pressure cooling in F2050 (BP4).

Sensor does not work (see section “Disturb-

ances in comfort”)

Defective control board AA23 in F2050

NIBE F2050

Chapter 9 | Disturbances in comfort 37

Accessories

Detailed information about the accessories and complete accessories list available at nibe.eu.
Not all accessories are available on all markets.

CONDENSATION WATER PIPE KVR
Condensation water pipe, different lengths.

KVR 10-10
1 metres Part no. 067 614
KVR 10-60
6 metres Part no. 067 618

KVR 10-30
3 metres Part no. 067 616

STAND AND BRACKETS
Ground stand GSU 30
F2050-6, -10 Part no. 067 653
Wall bracket BAU 30
For wall mounting F2050-6, -10 Part no. 067 832

38 Chapter 10 | Accessories

NIBE F2050

Technical data
Dimensions
F2050-6

741

353 631

Ställbar 40-50

307

Adjustable 40-50

364

383

F2050-10

924 993
95

400 670
5 0

855

100

Ställbar 40-50

365

Adjustable 40-50

422

437

NIBE F2050

965 1035
95
Chapter 11 | Technical data 39

Sound levels
2 m 6 m 10 m

LEK

F2050 is usually placed next to a house wall, which gives a directed sound distribution that has to be taken into consideration. Accordingly, when setting up, you should always attempt to select the side that faces the least sound-sensitive neighbouring area.
The sound pressure levels are further affected by walls, bricks, differences in ground level, etc and should therefore only be seen as guide values.
F2050 adjusts the fan speed depending on the ambient temperature and evaporation temperature.

Sound power 1

F2050-6 F2050-10

Nominal sound value

53

Max. sound value

62

Max. sound value, silent mode

53

Nominal sound value

53

Max. sound value

65

Max. sound value, silent mode 60 53 Hz

1
48.0 57.0 48.0 48.0 60.0 48.0

1 Sound power level, LW(A), according to EN12102 2 Sound pressure calculated according to directivity factor Q=4

2
42.0 51.0 42.0 42.0 54.0 42.0

Sound pressure at distance (m) 2

3

4

5

6

7

8

38.5 36.0 34.0 32.5 31.1 30.0

47.5 45.0 43.0 41.5 40.1 39.0

38.5 36.0 34.0 32.5 31.1 30.0

38.5 36.0 34.0 32.5 31.1 30.0

50.5 48.0 46.0 44.5 43.1 42.0

38.5 36.0 34.0 32.5 31.1 30.0

9
28.9 37.9 28.9 28.9 40.9 28.9

10
28.0 37.0 28.0 28.0 40.0 28.0

40 Chapter 11 | Technical data

NIBE F2050

Technical specifications

WORKING RANGE, HEATING

Supply temperature (°(C°C) )

65

60

55

50

45

40

35

30

25

20

15

-30 -20 -10 0

10

FSruapmplelydntienmg perature

RReettuurlrendnteinmg p

20 30 40 50
OUutotdmohorutsetemmppereartautruer (°C)

The supply temperature is permitted to be lower for a short period, e.g. at start-up.

WORKING RANGE, COOLING

Supply temperature (°C)
35

30

25

20

15

10

5

0

10

15

20

25

RReettuurrlnedtneimngp SFurapmplleydtneinmgperature

30

35

40

45

UOtuotmdohourstteemmppeerraattuurre ((°°CC))

CAPACITY AND COP
Power and COP at different supply temperatures during
continuous operation (excluding defrosting).

Power during heating operation
Maximum and minimum capacity during continuous opera-
tion.

F2050-6

Heating output (kW)

10

9

Maximum

8

7

6

5

Maximum

4

3

Minimum

2

1

0 -25 -20 -15 -10 -5

0

5

10 15

UOtuotmdohourstteemmppereartautruer

((°°CC))

FFlroawmlilneedtneimngpsetreamtupree3ra5t°uCr 35 °C

FFlroawmlilneedtneimngpsetreamtupree4ra5t°uCr 45 °C

FFlroawmlilneedtneimngpsetreamtupree5ra5t°uCr 55 °C STiylesnttlämgoed,ef,rsaumpplelydnteinmgpsetreamtupreer3a5t°uCr 35 °C STiylesnttlmägoed,ef,rsaumpplelydnteinmgpsetreamtupree5ra5t°uCr 55 °C

F2050-10

Heating output (kW)

13

12

Maximum

11

10

9

8

7 6

Maximum

5

4

Minimum

3

2

1

0 -25 -20 -15 -10 -5

0

5

10 15

UOtuotmdohourstteemmppereartautruer

((°°CC))

FFlroawmlilneedtneimngpsetreamtupree3ra5t°uCr 35 °C

FFlroawmlilneedtneimngpsetreamtupree4ra5t°uCr 45 °C

FFlroawmlilneedtneimngpsetreamtupree5ra5t°uCr 55 °C STiylesnttlämgoed,ef,rsaumpplelydnteinmgpsetreamtupreer3a5t°uCr 35

STiylesnttlmägoed,ef,rsaumpplelydnteinmgpsetreamtupree5ra5t°uCr 55

NIBE F2050

Chapter 11 | Technical data 41

Power during cooling operation
Maximum and minimum capacity during continuous operation.
F2050-6
Cooling output (kW) 12,0

10,0

8,0

6,0

Maximum

4,0 Minimum
2,0

0,0 10

15

20

25

30

35

40

45

UOtuotmdohourstteemmppeeraratutruer

(°CC))

SFurapmplyletdenminpgesratetumrep1e8ra°Ctur 18 °C

SFurapmplyletdenminpgesratetumrep7e°rCatur 7 °C

F2050-10
Cooling output (kW) 12,0

10,0

8,0 Maximum
6,0

4,0

2,0

Minimum

0,0 0

5 10 15 20 25 30 35 40 45 50 UOtuotmdohourstteemmppeeraratutruer (°CC))
SFurapmplyletdenminpgesratetumrep1e8ra°Ctur 18 °C
SFurapmplyletdenminpgesratetumrep7e°rCatur 7 °C

COP during heating operation F2050-6
COP 6

5

4

3

2

1

0 -20

-15 -10

-5

0

5

10

15

UOtuotmdohour stteemmppeerartautruer

FFlroawmlilneednteinmgpsetreamtupreer3a5tu°Cr (35 °C)

(°CC))

FFlroawmlilneednteinmgpsetreamtuprer4a5tu°Cr (45 °C)

FFlroawmlilneednteinmgpsetreamtuprer5a5tu°Cr (55 °C)

F2050-10

COP 7

6

5

4

3

2

1

0 -20

-15 -10

-5

0

5

10

15

UOtuotmdohour stteemmppeerartautruer

FFlroawmlilneednteinmgpsetreamtupreer3a5tu°Cr (35 °C)

(°CC))

FFlroawmlilneednteinmgpsetreamtuprer4a5tu°Cr (45 °C)

FFlroawmlilneednteinmgpsetreamtuprer5a5tu°Cr (55 °C)

42 Chapter 11 | Technical data

NIBE F2050

F2050 Output data according to EN 14 511, partial load 1 Heating Capacity / power input / COP (kW/kW/-) at nominal flow Outdoor temp: / Supply temp.
Cooling Capacity / power input / EER (kW/kW/-) at maximum flow Outdoor temp: / Supply temp. SCOP according to EN 14825 Nominal heat output (Pdesignh) average climate 35 °C / 55 °C (Europe) Nominal heat output (Pdesignh) cold climate 35 °C / 55 °C Nominal heat output (Pdesignh) warm climate 35 °C / 55 °C SCOP average climate, 35 °C / 55 °C (Europe) SCOP cold climate, 35 °C / 55 °C SCOP warm climate, 35 °C / 55 °C Energy rating, average climate 2 The product’s room heating efficiency class 35 °C / 55 °C 3 The system’s room heating efficiency class 35 °C / 55 °C 4 Electrical data Rated voltage Max operating current, heat pump Max operating current, compressor Max. power, fan Fuse Enclosure class Refrigerant circuit Type of refrigerant GWP refrigerant Volume Type of compressor CO2-equivalent (The cooling circuit is hermetically sealed.) Cut-out value pressure switch HP (BP1) Cut-out value pressure switch LP (BP2) Airflow Max airflow Working area Min./max. air temperature, heating Min./max. air temperature, cooling Defrosting system Heating medium circuit Max system pressure heating medium Recommended flow interval, heating operation Recommended flow interval, cooling operation Min. design flow, defrosting (100% pump speed) Min./max. HM temp, continuous operation Connection heating medium F2050 external thread Connection heating medium flex pipe Min. recommended pipe dimension (system) Dimensions and weight Width Depth Height (with stand) Net weight Miscellaneous Part no.

6

10

-7 / 35 °C 2 / 35 °C 2 / 45 °C 7 / 35 °C 7 / 45 °C 35 / 7 °C 35 / 18 °C

5.55 / 2.05 / 2.71 2.31 / 0.56 / 4.13 2.02 / 0.67 / 3.01 2.65 / 0.49 / 5.41 2.43 / 0.65 / 3.74 5.32 / 1.94 / 2.74 7.55 / 2.11 / 3.58

7.18 / 2.93 / 2.45 3.46 / 0.83 / 4.17 3.24 / 1.12 / 3.24 4.00 / 0.75 / 5.33 5.00 / 1.28 / 3.91 7.07 / 2.40 / 2.95 10.79 / 3.00 / 3.60

kW

5.20 / 5.60

kW

5.80 / 5.70

kW

5.57 / 5.48

5.08 / 3.58

4.10 / 3.05

6.76 / 4.55

6.3 / 6.5 6.5 / 6.2 6.9 / 6.6 4.6 / 3.4 3.9 / 2.9 6.4 / 4.4

A+++ / A++

A++ / A++

A+++ / A++

Arms Arms
W
Arms

230 V ~ 50 Hz, 230 V 2 ~ 50 Hz

15

16

14

15

50

86

16

16

IP24

kg
t MPa (bar) MPa (bar)

R32

675

1.3

1.84

Twin Rotary

0.88

1.24

4.15 (41.5)

0.079 (0.79)

m3/h

2,530

3,000

°C

-20 / 43

-20 / 43

°C

15 / 43

Reverse cycle

MPa (bar) l/s l/s l/s °C
DN (mm)

0.6 (6.0)

0.08 ­ 0.32

0.12 ­ 0.38

0.11 ­ 0.29

0.15 ­ 0.38

0.19

25 / 58

G1 (Ø28 mm)

G1 (Ø28 mm)

20 (22)

mm

993

1,035

mm

383

422

mm

781 (+10/-0)

895 (+10/-0)

kg

76

83

064 328

064 318

1 Power statements including defrosting according to EN 14511 at heating medium supply corresponding to DT=5 K at 7 / 45. 2 Reported efficiency for the system also takes the temperature regulator into account. If the system is supplemented with an external auxiliary boiler or
solar heating, the total efficiency of the system must be recalculated. 3 Scale for the product’s room heating efficiency class A++ to G. Control module model SMO S 4 Scale for the system’s room heating efficiency class A+++ to G. Control module model SMO S

NIBE F2050

Chapter 11 | Technical data 43

Energy labelling
INFORMATION SHEET

Supplier

Model

Temperature application

°C

Seasonal space heating energy efficiency class, average climate

Rated heat output (Pdesignh), average climate

kW

Annual energy consumption space heating, average kWh climate

Seasonal space heating energy efficiency, average % climate

Sound power level LWA indoors

dB

Rated heat output (Pdesignh), cold climate

kW

Rated heat output (Pdesignh), warm climate

kW

Annual energy consumption space heating, cold kWh climate

Annual energy consumption space heating, warm kWh climate

Seasonal space heating energy efficiency, cold cli- % mate

Seasonal space heating energy efficiency, warm

%

climate

Sound power level LWA outdoors

dB

F2050-6 35 / 55
A+++ / A++
5/6 2,116 / 3,250
200 / 139
6/6 6/5 3,487 / 4,604
1,110 / 1,617
161 / 119
265 / 178
53

DATA FOR ENERGY EFFICIENCY OF THE PACKAGE

Model

Control module model

Temperature application

°C

Controller, class

Controller, contribution to efficiency

%

Seasonal space heating energy efficiency of the

%

package, average climate

Seasonal space heating energy efficiency class of the package, average climate

Seasonal space heating energy efficiency of the

%

package, cold climate

Seasonal space heating energy efficiency of the

%

package, warm climate

F2050-6 SMO
35 / 55
204 / 143 A+++ / A++
165 / 123 269 / 182

NIBE
VI 4.0

F2050-10 35 / 55
A+++ / A++ 6/6
2,834 / 3,961 181 / 132 7/6 7/7
4,059 / 5,204 1,379 / 1,964
155 / 114 260 / 177
53
F2050-10 SMO
35 / 55
185 / 136 A+++ / A++
159 / 118 264 / 181

The reported efficiency of the package also takes the controller into account. If an external supplementary boiler or solar heating is added to the package, the overall efficiency of the package should be recalculated.

44 Chapter 11 | Technical data

NIBE F2050

TECHNICAL DOCUMENTATION

Model

F2050-6

Type of heat pump

Air-water Exhaust-water Brine-water Water-water

Low-temperature heat pump

Yes

No

Integrated immersion heater for additional heat

Yes

No

Heat pump combination heater

Yes

No

Climate

Average

Cold

Warm

Temperature application

Medium (55°C)

Low (35°C)

Applied standards

EN14511 / EN14825 / EN12102

Rated heat output

Prated 5.6

kW

Seasonal space heating energy efficiency

s

139

%

Declared capacity for space heating at part load and at outdoor temperature Declared coefficient of performance for space heating at part load and at

Tj

outdoor temperature Tj

Tj = -7 °C

Pdh

5.0

kW

Tj = -7 °C

COPd 1.95

Tj = +2 °C

Pdh

2.9

kW

Tj = +2 °C

COPd 3.51

Tj = +7 °C

Pdh

1.9

kW

Tj = +7 °C

COPd 4.99

Tj = +12 °C

Pdh

1.7

kW

Tj = +12 °C

COPd 6.33

Tj = biv

Pdh

5.0

kW

Tj = biv

COPd 1.95

Tj = TOL

Pdh

4.6

kW

Tj = TOL

COPd 1.75

Tj = -15 °C (if TOL < -20 °C)

Pdh

kW

Tj = -15 °C (if TOL < -20 °C)

COPd

Bivalent temperature Cycling interval capacity Degradation coefficient

Tbiv

-7

°C

Min. outdoor air temperature

Pcych

kW

Cycling interval efficiency

Cdh

0.96

Max supply temperature

TOL

-10

°C

COPcyc

WTOL

58

°C

Power consumption in modes other than active mode

Off mode

POFF

0.007

kW

Thermostat-off mode

PTO

0.011

kW

Standby mode

PSB

0.011

kW

Crankcase heater mode

PCK

0.000

kW

Additional heat Rated heat output
Type of energy input

Psup

1.0

kW

Electric

Other items Capacity control Sound power level, indoors/outdoors Annual energy consumption
Contact information

Variable

Rated airflow (air-water)

LWA

– / 53

dB

Nominal heating medium flow

QHE 3,250 kWh Brine flow brine-water or water-water heat pumps

NIBE Energy Systems ­ Box 14 ­ Hannabadsvägen 5 ­ 285 21 Markaryd ­ Sweden

2,340

m3/h m3/h m3/h

NIBE F2050

Chapter 11 | Technical data 45

Model

F2050-10

Type of heat pump

Air-water Exhaust-water Brine-water Water-water

Low-temperature heat pump

Yes

No

Integrated immersion heater for additional heat

Yes

No

Heat pump combination heater

Yes

No

Climate

Average

Cold

Warm

Temperature application

Medium (55°C)

Low (35°C)

Applied standards

EN14511 / EN14825 / EN12102

Rated heat output

Prated 6.5

kW

Seasonal space heating energy efficiency

s

132

%

Declared capacity for space heating at part load and at outdoor temperature Declared coefficient of performance for space heating at part load and at

Tj

outdoor temperature Tj

Tj = -7 °C

Pdh

5.8

kW

Tj = -7 °C

COPd 1.98

Tj = +2 °C

Pdh

3.5

kW

Tj = +2 °C

COPd 3.17

Tj = +7 °C

Pdh

2.3

kW

Tj = +7 °C

COPd 4.98

Tj = +12 °C

Pdh

2.2

kW

Tj = +12 °C

COPd 5.50

Tj = biv

Pdh

5.8

kW

Tj = biv

COPd 1.98

Tj = TOL

Pdh

5.8

kW

Tj = TOL

COPd 1.69

Tj = -15 °C (if TOL < -20 °C)

Pdh

kW

Tj = -15 °C (if TOL < -20 °C)

COPd

Bivalent temperature Cycling interval capacity Degradation coefficient

Tbiv

-7

°C

Min. outdoor air temperature

Pcych

kW

Cycling interval efficiency

Cdh

0.98

Max supply temperature

TOL

-10

°C

COPcyc

WTOL

60

°C

Power consumption in modes other than active mode

Off mode

POFF 0.003

kW

Thermostat-off mode

PTO

0.008

kW

Standby mode

PSB

0.008

kW

Crankcase heater mode

PCK

0.000

kW

Additional heat Rated heat output
Type of energy input

Psup

0.7

kW

Electric

Other items Capacity control Sound power level, indoors/outdoors Annual energy consumption
Contact information

Variable

Rated airflow (air-water)

LWA

– / 53

dB

Nominal heating medium flow

QHE

3,961

kWh

Brine flow brine-water or water-water heat

pumps

NIBE Energy Systems ­ Box 14 ­ Hannabadsvägen 5 ­ 285 21 Markaryd ­ Sweden

3,000

m3/h m3/h m3/h

46 Chapter 11 | Technical data

NIBE F2050

Chapter 11 | Technical data 47

NIBE F2050

Part Specification Sheet 051295-0 Page 2/2 Created:2021-06-16 16:08

Pr od u ct ion WI RI NG DI AGRAM F2050-6 ELSCHEMA F2050-6

MJN MJN

0.001 2021-06-16 2021-06-16

051295 0

Electrical circuit diagram
F2050-6

48 Chapter 11 | Technical data

TH1 TH2 TH3

DH

Tho-R Tho-A Tho-D

NIBE F2050

F2050-10

NIBE F2050

Part Specification Sheet 051292-2 Page 2/2 Created:2022-03-16 07:14

Chapter 11 | Technical data 49

0.001

2022-03-16

Pr od u ct ion

FBZ

2021-06-18

WI RI NG DI AGRAM F2050-10

ELSCHEMA F2050-10

051292 2

NIBE F2050

50 Chapter 11 | Technical data

Matning 230V 50 Hz

AA23 – X1 1 2 3 4 5 6
AA23 – X100 2 1

1 OR 2 GR
3

INV PWB2

F (4A)

P

BK BK

EB11 EB10 QN2

DH

CH 20S

BP2 LPT
BP1 BT16 BT14 BT17 BT28 Tho-P 63H1 Tho-R1 Tho-D Tho-S Tho-A

Item register
A
Accessories, 38 Addressing via cascade connection, 29 Adjustment, charge flow, 31 Alarm list, 36 Ambient temperature sensor, 27 Assembly, 7
B
Basic actions, 35
C
Cascade connection, 29 Charge pump, 23 Commissioning and adjusting, 30
Adjustment, charge flow, 31 Compressor heater, 30 Filling and venting the heating medium system, 30 Preparations, 30 Readjusting, heating medium side, 31 Start-up and inspection, 31 Communication, 28 Compatible indoor modules and control modules, 6 Component placement Sensor placement, 19 Compressor heater, 30 Condensation, 9 Connecting accessories, 23 Connections, 25 Connection to board (AA23, 20 Connection to board (PWB1), 19 Connection to control module, 28 Connection to indoor module, 28 Control Control ­ Heat pump (EB101), 32 Control – Heat pump (EB101), 32 Control – Heat pump EB101, 32 Control ­ Heat pump EB101 Heat pump settings ­ Menu 7.3.2, 32­33
D
Delivery and handling, 7 Assembly, 7 Condensation, 9 Dismantling panels, 11 Installation area, 9 Supplied components, 10 Transport, 7
Dimensions and setting-out coordinates, 39 Dismantling panels, 11 Dismantling top panel, 11 Disruption to comfort
Temperature sensor data, 34 Disturbances in comfort, 35
Alarm list, 36 Troubleshooting, 35 Docking alternatives, 23
E
Electrical circuit diagram, 47 Electrical connection, 17 Electrical connections, 24
Addressing via cascade connection, 29 Ambient temperature sensor, 27 Cascade connection, 29
NIBE F2050

Communication, 28 Connecting accessories, 23 Connections, 25 Connection to control module, 28 Connection to indoor module, 28 External heating cable (KVR 10) , 27 General, 24 Power connection, 25 Software version, 28 Energy labelling, 44 Data for energy efficiency of the package, 44 Information sheet, 44 Technical documentation, 45 External heating cable (KVR 10) , 27
F F2050 does not start, 35 F2050 not communicating, 35 Filling and venting the heating medium system, 30
G General, 24
H Heat pump settings ­ Menu 7.3.2, 32­33 High room temperature, 35
I Important information, 4
Compatible indoor modules and control modules, 6 Inspection of the installation, 5 Safety information, 4 Serial number, 4 Inspection of the installation, 5 Installation area, 9 Installing the installation Symbol key, 22
L Large amount of water below F2050, 35 List of components, 16 Low hot water temperature or no hot water, 35 Low room temperature, 35
M Marking, 4
P Pipe connections, 22
Charge pump, 23 Docking alternatives, 23 General, 22 Pipe connections flex hose, 23 Pipe coupling, heating medium, 22 Pressure drop, heating medium side, 23 Symbol key, 22 Water volumes, 22 Pipe connections flex hose, 23 Pipe coupling, heating medium, 22 Power connection, 25 Preparations, 30 Pressure drop, heating medium side, 23
R Readjusting, heating medium side, 31 Removing the front panel, 12
Item register 51

S
Safety information, 4 Marking, 4 Symbols, 4
Sensor placement, 19 Connection to board (AA23, 20 Connection to board (PWB1), 19 Sensor placement in F2050, 21 Sensors etc., 21
Sensor placement in F2050, 21 Sensors etc., 21 Serial number, 4 Service, 34 Service actions
Temperature sensor data, 34 Software version, 28 Sound levels, 40 Start-up and inspection, 31 Supplied components, 10 Symbol key, 22 Symbols, 4
T
Technical data, 39 Dimensions and setting-out coordinates, 39 Electrical circuit diagram, 47 Sound pressure levels, 40 Technical Data, 41
Technical Data, 41 Temperature sensor data, 34 The heat pump design, 13
Component locations, 13 Electrical components, 18 Electrical connection, 17 List of components, 16 Transport, 7 Troubleshooting, 35 Basic actions, 35 F2050 does not start, 35 F2050 not communicating, 35 High room temperature, 35 Large amount of water below F2050, 35 Low hot water temperature or no hot water, 35 Low room temperature, 35

52 Item register

NIBE F2050

Contact information

AUSTRIA
KNV Energietechnik GmbH Gahberggasse 11, 4861 Schörfling Tel: +43 (0)7662 8963-0 [email protected] knv.at
FINLAND
NIBE Energy Systems Oy Juurakkotie 3, 01510 Vantaa Tel: +358 (0)9 274 6970 [email protected] nibe.fi
GREAT BRITAIN
NIBE Energy Systems Ltd 3C Broom Business Park, Bridge Way, S41 9QG Chesterfield Tel: +44 (0)330 311 2201 [email protected] nibe.co.uk

CZECH REPUBLIC
Druzstevní závody Drazice – strojírna s.r.o. Drazice 69, 29471 Benátky n. Jiz. Tel: +420 326 373 801 [email protected] nibe.cz

DENMARK
Vølund Varmeteknik A/S Industrivej Nord 7B, 7400 Herning Tel: +45 97 17 20 33 [email protected] volundvt.dk

FRANCE
NIBE Energy Systems France SAS Zone industrielle RD 28 Rue du Pou du Ciel, 01600 Reyrieux Tél: 04 74 00 92 92 [email protected] nibe.fr

GERMANY
NIBE Systemtechnik GmbH Am Reiherpfahl 3, 29223 Celle Tel: +49 (0)5141 75 46 -0 [email protected] nibe.de

NETHERLANDS
NIBE Energietechniek B.V. Energieweg 31, 4906 CG Oosterhout Tel: +31 (0)168 47 77 22 [email protected] nibenl.nl

NORWAY
ABK-Qviller AS Brobekkveien 80, 0582 Oslo Tel: (+47) 23 17 05 20 [email protected] nibe.no

POLAND
NIBE-BIAWAR Sp. z o.o. Al. Jana Pawla II 57, 15-703 Bialystok Tel: +48 (0)85 66 28 490 biawar.com.pl

SWEDEN
NIBE Energy Systems Box 14 Hannabadsvägen 5, 285 21 Markaryd Tel: +46 (0)433-27 30 00 [email protected] nibe.se

SWITZERLAND
NIBE Wärmetechnik c/o ait Schweiz AG Industriepark, CH-6246 Altishofen Tel. +41 (0)58 252 21 00 [email protected] nibe.ch

For countries not mentioned in this list, contact NIBE Sweden or check nibe.eu for more information.

IHB EN 2318-2 631411

NIBE Energy Systems Hannabadsvägen 5 Box 14 SE-285 21 Markaryd [email protected] nibe.eu
WS name: -Gemensamt WS version: a1069 WS release date: 2023-05-02 12:04 Publish date: 2023-06-28 10:44

This is a publication from NIBE Energy Systems. All product illustrations, facts and data are based on the available information at the time of the publication’s approval. NIBE Energy Systems makes reservations for any factual or printing errors in this publication.
©2023 NIBE ENERGY SYSTEMS

631411

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

NIBE User Manuals

Related Manuals