ZURN 350SM Double Check Valve Assembly Instructions

June 13, 2024
ZURN

ZURN 350SM Double Check Valve Assembly

Product Information

The Model 350 Double Check Valve Assembly is designed for installation on water lines to protect against both back siphonage and back pressure of polluted water into the water supply. It provides protection where a potential health hazard does not exist. The assembly is made of high-quality materials such as cast bronze, reinforced nylon, stainless steel, and FDA-approved elastomers. Itfeatures threaded end connections and is available in sizes 3/4, 1, 1-1/4, 1-1/2, and 2.

Materials:

  • Main valve body: Cast Bronze, ASTM B 584 (3/4-1)
  • Housing: Reinforced Nylon
  • Fasteners: Stainless Steel, 300 Series
  • Elastomers: Silicone (FDA Approved), Buna Nitrile (FDA Approved)
  • Internals: Springs, Ball Valves, Struts, Handles – Stainless Steel, 300 Series

Features:

  • Sizes: 3/4, 1, 1-1/4, 1-1/2, 2
  • Maximum working water pressure: [maximum pressure]
  • Maximum working water temperature: [maximum temperature]
  • Hydrostatic test pressure: [test pressure]
  • End connections: Threaded

Options:

  • with full port QT ball valves (standard)
  • less ball valves, male pipe thread (3/4 – 1 only)
  • with Model SXL lead-free bronze Y-type

Accessories:

  • Repair kit
  • Thermal expansion tank (Model XT)
  • QT-SET Quick Test Fitting Set
  • Winterizing Blow out/Flush fitting (RK34-350BOF, RK1-350BOF or RK114-350-375BOF)

Optional Lead-Free Strainer:
The Model SXL is a lead-free strainer that can be combined with the assembly for additional protection.

Product Usage Instructions

  1. Determine the appropriate size of the Model 350 Double CheckValve Assembly based on your water line.
  2. Ensure that there is no potential health hazard present in the water supply.
  3. Install the assembly on the water line using the threaded end connections.
  4. If required, choose the desired options for the assembly, such as full port QT ball valves or a lead-free strainer.
  5. If needed, install any additional accessories such as a repair kit, thermal expansion tank, quick test fitting set, or winterizing blow out/flush fitting.
  6. For outdoor installations, follow the provided diagram to ensure proper direction of flow and protective enclosure placement.
  7. For indoor installations, follow the provided diagram to ensure the proper direction of flow.
  8. Regularly inspect and maintain the assembly according to the user manual to ensure optimal performance and protection against back siphonage and backpressure.

Application
Designed for installation on water lines to protect against both back siphonage and backpressure of polluted water into the water supply. Assembly shall provide protection where a potential health hazard does not exist.

Standards Compliance
(Horizontal & Vertical)

  • ASSE® Listed 1015
  • cUPC® Listed
  • CSA® Certified B64.5
  • AWWA Compliant C510
  • Approved by the Foundation for Cross Connection Control and Hydraulic Research at the University of Southern California
  • UL® Classified (less shut-off valves only)
  • C-UL® Classified (less shut-off valves only

Materials

  • Main valve body Cast Bronze, ASTM B 584 (3/4-1″)
  • Housing Reinforced Nylon
  • Fasteners Stainless Steel, 300 Series
  • Elastomers Silicone (FDA Approved)
  • Buna Nitrile (FDA Approved)
  • Internals Delrin, NSF Listed
  • Springs Stainless Steel, 300 series
  • Ball Valves Cast Bronze, ASTM B 584
  • Struts Stainless Steel, 300 Series
  • Handles Stainless Steel, 300 Series

Options
(Suffixes can be combined)

  • with full port QT ball valves (standard)
  • L :  less ball valves, male pipe thread (3/4″ – 1″ only)
  • S : with Model SXL lead-free bronze “Y” type strainer
  • FT : with integral male 45° flare SAE test fitting
  • BOF : with blowout / flush-fitting

Accessories

  1. Repair kit
  2. Thermal expansion tank (Model XT)
  3. QT-SET Quick Test Fitting Set
  4. Winterizing Blow out/Flush fitting (RK34-350BOF,
  5. RK1-350BOF or RK114-350-375BOF)

Features

  • Sizes: 3/4″, 1″, 1-1/4″, 1-1/2″, 2″
  • Maximum working water pressure 175 PSI
  • Maximum working water temperature 180°F
  • Hydrostatic test pressure 350 PSI
  • End connections Threaded ANSI B1.20.1

Dimensions & Weights

(do not include pkg.)

MODEL 350 SIZE DIMENSIONS (approximate) WEIGHT

A

| B LESS BALL

VALVES

| ****

C

| ****

D

| ****

E

| ****

F

| ****

G

| ****

H

| LESS BALL

VALVES

| WITH BALL

VALVES

in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| in.| mm| lbs.| kg| lbs.| kg
3/4| 20| 11| 279| 6 5/8| 168| 1 7/8| 48| 3 3/4| 95| 3| 76| 1 1/4| 32| 15 1/8| 384| 11 7/16| 291| 2.3| 1.0| 4.3| 2.0
1| 25| 12 1/4| 311| 7| 178| 2 1/16| 52| 4 1/8| 105| 3 1/4| 83| 1 3/4| 45| 17| 431| 12 5/16| 313| 3.0| 1.4| 6.0| 2.7
1-1/4| 32| 14 7/8| 378| 14 3/8| 367| 3 3/8| 86| 6 3/4| 171| 3 3/4| 95| 2 1/4| 57| 20 1/2| 521| 18 1/2| 470| 17.2| 7.8| 19| 8.6
1-1/2| 40| 15 1/4| 387| 14 3/8| 367| 3 3/8| 86| 6 3/4| 171| 3 3/4| 95| 2 1/4| 57| 22| 559| 20 1/4| 514| 17| 7.7| 20| 9.1
2| 50| 16| 406| 14 3/8| 367| 3 3/8| 86| 6 3/4| 171| 3 3/4| 95| 2 1/4| 57| 24| 609| 20 3/4| 527| 18| 8.2| 22| 10

Flow Characteristics

  • MODEL 350 3/4″ & 1″ (STANDARD & METRIC)
  • MODEL 350, 1-1/4″, 1-1/2″ & 2″ (STANDARD & METRIC)

TYPICAL INSTALLATION

Local codes shall govern installation requirements. To be installed in accordance with the manufacturers’ instructions and the latest edition of the Uniform Plumbing Code. Unless otherwise specified, the assembly shall be mounted at a minimum of 12” (305mm) and a maximum of 30” (762mm) above adequate drains with sufficient side clearance for testing and maintenance. If installed below grade, be certain adequate drainage is provided to prevent the device from being submerged.

Capacity thru Schedule 40 Pipe

Pipe size| 5 ft/sec| 7.5 ft/sec| 10 ft/sec| 15 ft/sec
1/2″| 5| 7| 9| 14
3/4″| 8| 12| 17| 25
1″| 13| 20| 27| 40
1 1/4″| 23| 35| 47| 70
1 1/2″| 32| 48| 63| 95
2″| 52| 78| 105| 167

Specifications

The Double Check Valve Backflow Preventer shall be ASSE® Listed 1015, rated to 180°F and supplied with full port ball valves. The main body shall be Bronze for sizes 3/4″ & 1″, and Nylon for sizes 1-1/4″ to 2″. The housing shall be reinforced Nylon and the seat disc elastomers shall be silicone (FDA Approved). The first and second checks shall be accessible for maintenance without removing the device from the line. The Double Check Valve Backflow Preventer shall be a ZURN WILKINS Model 350.

Zurn Industries, LLC  Wilkins 1747 Commerce Way, Paso Robles, CA U.S.A. 93446 Ph. 855-663-9876, Fax 805-238-5766 In Canada

Zurn Industries Limited 7900 Goreway Drive, Unit 10, Brampton, Ontario L6T 5W6, 877-892-5216 www.zurn.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

ZURN User Manuals

Related Manuals