Honeywell TR21-WK Wireless Temperature Sensor and Receiver Kit Instruction Manual
- June 4, 2024
- Honeywell
Table of Contents
Honeywell TR21-WK Wireless Temperature Sensor and Receiver Kit
INSTALLATION INSTRUCTIONS
APPLICATION
The WRECVR receiver and TR21-WS, TR23-WS, TR21-WK, and TR23-WK are a family of wireless wall modules and receiver for use with:
- Spyder Unitary Controllers: PUL, PVL, etc.
- Excel 10 W7750, W7751, W7752, and W7753 controllers
- T7350, T7351, and TB8575 low-voltage Suite PRO™ thermostats
- Will not work with TB7220, TB8220 or TB line voltage thermostats, XL15s, W7762, W7763 or certain other XL controllers,
- Will work with WEBs-AX™ I/O Module products if using a separate transformer
- Compatibility with various other non-Honeywell controllers that accept 10K type2 NTC temperature inputs
NOTE:
Refer to the TR21 and TR23 Wall Modules – Specification Data, form
63-1332, for specific model features and additional information.
Model No. | FCC/IC ID’s |
---|---|
TR21-WS | FCC ID: HS9WLKFWM IC: 573R-WLKF |
TR21-WK
TR23-WS
TR23-WK
TR21-WSU
TR23-WSU
WRECVR| FCC ID: HS9WLKFRV IC: 573R-WLKF
WRECVRU
FEATURES
- Wall module to Receiver (point to point) wireless kits can replace any standard wired sensor
- Wireless Kits (wall module and receiver) are pre-bound at the factory for quick installation
- Signal Strength LED built into the wall module
- Low battery indication
- Optional dip switches available to bind any wall module to any receiver
- Approximate 5 year battery life with AA Alkaline (included), 7.5 year with Lithium
- Locking screw discourages tampering and battery theft.
SPECIFICATIONS
Models: For specific model information, see Specification Data, form
63-1332.
Environmental Ratings:
- Wall Module Operating Temperature: 45° to 99°F (7° to 37°C).
- Receiver Operating Temperature: -40° to 150°F (-40° to 65.5°C).
- Storage Temperature: -40° to 150°F (-40° to 65.5°C).
- Operating Humidity: 5% to 95% RH (non-condensing)
Accuracy: +/- 1ºF (+/- 0.5ºC) across 12ºC to 30ºC
Setpoint Range for TR23: 56° to 84°F (13° to 29°C) Accessories:
50007298-001 (pack of 12) medium, cover plate; 6-7/8 x 5 in. (175 x 127 mm).
Power:
Receiver Voltage: 20 – 30VAC/DC, 50/60Hz; 24VAC typical
Housing:
- Wall Module: UL94-HB
- Receiver: UL94-5VA
Radio Frequency 2.4 GHz (IEEE Std 802.15.4-2003 compliant)
- Open Range: 3000 feet
- Typical Range: 100 feet
- Output power: 16dBm
- Receiver power consumption: <1.5 VA@24VAC
TR21-WS, TR23-WS, TR21-WK, TR23-WK, WRECVR
Approximate battery life under normal operating conditions:
- 5 years with two AA Alkaline batteries (included)
- 7.5 years with two AA Lithium Batteries
Transmission interval: 30 seconds
Pressing override button or signal strength button will force an immediate
transmission.
Approvals:
This device complies with Part 15 of the FCC rules. Operation is subject to
the following two conditions:
- this device may not cause harmful interference, and
- this device must accept any interference received, including interference that may cause undesired operation.
Mounting the Receiver
Receiver dimensions in in. (mm).
The receiver can be mounted on any surface using screws (No. 6 or No. 8)
appropriate for the mounting surface. The receiver can also be mounted to the
Spyder controller using the mounting slots and tabs (dovetails), and can be
mounted to a DIN rail.
INSTALLATION
CAUTION
Erratic System Operation Hazard.
Failure to follow proper wiring practices can introduce disruptive electrical
interference (noise). Keep wiring at least one foot away from large inductive
loads such as motors line starters, lighting ballasts, and large power
distribution panels. Shielded cable is required in installations where these
guidelines cannot be met. Ground shield only to grounded controller case.
IMPORTANT
All wiring must comply with local electrical codes and ordinances or as
specified on installation wiring diagrams.
- Receiver wiring can be sized from 16 to 22 AWG (1.31 to 0.33 sq. mm) depending on the application.
- The maximum length of wire from a device to a receiver is 100 ft. (30.5 m).
Mounting the Wall Module
Mount the wall module on an inside wall approximately 54 in. (1372 mm) from
the floor (or in the specified location) to allow exposure to the average zone
temperature. Do not mount the wall module on an outside wall, on a wall
containing water pipes, or near air ducts. Avoid locations that are exposed to
discharge air from registers or radiation from lights, appliances, or the sun.
When mounting to drywall, use the horizontal mounting screw locations, as
shown in .
Mounting the wall module on the wall
and temperature limit set screw locations (TR23 shown).
There is a locking screw option to prevent tampering and access to
batteries. The screw is provided with the wall module, and screws into the
slot shown in Wall module features (TR23 shown).
after the device is snapped onto the subbase. If desired, insert the two red
end stoppers into temperature scale to set the desired temperature range
limit.
Mounting the wall module on the wall
and temperature limit set screw locations (TR23 shown).
For TR23 models, insert the desired dial through the opening in the cover.
Align the keyed shaft on the knob with the keyed slot into the fitting on the
subbase, then press down until it snaps into place.
WIRING
Attach the wires from the device terminals to the appropriate receiver
terminals.
CAUTION
Improper Electrical Contact Hazard. Screw type terminal blocks are designed to
accept no more than one 16 AWG (1.31 sq. mm) conductor. Connect multiple wires
that are 16-18 AWG (1.31-0.82 sq. mm) with a wire nut. Include a pigtail with
this wire group and attach the pigtail to the individual terminal block.
Wire the terminal block as follows:
-
For single wires, strip 3/16 in. (5 mm); for multiple wires going into one terminal, strip 1/2 in. (13 mm) insulation from the conductor.
-
If two or more wires (18 to 22 AWG only) are being inserted into one terminal, twist the wires together before inserting.
NOTE: When two or more wires are being inserted into one terminal, be sure to twist them together. Deviation from this rule can result in improper electrical contact. Attaching two wires (18 to 22 AWG) to receiver terminals. -
Insert the wire in the required terminal location and tighten the screw to complete the termination.
-
Review and verify the terminal connection wiring and DIP switch settings.
Note
WHEN USING THE WIRELESS TR23 SENSOR WITH THE T7350 BE SURE TO USE THE RELATIVE
SCALE SETPOINT KNOB. WHEN USING THE WIRELESS TR21 SENSOR WITH THE T7350, DO
NOT WIRE TERMINAL 5 AND TERMINAL 6.
DIP Switch Labels
This device is packed with tear-off DIP switch labels you can attach to the
receiver and indicate which DIP switches are on and off.
TESTING FOR SIGNAL STRENGTH
When the receiver is powered and batteries are placed in the wall module,
communication will begin automatically within 2 seconds. The receiver RF
signal light will flash every 30 seconds to confirm each transmission. You can
force immediate communication by pressing the signal strength button on the
side of the wall module with a 1-1.6 mm diameter probe with flat or rounded
face (a common paperclip will do) Wall module features (TR23
shown).
. This may be required to initiate communication when replacing a wall module.
The signal strength LED next to the signal strength button will light up on
the side to show the relative signal strength. The signal strength LED will
initially light amber when the signal strength button is pressed to verify
that you are pressing the signal strength button. When you release the signal
strength button, the light will behave as shown in Table 1.
Signal Strength LED.
LED | Signal Strength |
---|---|
Remains Green for 5 seconds | Strong |
Remains Amber for 5 seconds | Weaker (still acceptable) |
Amber blinks for 5 seconds | No signal |
If no signal is received, test the wall module in a different location until a
suitable signal strength is received by the receiver. Pressing the signal
strength button on the wall module will cause a five-second flash on the RF
signal LED on the receiver, and pressing the override button will cause a
single flash on the receiver. In normal operation, the sensor transmits to
the receiver every 30 seconds. If the receiver fails to receive a signal after
15 attempts (7.5 minutes), the receiver will try to re-establish communication
every minute for 8 consecutive minutes. During this time (maximum 15.5
minutes) the receiver will continue to output the last valid temperature value
it received from the sensor. If there is no valid signal received after 15.5
minutes, the receiver will simulate an open circuit (like a cut wire on a
wired sensor) and go into a sleep mode. Thereafter, every ten minutes, the
receiver will try to re-establish signal.
BINDING THE WALL MODULE AND RECEIVER TO EACH OTHER
The TR21-WK and TR23-WK wireless kits include a wall module and receiver that
have already been bound in the factory to automatically communicate with each
other. They can be identified as matching by the identical bind numbers
printed on the labels. The S2 and S3 DIP switches on the receiver (used to
bind the two devices) and the 12 DIP switches on the wall module will all be
in the OFF position. As soon as power is applied to the receiver and the
batteries are installed in the wall module, the two devices start to talk to
each other. If the two devices don’t communicate immediately, remove and re-
install one battery, leaving it out for 10 seconds OR you can initiate
communication by pressing the signal strength button on the sensor (using
paperclip). Each wireless kit has a unique binding, so even though multiple
wireless kits have S2 and S3 switches all in the OFF position, each device
will only communicate to the device to which it was paired and shipped as a
kit. There may be times when you want to bind a receiver to a wall module
using the DIP switches. This is done simply by matching any S2/S3 DIP switch
settings on the receiver with the DIP switch settings on the wall module. Wall
modules in close proximity must have different DIP switch settings (except
when modules are using the all-OFF default binding).
DIP switches S2/S3 are provided for two reasons:
- If the wall module needs to be replaced, a TR21-WS or TR23-WS wall module can be purchased. To bind any wall module and receiver, simply set the DIP switches S2/S3 on both the receiver and the wall module to any matching DIP configuration. To prepare for this ahead of time, the receiver and wall module in the WK kit can be set with a matching dip switch configuration when mounted. The tear off tab on the receiver allows the installer to write down the on/off DIP configuration. Then the new wall module’s DIP switches can be set by matching the old wall module’s DIP switches, without having to set or check the DIP switches on the receiver.
- If wall modules and receivers get mixed up in the field (even though they are marked with matching numbers from the factory), DIP switches can be used to bind any wall module to any receiver simply by matching the S2/S3 DIP switches. If setting DIP switches, be sure that each wireless sensor/receiver pair in a given building has a unique DIP switch setting to prevent cross-talk.
Wall module DIP switches and
Receiver DIP switches S1, S2, and S3. Figure shows an example of sensor DIP
switches matching S2 and S3 DIP switches on receiver.
shows matching DIP switch settings binding the wall module and receiver.
Controller Matching
The TR21 and TR23 wireless wall modules can be used with many different
controllers. The S1 switch on the receiver can be set for a number of
different controller requirements. See Table 2 for DIP switch settings, and
see Table 3 for a description of the controller.
S1 DIP Switch Settings.
Controller | S1 DIP Switches | |
---|---|---|
1 | 2 | 3 |
1. | Spyder/Comfort Point 20Kohm, XL10 | ON |
2. | XL600, 500, 100, 80 | OFF |
3. | 10K type 2, 3-wire | ON |
4. | 10K type 2, see I&I | OFF |
5. | 10K type 2, 4-wire | ON |
6. | 10K type 2, 3-wire | OFF |
Controller Descriptions.
Controller | Description | |
---|---|---|
1. | Spyder/Comfort Point 20Kohm, XL 10 | Default setting. For use with Spyder |
and Comfort Point 20K ohm controllers For use with XL10 VAV, W7750, W7751,
etc.
2.| Honeywell Other| For use with XL600/500/100.
3.| 10K type 2| 10K ohm NTC type 2 output, 2K-3K ohm knob span:
- Common
- Temperature (Override button temporarily shorts the temperature output)
- Setpoint
4.| 10K type 2| 10K ohm NTC type 2 output, 1K -11K ohm knob span.
5.| 10K type 2| 10K ohm NTC type 2 output, 0-10K ohm knob span:
- 10K out
- Common (for temperature, override, and setpoint)
- Override
- Setpoint
6.| 10K type 2 (Comfort Point 10K ohm controllers)| 10K ohm NTC type 2 output, 0-9500 ohm knob span:
- Common
- Temperature (Override button temporarily shorts the temperature output)
- Setpoint
Low Battery Signal
When there are approximately 2 months of battery life remaining, the LED on
the front of the wall module (next to the Override button) will flash red
every 15 seconds. In addition, the LOW BAT digital output from the receiver
will close. This LOW BAT output signal can be sent to an unused DI on the
controller to let the user know that there is a low battery condition. Replace
the batteries whenever the LOW BAT contact closes, or flashing red light is
seen next to the Override LED on the face of the wall module. Normal operation
will automatically resume.
NOTE:
If the batteries go dead, the LOW BAT digital output (open/close) signal
will open again. The LOW BAT digital output will close only when batteries are
running low, not when they are completely dead, or are not installed. This
ensures that a lack of signal is not confused with dead or missing batteries.
Whenever there is no signal, or batteries have gone completely dead, the
receiver LOWBAT output will send an open circuit reading to the controller for
temperature (and set point, if applicable).
Override Button
To save battery life, the override button LED will only light when the button
is pressed. It will not remain lit, as on standard wired TR23 and TR24 models.
Override will still be activated when the button is pressed. If using with the
XL10, pressing and briefly holding the override button will cause it to behave
like other standard wired TR23s. The LED will remain lit for 9 seconds max. to
confirm it has been pressed from 1-4 seconds.
REPLACING A WALL MODULE
When replacing a wall module, set the DIP switches the same as the wall module
being replaced. If the previous wall module DIP switches are all set to OFF,
it will be necessary to reset the S2 and S3 receiver dip switches to any
configuration not being used by other receivers in the area, and then set the
wall module DIP switches to the same setting. At least one of the 12 DIP
switches must be set to the ON (up) position.
General Rules for Installing Wireless
Wall Modules
Communication between the wall module and receiver can be influenced by a
number of factors. Type and thickness of building materials and the way in
which they are oriented in relation to the wall module and receiver will
affect communication. Try to orient the wall module and receiver so that if
they are separated by a wall(s), the direction of signal travel is as
perpendicular to the wall(s) as possible. This reduces the effective wall
thickness. Do not place either the wall module or receiver inside metal
cabinets or enclosures. Signal reliability can be diminished if the receiver
is installed in metal fan coil units. Older buildings may have plaster and
lathe walls with metal mesh that can significantly reduce signal strength.
When mounting the receiver on a metal duct, stronger communication is possible
if the wall module is on the same side of the duct so the signal doesn’t need
to travel through the metal duct. Standard drywall (gypsum board) does not
greatly affect signal strength. Be aware that occasional signal drop outs may
occur in any wireless installation, and the controller must be able to
accommodate for sensor and setpoint outputs from the receiver that may
occasionally go into a brief open circuit mode. Reduce as much as possible the
amount of metal (ducts, file cabinets, etc.) between and around the sensor and
the wall module. For the most robust wireless link, install the wall module in
locations with the strong signal (Green light as described in Table 1). While
the signal may appear green at any given moment, movement of people,
repositioning of furniture or other structures (especially when made of
metal), or the presence of other strong radio signals may cause temporary
and/or frequent functional disruption of the wireless signal. The TR21-WK and
TR23-WK have been successfully employed in hundreds of different locations and
applications. However, because of the variability of various environments,
Honeywell cannot guarantee that these wireless kits will work successfully in
every application, even when a green signal strength is indicated on initial
installation. Although no standalone diagnostics tools are available for the
TR wireless products, the self-diagnostics and LED indicators on the wall
module and receiver do provide a reliable indication of signal strength at any
given point in time.
Figures
Wall Module subbase dimensions in
inches (mm) (TR23 shown).
Wiring receiver to Excel 10.
Wiring receiver to Spyder Unitary
Controller.
Wiring receiver to T7350 thermostat.
References