Goodman AWSF24SU1610 Wall Mount Air Handler Owner’s Manual

June 13, 2024
Goodman

Goodman AWSF24SU1610 Wall Mount Air Handler Owner’s Manual

Product Features

  • AWSF Models: Equipped with a Check Flowrator
  • Direct-drive, multi-speed motors allows air volume variation for heating/cooling
  • Sequence-controlled, rust-resistant nickel chromium heating elements of 5, 8, and 10 kW
  • Aluminum tubing coils on all models
  • Cabinet air leakage less than 2.0% at 1.0 inch H₂O when tested in accordance with ASHRAE standard 193
  • Cabinet air leakage less than 1.4% at 0.5 inch H₂O when tested in accordance with ASHRAE standard 193
  • Factory-installed pull-type disconnect
  • Thermoplastic drain pan with bottom primary and secondary drain connections
  • Built-in filter rack (filter included)
  • Large chassis (2½- and 3-ton units) – front return only
  • Small chassis (1½- and 2-ton units) – front or bottom return
  • Wall-hanging bracket provided
  • AHRI Certified; ETL Listed

Nomenclature

Accessories

model item # description
AWSF18-AWSF24 Wad-1 Wall access door
AWSF30-AWSF36 Wad-2 Wall access door

Product Specifications

| AWSF18 SU1605 AA| AWSF18 SU1608 AA| AWSF24 SU1605 AA| AWSF24 SU1608 AA| AWSF24 SU1610 AA| AWSF30 LU1605 AA
---|---|---|---|---|---|---
Nominal Ratings
Cooling (BTU/h)| 18000| 18000| 24000| 24000| 24000| 30000
Electric Heat (kW)| 5| 8| 5| 8| 10| 5
Blower
Diameter| 10| 10| 10| 10| 10| 10
Width| 6| 6| 6| 6| 6| 8
Coil Connections
Liquid| ⅜”| ⅜”| ⅜”| ⅜”| ⅜”| ⅜”
Suction| ⅝”| ⅝”| ⅝”| ⅝”| ⅝”| ¾”
Coil Drain Connection (FPT)| ¾”| ¾”| ¾”| ¾”| ¾”| ¾”
Electrical d ata
Voltage| 208/230| 208/230| 208/230| 208/230| 208/230| 208/230
Minimum Circuit Ampacity| 24.9/28| 36/41.3| 24.9/28| 36/41.3| 46.6/53| 26/29.8
Max. Overcurrent Device (Amps)| 25/30| 40/45| 25/30| 40/45| 50/60| 30/30
Minimum VAC| 197| 197| 197| 197| 197| 197
Maximum VAC| 253| 253| 253| 253| 253| 253
Blower motor
Full Load Amps (FLA)| 2.6| 2.6| 2.6| 2.6| 2.6| 3.8
Horsepower (HP)| 1/3| 1/3| 1/3| 1/3| 1/3| 1/2
ship weight (lbs)| 84| 84| 84| 84| 84| 109
| AWSF30 LU1608 AA| AWSF30 LU1610 AA| AWSF36 LU1605 AA| AWSF36 LU1608 AA| AWSF36 LU1610 AA
Nominal Ratings
Cooling (BTU/h)| 30000| 30000| 36000| 36000| 36000
Electric Heat (kW)| 8| 10| 5| 8| 10
Blower
Diameter| 10| 10| 10| 10| 10
Width| 8| 8| 8| 8| 8
Coil Connections
Liquid| ⅜”| ⅜”| ⅜”| ⅜”| ⅜”
Suction| ¾”| ¾”| ¾”| ¾”| ¾”
Coil Drain Connection (FPT)| ¾”| ¾”| ¾”| ¾”| ¾”
Electrical d ata
Voltage| 208/230| 208/230| 208/230| 208/230| 208/230
Minimum Circuit Ampacity| 37.7/43| 48/54.8| 26/29.8| 37.7/43| 48/54.8
Max. Overcurrent Device (Amps)| 40/45| 50/60| 30/30| 40/45| 50/60
Minimum VAC| 197| 197| 197| 197| 197
Maximum VAC| 253| 253| 253| 253| 253
Blower motor
Full Load Amps (FLA)| 3.8| 3.8| 3.8| 3.8| 3.8
Horsepower (HP)| 1/2| 1/2| 1/2| 1/2| 1/2
ship weight (lbs)| 109| 109| 109| 109| 109

Dimensions

Note – Once installed, top of unit must be level or slightly tilted back to ensure proper condensate drainage

Cabinet Dimensions

| Large Chassis| Small Chassiss
2.5 & 3.0 Ton| 1.5 & 2.0 Ton
A| 36| 36
B| 24| 203/16
C| 21| 16⅛
D| 19⅞| 16
E| 15⅞| 11



Fresh Air Openings



| A| B| C| D| E| F| G| H| I| J| K| L| M| N
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---
AWSF 18-24| 36″| 20¼”| 16⅛”| 16″| 11″| 1¾”| 1½”| 2¼”| ⅞”| 1⅛”| 1¾”| 4″| 6″| 10″
AWSF 30-36| 36″| 24″| 21″| 19⅞”| 16″| 4⅛”| 1½”| 1¾”| 2″| 1¼”| 2⅜”| 4″| 8″| 12″

Air lfow Data

__model| speed Tap| Cfm delivered Against External st atic Pressure
---|---|---
0.1″| 0.2″| 0.3″| 0.4″| 0.5″
AWSF18SU16 AA| T1| 630| 602| 576| 550| 521
T2| 630| 602| 576| 550| 521
T3| 637| 609| 586| 557| 531
T4| 630| 602| 576| 550| 521
T5| 846| 824| 800| 777| 756
AWSF24SU16
AA| T1| 630| 602| 576| 550| 521
T2| 630| 602| 576| 550| 521
T3| 784| 763| 742| 728| 705
T4| 630| 602| 576| 550| 521
T5| 846| 823| 800| 777| 756
AWSF30LU16 AA| T1| 683| 604| 525| 460| 369
T2| 900| 856| 803| 734| 681
T3| 1079| 1025| 989| 949| 889
T4| 944| 897| 848| 783| 733
T5| 1168| 1127| 1083| 1050| 1005
AWSF36LU16
AA| T1| 1114| 1072| 1031| 982| 924
T2| 1114| 1072| 1031| 982| 924
T3| 1225| 1191| 1152| 1112| 1071
T5| 1287| 1255| 1219| 1183| 1146
1360| 1329| 1299| 1264| 1230

Note: Airflow data indicated is at 230 V with no filter in place.

NOTES;

  1. 1. RED WIRE TO BE ON
    TRANSFORMER TERMINAL “3” FOR 230 VOLTS AND ON
    TERMINAL “2” FOR 208 VOLTS.

  2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO
    “Y” FROM THERMOSTAT/CONDENSER (SEE TABLE-1),

  3. ASTERISK (*) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.

  4. COLOR CODES:
    BK- BLACK
    BL- BLUE
    BR- BROWN
    GR- GREEN
    PU- PURPLE
    RD RED
    WH- WHITE
    YL – YELLOW

  5. INTEGRATED CONTROL:
    FACTORY WIRING:
    HIGH VOLTAGE:
    LOW VOLTAGE:

    FIELD WIRING :
    HIGH VOLTAGE:
    READ THE INSTRUCTIONS:
    CLASS III:

  6. COMPONENT CODE:
    C – CONTACTOR
    DISC- DISCONNECT SWITCH
    EM – EVAPORATOR MOTOR
    F – FUSE HIR – HEATER ELEMENT
    R – RELAY SEQ – SEQUENCER
    TL – THERMAL LIMIT
    TR – TRANSFORMER

  7. FOR UNITS USING JKW AND SKW HEATERS, WHITE WIRE WILL BE CONNECTED TO TERMINAL 4

WIR E COLOR NOMINAL BTUR
PINK 18000

TABLE-1

0140A00911-A
Wiring : is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.

Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

NOTES:

  1. REDWIRE TO BE ON TRANSFORMER TERMINAL 3″ FOR 230 VOLTS AND ON TERMINAL “2” FOR 208 VOLTS.

  2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO Y FROM THERMOSTATICONDENSER (SEE TABLE-1).

  3. ASTERISK (‘) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.

  4. .COLOR CODES:
    BL-BLUE
    BR-BROWN
    GR- GREEN
    PU-PURPLE
    RD-RED
    WH-WHITE
    YL- YELLOW

  5. INTEGRATED CONTROL:
    FACTORY WIRING:
    HIGH VOLTAGE:
    LOW VOLTAGE:
    FIELD WIRING:
    HIGH VOLTAGE:
    READ THE INSTRUCTIONS:
    CLASS lll :

  6. COMPONENT CODE:
    C – CONTACTOR
    DISC DISCONNECT SWITCH
    EM EVAPORATOR MOTOR
    F – FUSE
    HTR HEATER ELEMENT
    R – RELAY SEQ SEQUENCER
    TL- THERMAL LIMIT
    TR – TRANSFORMER

  7. .FOR UNITS USING 3K AND SKIW HEATERS, WHITE WIRE WILL BE CONNECTED TO TERMINAL 4.

WIRE COLOR NOMINAL BTUR
PINK 24000

TABLE-1

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.
Warning
High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

NOTES:

  1. REDWIRE TO BE ON TRANSFORMER TERMINAL 3″ FOR 230 VOLTS AND ON TERMINAL “2” FOR 208 VOLTS.

  2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO Y FROM THERMOSTATICONDENSER (SEE TABLE-1).

  3. ASTERISK (‘) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.

  4. .COLOR CODES:
    BL-BLUE
    BR-BROWN
    GR- GREEN
    PU-PURPLE
    RD-RED
    WH-WHITE
    YL- YELLOW

  5. INTEGRATED CONTROL:
    FACTORY WIRING:
    HIGH VOLTAGE:
    LOW VOLTAGE:
    FIELD WIRING:
    HIGH VOLTAGE:
    READ THE INSTRUCTIONS:
    CLASS lll :

  6. COMPONENT CODE:
    C – CONTACTOR
    DISC DISCONNECT SWITCH
    EM EVAPORATOR MOTOR
    F – FUSE
    HTR HEATER ELEMENT
    R – RELAY SEQ SEQUENCER
    TL- THERMAL LIMIT
    TR – TRANSFORMER

WIRE COLOR NOMINAL BTUR
PINK 30000

Warning

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

NOTES:

  1. REDWIRE TO BE ON TRANSFORMER TERMINAL 3″ FOR 230 VOLTS AND ON TERMINAL “2” FOR 208 VOLTS.

  2. CONFIRM SPEED TAP SELECTED IS APPROPRIATE FOR APPLICATION. IF SPEED TAPS NEEDS TO BE CHANGED, CONNECT APPROPRIATE WIRE FROM MOTOR TO Y FROM THERMOSTATICONDENSER (SEE TABLE-1).

  3. ASTERISK (‘) INDICATES THAT HEATING ELEMENT, THERMAL LIMIT, RELAY AND INTERCONNECTING WIRES AND JUMPERS OF HEATER #2 ARE DELETED WITH SINGLE ELEMENT UNITS.

  4. .COLOR CODES:
    BL-BLUE
    BR-BROWN
    GR- GREEN
    PU-PURPLE
    RD-RED
    WH-WHITE
    YL- YELLOW

  5. INTEGRATED CONTROL:
    FACTORY WIRING:
    HIGH VOLTAGE:
    LOW VOLTAGE:
    FIELD WIRING:
    HIGH VOLTAGE:
    READ THE INSTRUCTIONS:
    CLASS lll :

  6. COMPONENT CODE:
    C – CONTACTOR
    DISC DISCONNECT SWITCH
    EM EVAPORATOR MOTOR
    F – FUSE
    HTR HEATER ELEMENT
    R – RELAY SEQ SEQUENCER
    TL- THERMAL LIMIT
    TR – TRANSFORMER

WIRE COLOR NOMINAL BTUR
PINK 30000

Warning

High Voltage: Disconnect all power before servicing or installing this unit. Multiple power sources may be present. Failure to do so may cause property damage, personal injury, or death.

Limed Warrant; he duration of warranty coverages n Texas  in some cases
Our continuing commitment to quality products may mean a change in specifications without notice.
02023 QALK COMPONIT TECHMAL OGS MANIRAC TIIMG, £ * Houston, Texas » Printed in the USA.
wwwgoodmanmfg.com SS-GAWSF