POWERCOM UPSMON PRO V2 UPS Monitoring Software User Manual

June 13, 2024
POWERCOM

UPSMON PRO V2.57
UPS Monitoring Software
User’s Manual

Overview

UPSMON PRO is compatible with the following windows :

  1. Windows XP, Vista, 7, 8, and 10 (32-Bit and 64-Bit)
  2. Windows Server 2000, 2003, 2008, 2012, 2016, and Hyper-V (32-Bit and 64-Bit)

NOTE: administrator authority is necessary to execute at windows here

POWERCOM UPSMON PRO V2 UPS Monitoring Software - Overview
1

UPS Connecting

To start the ups connection :

  1. Connect Page

  2. Choose the ups connecting interface :
    2.1 USB Port
    2.2 SNMP Card : Fill in the snmpcard ip address
    2.3 COM Port : The serial port cable is attached from the ups box
    NOTE: The serial port cable is not suitable from the others
    2.4 UPSMON PRO : Fill in the upsmon-pro computer ip address

  3. Then you will successfully get the ups monitoring as below :
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - Overview
3POWERCOM UPSMON PRO V2 UPS Monitoring
Software - Overview 4

Shutdown Configuration

Below steps guides you shutdown windows and ups when power failure occurs :

  1. Run Time Page

  2. Windows shutdown type (a)
    2.1 None : No any reaction for windows even the blackout condition
    2.2 Shut down : Running out of the procedures to save the programs to hard disk
    2.3 Hibernate : Power-saving state and puts open documents and programs on hard disk

  3. Power failure windows shutdown delay (b1) : After this period of time runs out, windows start to act shutdown
    Battery limited capacity shutdown (b2) : Once the battery is declining to this level, windows start to act shutdown
    Low battery shutdown (b3) : If the condition of battery is low, the windows act shutdown Any one of the(b1,2,3)item-conditions is fulfilled, upsmon execute windows shutdown or hibernate at once

  4. UPS shutdown delay (c) : This duration is affording to completely shutdown the computer

  5. Execute command file (d) : when (b1) seconds runs out, upsmon will start to act your designate command
    5.1 Time to execute command file : your command have such more seconds to run.
    And then upsmon commit windows shutdown

  6. Ups start delay time (e1) : To charge the more power, the ups will delay its power supply
    Ups start battery capacity (e2) : To charge the more power, the ups will supply its power when the battery ascend to this capacity %
    Only both of the(e1, 2) item-conditions is fulfilled, ups will start to supply its power

Email Notification

It supplies an active E-Mail notification :

  1. Notification Page

  2. Enter your SMTP Mail server’s information (ex : SMTP Server, User name, Port, Authentication, Sender’s mail, Receiver’s mail)
    NOTE : This feature requires your e-mail account support SMTP Server

  3. Button Mail Test : It helps you to check the email configuration is okay or not

  4. Checkup Daily Report : It reports you the summary ups output power (Watt)

UPS Control

  1. UPS Control Page

  2. Battery Test Function
    2.1 Quick Battery Test : Ups switch its power from battery
    2.2 Battery Test for Specific Time : Exhaust the battery power for this period of time
    2.3 Test for Specific Battery Level : Exhaust the battery capacity to this battery level
    2.4 Deep Battery Test : Exhaust the battery to low condition
    2.5 Cancel Test : Stop battery testing

  3. UPS Function Setting : Select the function to set the UPS, there will be the corresponding parameter options, and then press Execute button to set the selected function

  4. Green Mode :
    ON : The ups automatically turn off its power if the load is low
    OFF : UPS will sustain the power to its limit

  5. Power Failure UPS Sound : Turn on and off the alarm in your desire

Historical Event

It displays all ups events which taken place

Record Viewer

  1. Record Viewer Page
  2. It records and actively shows UPS information : I/P Voltage, I/P Frequency, O/P Voltage, Battery Level, Load, and Temperature
  3. As well you can check up the historical data by calendar (Upper Right Corner)

Outlets Control

  1. Outlets – Control Page
  2. Turn ON/OFF the outlets power at once
  3. Set up the UPS-Outlet shutdown sequence for blackout condition

NOTE: This feature requires the specific UPS to support

UPS Schedule

It helps you to have an automatic UPS OFF / ON / Battery self test

  1. Schedule Page

  2. Recurrence & Occurrences : Once / Daily / Weekly / Monthly

  3. Event : Ups shutdown / ups start / battery test

  4. If you set up the UPS shutdown, all the UPSMON-Slaves will execute OS shutdown earlier 30 seconds than UPSMON-Master
    NOTE: The time of ups shutdown must be earlier than ups start

  5. You can check the last UPS schedule for the current status

Multi OS Connect

POWERCOM UPSMON PRO V2 UPS Monitoring Software - Multi OS Connect
1

The UPSMON PRO can play the role as Master or Slave

  1. UPSMON PRO Master : Physically connect(RS232 / USB) with ups
    ==> Master can share the ups information to other Slaves
    ==> EX : IP 10.192.136.231 (Master pc ip address)

  2. UPSMON PRO Slave : Get the ups information from UPSMON PRO Master by ways of the internet or intranet
    ==> All the other pc, which installed upsmon pro, can get the ups status from UPSMON PRO Master
    EX : UPSMON PRO Windows / Connect Page / UPSMON PRO : 10.192.136.231

And then you get ups connection

POWERCOM UPSMON PRO V2 UPS Monitoring Software - Multi OS Connect
3

EX : UPSMON PRO Linux
==> Execute the UPSMON-PRO-for-Linux application : ./upsmon
==> Choose UPSMON-PRO (4) with Master IP address
==> UPSMON : Start Monitor ==> It means the connection is successful

POWERCOM UPSMON PRO V2 UPS Monitoring Software - Multi OS Connect
4

Web Portal

Ups remotely monitoring via browser

  1. Connect Page
  2. Enable Web Server UPSMON Function
  3. IP Address : Make sure this Windows has a IP address (ex : 10.192.136.231)
  4. Port : 8000 (default)
  5. User Name : UPSMON (default)
  6. Password : UPSMON (default)

NOTE: This feature requires your windows has a connectable ip address

POWERCOM UPSMON PRO V2 UPS Monitoring Software - Web Portal
2

Windows auto startup

Below configuration can help you to auto startup windows when power is restored

  1. PC Restart
  2. When the PC brand logo screen appears, press correct key on your keyboard to open to the BIOS Setup window (For general PCs, press the delete key)
  3. Use your arrow keys on the keyboard to select the correct power option
  4. Select the correct setting to enable PC power always on. For general PCs, use your arrow keys to Enable “Restore on AC Power Loss”
  5. Save your changes

NOTE: Each PC varies in how to enter and make changes to the BIOS settings

VMWare Support

A. Get ups monitoring on Vmware-Windows

  1. Vmware-Windows upsmon get ups connection from usb
    ==> Start Vmware ESXi
    ==> Vmware-Windows >> Actions >> Edit settings
    ==> Add other device >> USB device >> Powercom HID UPS Battery >> Save
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
2 POWERCOM UPSMON PRO V2 UPS
Monitoring Software - VMWare Support 3

  2. Vmware-Windows install upsmon pro and choose usb connection
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
4

  3. Successfully get ups monitoring
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
5

  4. UPSMON PRO >> Run Time >> Shutdown Vmware Esxi (Enable) >> Setup

  5. Filled in your Vmware Exsi IP / User Name (administrator) / Password

B. Vmware OS shutdown with sequence configuration

POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
8

  1. Install Vmware vSphere Client

  2. Start Vmware vSphere Client and login to the Vmware Esxi

  3. Vmware host >> Software >> Virtual Machine Startup / Shutdown >> Properties
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
10

  4. This windows is allowed you to setup : shutdown type / shutdown delay / shutdown order / startup order
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
11 Ex : In above example : Win7Eng shutdown first / Win2016Eng shutdown last
    C. Power failure and the Vmware shutdown as sequence
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - VMWare Support
12

SMS Alarm

A. Configuration >> UPSMON >> Email Notification

  • User Name and password >> Check with your ups vendor
  • UPS Name >> Receive alarm’s message with ups label
  • Phone Number >> Receive alarm’s phone number
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
1

B. Smart Phone >> Get messages

  1. Alarm >> Power failure
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
2

  2. Alarm >> Power restore
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
3

  3. Alarm >> UPS connect lost
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
4

  4. Alarm >> UPS battery test
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
5

  5. Alarm >> UPS battery test normal
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
6

  6. Alarm >> UPS battery fail
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
7

  7. Alarm >> UPS battery expired
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
8

  8. Alarm >> UPS fail
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
9

  9. Alarm >> UPS overload
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
10

  10. Alarm >> UPS bypass on
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
11

  11. Alarm >> UPS bypass off
    POWERCOM UPSMON PRO V2 UPS Monitoring Software - SMS Alarm
12