Model No. | Description | Adapter Cutout | Dimensions (inches) |
---|---|---|---|
G3AD | G306A to M-VIEW Touch 7 Cutout Adapter | G310S to M-VIEW Touch 10 Cutout | |
Adapter | G310S to M-VIEW Touch 12 Cutout Adapter | ||
Part Number | 00034621 | 00034620 | 00034622 |
Existing Unit | M-VIEW Touch | G306A / MV-7T | G310S / MV-10T |
Dimensions (inches) | 8.83 x 7.08 x 7.06 x 4.89 | 12.83 x 9.50 x 10.197 x 7.931 |
12.83 x 9.50 x 11.458 x 7.561
Note:
The product specifications and designs are subject to change without prior
notice. FW MURPHY product names and the FW MURPHY logo a proprietary
trademarks. This document, including textual matter and illustrations, is
copyright-protected with all rights reserved. (c) 2021 FW MURPHY. A copy of
our typical warranty may be viewed or printed by going to
www.fwmurphy.com/warranty .
Product Usage Instructions
- Remove the existing G3 HMI from the panel.
- Install the new G3 to M-VIEW Touch adapter panel into the existing G3 cutout using the supplied panel gasket.
- Install the new KEPS nuts (supplied) onto the new panel and tighten them evenly for uniform gasket compression. Note: Do not exceed a maximum torque of 17-inch pounds (1.92 N-m) to avoid damage to the front panel.
- Install the new M-VIEW Touch into the adapter panel using the supplied mounting clips and tighten to 6.0 pound-force inch (96 ounce-force inch) evenly for uniform gasket compression. The mounting clips may require removing the mounting foot depending on the proximity of the M-VIEW Touch to the original G3 cutout.
Model G3AD – G3 to M-VIEW® Touch Adapter Panels
The model G3AD adapter panels provide the necessary hardware to install an
M-VIEW® Touch into an existing cutout where a G3 unit once resided. These
panels are coated with a durable silver finish that matches the powder coat
used on the M-VIEW Touch series HMI. Also included in the kit are the
necessary KEPS nuts and panel gasket required to meet any NEMA 4X/IP66 (face
only) application.
Mounting Procedure
-
Remove existing G3 HMI from the panel.
-
Install the new G3 to M-VIEW Touch adapter panel into the existing G3 cutout using the supplied panel gasket.
-
Install new KEPS nuts (supplied) onto the new panel and tighten them evenly for uniform gasket compression.
Note: Tightening the KEPS nuts beyond a maximum of 17-inch pounds (1.92 N-m) may cause damage to the front panel. -
Install new M-VIEW Touch into the adapter panel using the mounting clips supplied and tighten to 6.0 pound-force inch (96 ounce-force inch) evenly for uniform gasket compression.
Adapter Panel Dimensions
Existing G3 Unit | Replacement M-VIEW Touch | A | B | C | D |
---|---|---|---|---|---|
G306A | MV-7T | 8.83 | 7.08 | 7.06 | 4.89 |
G310S | MV-10T | 12.83 | 9.50 | 10.197 | 7.931 |
G310S | MV-12T | 12.83 | 9.50 | 11.458 | 7.561 |
Ordering Information
Model NO | Description | Part Number |
---|
__
__
__
G3AD
| G306A to M-VIEW Touch
7 Cutout Adapter
| 00034621
G310S to M-VIEW Touch
10 Cutout Adapter
| 00034620
G310S to M-VIEW Touch
12 Cutout Adapter
| 00034622
Warranty
In order to consistently bring you the highest quality, full-featured products, we reserve the right to change our specifications and designs at any time. FW MURPHY product names and the FW MURPHY logo are proprietary trademarks. This document, including textual matter and illustrations, is copyright protected with all rights reserved. (c) 2021 FW MURPHY. A copy of our typical warranty may be viewed or printed by going to www.fwmurphy.com/warranty.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>