FW MURPHY TDX6 Temperature Scanner-Pyrometer Instruction Manual

June 4, 2024
FW MURPHY

FW MURPHY TDX6 Temperature Scanner-Pyrometer

FW-MURPHY-TDX6-Temperature-Scanner-Pyrometer-product

Please read the following instructions and warnings before installation. Visually inspect the product for any damage that may have occurred during shipping. It is your responsibility to have a qualified person install this unit and make sure it conforms to NEC and local codes.

Before beginning installation of this product:

  • Disconnect all electrical power to the machine
  • Make sure the machine cannot operate during installation
  • Follow all safety warnings of the machine manufacturer
  • Read and follow all installation instructions

Description

The TDX6 is an advanced design 6-point temperature scanner and pyrometer. It continually scans six grounded or ungrounded thermocouples, displays the temperature of the thermocouple selected and has adjustable trip points for each input. A trip point read/scan knob provides for display and check/adjustment of the thermocouple temperature trip point. If any trip point is reached, its output turns ON and can be used as a control signal or to initiate alarms and/or shutdown.

Specifications

  • Power Requirements (Operating Voltages): 120 VAC or 80-250 VDC, CD ignition or 24 VDC

  • Outputs:

    • Models TDX6-B and TDX6-D:
      Six (6) isolated Field-Effect Transistor (F.E.T.) outputs; 0.1 A@ 250 VDC; switches on (applies ground) above trip point and switches off (removes ground) below trip point
  • Operating Temperature: -4 to 158° F (-20 to 70° C)
    Storage Temperature: -40 to 300° F (-40 to l50° C)
    Case: ABS 1/4 DIN (90 x 90 mm)
    Scanning Speed: Complete scan in 30 seconds

  • Reset Differential:

    • F.E.T. Models: Decreases 3° F or (C)
  • Display Update Time: Updates temperature every 0.3 seconds Start-up Time Delay: Unit is locked out for 10 seconds after ignition voltage is sensed

  • Ambient Cold Junction Compensation Range:
    2° F from 32° F to 122° F (1° C from 0° C to 50° C )

  • Measurement Range: Monitor Range 0-1999° F or (C)

  • Accuracy:

    • With J-type thermocouple: from 50-150° F (J0-66° C) +3° F ( +2° C), from 150-1200° F (66-649° C) ±1.0% of reading
      With K-type thermocouple: from 400-2000° F (204-1076° C) ±1.0% of reading
  • Trip Point Accuracy: ±3° F (±2° C) of reading

  • Trip Point Adjustment Range: 0-1999 Degrees

  • Open Thermocouple Input: A number 1 appears in the display to the right of the channel number and the trip point operates

TDX6 Interface Capabilities

Model Power Source Rating
LCDT CD Ign., 120 VAC, 12/24 VDC C C1.I, Div.1, Gr. D, Haz. areas*
S5101 120 VAC, 12/24 VDC C1.I, Div.1, Gr. D, Haz. areas*
TTD™ CD Ign., negative ground, 12/24 VDC C1.1, Div.2, Gr. D, Haz. areas**
TATTLETALE® CD Ign., 120 VAC, 12/24 VDC Non-Hazardous areas

PLC’s and various annunciators not listed, contact factory

Dimension

FW-MURPHY-TDX6-Temperature-Scanner-Pyrometer-fig-1

  • An isolation barrier is needed between the TDX6 and an Annunciator rated for Class I, Division I, Group D, and Hazardous Areas.
  • When used with approved ignition. Contact FW Murphy Production Controls for details.
  • When power requirements are used as stated in the Specifications section.
  • Using grounded thermocouples introduces the risk of odd currents or voltages being imposed on the thermocouple signal which can affect the accuracy of the reading. This is an inherent problem of grounded thermocouples and the reason why we prefer ungrounded thermocouples.

Wiring

Even though the TDX6 is a six-channel temperature monitor, it will monitor and display from 1 to 6 thermocouples with equal results. When monitoring less than six temperature channels, always jumper the unused thermocouple terminals on the back of the TDX6 with the factory-installed jumper provided. The unused channel will display approximate ambient temperature.

Grounded or Ungrounded Thermocouples

NOTE:
We prefer ungrounded thermocouples. Using grounded thermocouples introduces the risk of odd currents or voltages being imposed on the thermocouple signal which can affect the accuracy of the reading.

  1. Connect the thermocouple leads to the thermocouples. (See Using Thermocouple Extension Wire for details if extension wire is needed.) NOTE: Attach wire markers to each thermocouple lead identifying polarity and thermo couple number.
  2. Remove the factory-installed jumper on the TDX6 for each thermocouple to be installed.
  3. Connect the positive lead of thermocouple TCL to the positive (+) terminal of terminal strip TCI (see wiring diagram below).
  4. Connect the negative lead of thermocouple TCI to the negative (-) terminal of terminal strip TCl.
  5. Repeat steps 2 thru 4 with each thermocouple to be monitored.FW-MURPHY-TDX6-Temperature-Scanner-Pyrometer-fig-2

NOTES:

  1. Remove the input jumper when the thermocouple is connected to the input.
  2. Thermocouple input
  3. Power input 120 VAC, 80-250 VDC, CD ignition or 24 VDC, positive or negative ground.
  4. Interfaced components must meet area classification requirements.
  5. When using the TDX6 with inductive loads, we recommend installing a suppression diode across all coils.
Connecting Power Wires
  1. Be sure the power is OFF.
  2. Connect the power input leads to the small terminal block located at the back of the TDX6. (TDX6 connections have no polarity.)

Operation Test

Perform the Operation Test after the TDX6 is installed and wired appropriately.

  1. Slowly rotate each trip point potentiometer clockwise until detent is felt.

  2. Apply power to the monitor.

  3. Verify that the TRIP POINT READ knob is in SCAN mode. The left side of the display will show the thermocouple number. The right side of the display will show the temperature of that thermocouple.
    NOTE:
    When the TRIP POINT READ knob is in the SCAN mode, depressing the THERMOCOUPLE READ push button will stop the scan sequence at the next chan­nel and display the thermocouple number and its reading. Scanning will resume approximately 3 seconds after the push button is released. With the TRIP POINT READ knob selecting a number, the push button should not be depressed.

  4. Set the TRIP POINT READ knob to the number 1 setting. On the right side of the display window, you will see the trip point reading of the TCI thermocouple. The left side of the display will continue to scroll 1 to 6 indicating that the unit is still scanning all channels.

  5. Rotate the TPl trip point potentiometer counterclockwise until the trip point TPl turns on and trips the shutdown device or alarm. Verify by observation.

  6. Rotate the trip point potentiometer TPl clockwise several turns to tum off TPl.

  7. Reset the alarm or shut off the device.

  8. Set the TRIP POINT READ knob to the TP2 position to display the TP2 temperature trip point.

  9. Repeat steps 4 thru 7 with each thermocouple to be tested.

Trip Point Adjustment

  1. Apply power to the temperature monitor.
  2. Set the TRIP POINT READ knob to the 1 position.
  3. Rotate the trip point adjustment potentiometer TPI until the display indicates the desired trip point temperature for TPl.
  4. Repeat steps 2 and 3 for each thermocouple to be set. Turn the TRIP POINT READ knob to the SCAN position to resume operations.

Using Thermocouple Extension Wire

CAUTION:
The use of non-thermocouple wire will cause inaccurate temperature sensing and erratic operation. KEEP ALL HIGH VOLTAGE WIRING SUCH AS SPARK PLUG OR IGNITION WIRES AWAY FROM THERMOCOUPLES AND EXTENSION WIRING.

If the thermocouple leads are not long enough, you will need to use a thermocouple extension wire. The thermocouple extension wire must be of the same material as the thermocouple lead wires (see chart). Metallic-shielded thermocouple wire is recommended. It provides electrical shielding as well as protection against wear and abrasion.

Thermocouple Extension Wire Color Code Chart

Thermocouple Wire| Color Code / Material
Type P/N| Extension P/N| Positive Lead| Negative Lead
J (I 0-00-0526)| Jx (00-00-3271)| White/Iron| Red/Constantan
K (I 0-00-0527)| Kx (00-00-3272)| Yellow/Chromel| Red/Alumel

To prevent problems of interference from electrical noise, DO NOT route thermocouple wires in the same conduit or within 12 in. (305 mm) of igni tion wires or alternating current conductors. When connecting the thermocouple leads, twist the wire connections, then install wire nuts, such as ceramic, which have no metal insert.

FW MURPHY PRODUCTION CONTROLS
SALES, SERVICES &ACCOUNTING 4646 S. HARVARD AVE. TULSA, OK 74135

MANUFACTURING

  • 2151 RANDON DYER ROAD ROSENBERG, TX 77471
  • 5757 FARINON DRIVE SAN ANTONIO, TX 78249

DOMESTIC SALES & SUPPORT
FW MURPHY PRODUCTS

FW MURPHY CONTROL SYSTEMS & SERVICES

INTERNATIONAL SALES & SUPPORT

CHINA

LATIN AMERICA & CARIBBEAN

SOUTH KOREA

  • PHONE: +82 70 7951 4100

  • EMAIL: INTERNATIONAL@FWMURPHY.COM.

  • FM 668576 (San Antonio, TX – USA)

  • FM 668933 (Rosenberg, TX – USA)

  • FM 523851 (China)

  • TS 589322 (China)

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals