FW MURPHY S1501 Microcontroller Annunciator Instruction Manual

June 13, 2024
FW MURPHY

FW MURPHY S1501 Microcontroller Annunciator

WIRING

FW-MURPHY-S1501-Microcontroller-Annunciator-fig-1
\(2\)

Installation

Installation Notes:

  1. Barriers must be CSA Certified for installation in Canada or NRTL Approved for installation in U.S. and must be installed in accordance with manufacturer instructions.
  2. Maximum non-hazardous area voltage must not exceed 250 Volts.
  3. Install in accordance with the Canadian Electrical Code, Part I for installation in Canada.
  4. Install in accordance with the NEC (ANSI/NFPA 70) and ANSI/ISA RP12.6. for installation in U.S.
  5. If Dual Channel Barrier with Volt/Ohm parameters are used , both channels must be positive and have the same polarity and the following parameters shall apply.
    • one 14V (max), 150 Ohm (min)
    • one 14V (max), 150 Ohm (min)
  6. If two single channel barriers with Volt/Ohm parameters are used for a two-barrier configuration, both channels must be positive and have the same polarity and the following parameters shall apply to each channel:
    • one 14V (max), 150 Ohm (min)
    • one 14V (max), 150 Ohm (min)