Fronius TS 100A-1 Smart Meter User Guide
- June 13, 2024
- Fronius
Table of Contents
Fronius TS 100A-1 Smart Meter User Guide
FIND
MORE INFORMATION
manuals.fronius.com/html/4204260350
Perfect Welding / Solar Energy / Perfect Charging
WARNING! Incorrect operation and incorrectly performed work can cause serious personal injury or material damage. The Fronius Smart Meter may only be installed and commissioned by trained personnel and only within the scope of the technical regulations. Before working with the device, read and understand all enclosed, printed and online documents! This document does not describe all of the possible system configurations.
FRONIUS INTERNATIONAL GMBH
SOFTWARE REQUIREMENTS
Fronius Data manager 2.0| ≥ 3.16.1 version
Fronius Symo Hybrid| ≥ 1.16.1 version
MEASURING INPUT
Nominal voltage (1-phase) range| 230 V (-30 % to +20 %)
Self-consumption – voltage path (max. voltage)| ≤ 8 VA
Nominal frequencyTolerance| 50 – 60 Hz45 – 65 Hz
Nominal current, lb| 5 A
Maximum current, Imax| 100 A
Starting current| 40 mA
Short-time overload(EN IEC 62053-21, EN IEC 62053-23)| 30 lmax / 0.001 s
Self-consumption – current path (max. current)| ≤ 1 W
Power factor Operating range(EN IEC 62053-21, EN IEC 62053-23)| cosφ 0.5 ind –
0.8 cap
Current distortion factor| In acc. with EN 62053-21
OUTPUTRS485 communication (Electrically isolated from measuring input)
StandardAddresses| RS485 – 3 conductors1 – 255
Baud rate| 9600, 19200 bit/s
Response time| ≤ 200 ms
INSULATION (EN IEC 62052-11, EN IEC 62053-21)
Installation category| III
Degree of pollution| 2
Insulation voltage| 4000 VAC RMS (1 min)
ELECTROMAGNETIC COMPATIBILITY
Emission test| In acc. with EN IEC 62052-11, EN 50470-3
Immunity test| In acc. with EN IEC 62052-11, EN 50470-3
OPERATING CONDITIONS
Reference temperature| 25 °C (± 5 °C)
Operating range| -25 to +65 °C
Temperature limit for storage and transport| -30 to +80 °C
Mechanical environment Electromechanical environment| M2E2
HOUSING
Housing| 2 modules according to DIN 43880
Sealable housing/terminal cover|
Connection| Screw connection
Mounting| Can be snapped onto 35 mm DIN rail
Housing material| Noryl, self-extinguishing
Degree of protection (EN 60529)| IP51 housing, IP20 connections
Weight| 160 grams
TERMINALS – MEASURING INPUT
Wire| max. 25 mm²
Recommended torque| max. 2.8 Nm
TERMINALS – DATA OUTPUT
Wire| min 0.05 mm²
Recommended torque| max. 0.4 Nm
Detailed, country-specific warranty terms are available on: www.fronius.com/solar/warranty
- SWITCH OFF THE CIRCUIT BREAKER **(Step: 1)
**
-
MOUNT THE SMART METER (Step: 2)
-
a 1 PHASE, 2 WIRES (Step: 3a)
-
b 1 PHASE, 2 WIRES (Step: 3b)
-
MOUNT THE PROTECTIVE COVER (Step: 4)
-
CONNECT THE DATA CABLES (Step: 5)
-
SET UP THE TERMINATING RESISTOR (Steps: 6-7)
-
MOUNT THE CONNECTOR COVERS (Step: 8)
-
SWITCH ON THE CIRCUIT BREAKER (Step: 9)
-
NAVIGATE IN THE SETTINGS **(Step: 10)
1 x page up / value up
1 x page down / value down
2 sec. adjust / confirm
**
-
ENTER THE SETTINGS (Step: 11)
-
SETUP THE PASSWORD (Step: 12)
Factory default: 2633
-
SETUP THE ADDRESS (Step: 13)
Factory default: Modbus Address 001
-
EXIT THE SETTINGS (Step: 14)
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>