Product Information

  • Product Name: PowerValue 11 6-10 kVA
  • Manufacturer: ABB
  • Product Manual: https://manual-hub.com/
  • Manual Version: 04-3628_ABB_PVA11_T_6-10kVA_EN_REV-B.doc

Product Usage Instructions

Safety Instructions:

  • Read and follow all safety instructions provided in the manual.
  • The UPS system contains components that carry high currents and voltages. Only perform operations inside the UPS if you are a service engineer from the supplier or an authorized agent.
  • The UPS system must be properly grounded to earth and is IP 20 rated against electrical shock and foreign objects.

Site Planning and Positioning:

  • Plan the installation before starting.
  • Choose an appropriate location for positioning the UPS. Please refer to the complete user manual for detailed instructions on installation, commissioning, operation, and maintenance of the UPS and batteries. It is important to follow all instructions provided in the manual for safe and proper usage of the product. For any further assistance or support, please contact the manufacturer or their authorized agents.

FOREWORD

The UPS System operates with mains, battery or bypass power. It contains components that carry high currents and voltages. The properly installed UPS System is grounded to earth and IP 20 rated against electrical shock and foreign objects. OPERATIONS INSIDE THE UPS MUST BE PERFORMED BY A SERVICE ENGINEER FROM THE SUPPLIER OR FROM AN AGENT AUTHORIZED BY THE SUPPLIER. This user manual contains guidelines to check delivery, installing and commissioning of the UPS and is intended for people who plan the installation, install, commission and use or service the UPS. The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. THE INSTRUCTIONS IN THIS MANUAL SHOULD BE FOLLOWED DURING INSTALLATION, OPERATION AND MAINTENANCE OF THE UPS AND BATTERIES. Read carefully all instructions and save this manual for future reference.

SYMBOLS

The following symbols are used in this manual, the list below describes each symbol.ABB-PowerValue-11-6-10-kVA-External-Battery-fig-1
\(1\)

SAFETY INSTRUCTIONS

Operator precautions
The user must follow the precautions and only perform the described operations. Also in these measures the operator of the UPS System must adhere to the instructions in this manual. Any deviations from the instructions could be dangerous to the user or cause accidental load loss.
The only user operations permitted are:

  • Use of the LCD control panel (LCD Display) and Maintenance Bypass (if present)
  • Start up and shut down of the UPS (excluding the commissioning start up)
  • Operation of additional connectivity devices
  • THE SUPPLIER DOES NOT TAKE ANY RESPONSIBILITY FOR DAMAGES CAUSED THROUGH WRONG MANIPULATIONS OF THE UPS SYSTEM.

WARNING! IT IS PROHIBITED TO REMOVE ANY SCREWS FROM THE UPS SYSTEM OR FROM THE BATTERY CABINET: DANGER OF ELECTRICAL SHOCK.
WARNING! HIGH FAULT CURRENTS (LEAKAGE CURRENTS): BEFORE CONNECTING THE MAINS YOU MUST ENSURE THAT THERE IS A PROPER EARTH CONNECTION!
WARNING! THE USER MUST DISPLAY A WARNING SHIELD ON ALL PRIMARY UPS CIRCUIT BREAKERS. THE SERVICE PERSONNEL HAS TO BE INFORMED ABOUT DANGEROUS VOLTAGES. THE WARNING PANELS MUST CONTAIN THE FOLLOWING TEXT: “ BEFORE STARTING WITH THE MAINTENANCE WORK ON THE CIRCUIT BREAKERS , MAKE SURE THE UPS IS ISOLATED.”

Environmental Considerations

To operate the UPS at the best efficiency point, your installation site should meet the environmental parameters outlined in this manual. Excessive amount of dust in the operating environment may cause damage or lead to malfunction. The UPS should be always protected from the outside weather and sunshine. The operating environment must meet the weight, airflow, size and clearance requirements specified in the technical datasheet. Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or in an environment exceeding environmental requirements here below. An ambient temperature of +20°C to +25°C is recommended to achieve a long life of the UPS and batteries. The cooling air entering the UPS must not exceed +45 °C and the humidity should be below 95% (non-condensing).

Declaration of Safety conformity and CE marking
PowerValue 11 is designed, manufactured and commercialized in accordance with the standard EN ISO 9001 of Quality Management Systems. The marking shows the conformity to the EEC Directive by means of the application of the following standards in accordance with the specifications of the harmonized standards:

  • 2006/95/EC Low voltage directive.
  • 2004/108/EC Electromagnetic Compatibility directive (EMC).

Standards as reference:

  • EN- 62040-1. Uninterruptible power supply (UPS). Part 1-1: General and safety requirements for UPS’s used in accessible areas by end users.
  • EN- 60950-1. IT equipment. Safety. Part 1: General requirements.
  • EN- 62040-2. Uninterruptible power supply (UPS). Part 2: EMC requirements.

The suppliers responsibility is excluded in the event of any modification or intervention in the product by the customer’s side.

| Product Standards| Standards
---|---|---
Safety| EN 62040-1| EN 60950-1
| | EN 61000-4-2
| | EN 61000-4-3
Electromagnetic Compatibility (EMC)| | EN 61000-4-4
| EN 62040-2| EN 61000-4-5
| | EN 61000-4-6
| | EN 61000-4-8
| | EN 61000-4-11
| | EN 61000-2-2

Table 1: Standards

Inquiries
Address inquiries about the UPS to the local office or agent authorized by the supplier. Please note the type code and the serial number of the equipment and contact your nearest agent authorized by the supplier. The Code and the serial no. are shown on the nameplate of the product. For further information on troubleshooting, go to Section 6.

Operation

  • Do not remove the enclosure of the UPS. This system is to be serviced by qualified service personnel only.
  • Do not disconnect the mains cable from the UPS or the building wiring socket during operation as this would remove the ground to the UPS and of all connected loads.
  • An integral single emergency switching device which prevents further supply to the load by the UPS in any mode of operation should be provided in the building wiring installation.
  • An appropriate disconnect device as short-circuit backup protection should be provided in the building wiring installation.
  • In order to fully disconnect the UPS, press the OFF button. Only after the UPS is shutdown, disconnect the mains load.
  • Indiscriminate operation of switches may cause output loss or damage to equipment. Refer to instruction before conducting any control.
  • While the UPSs work as a parallel system, the external parallel cable should be reinforced insulation.

Maintenance, servicing and faults
Repairs may be carried out only by qualified maintenance personnel as the UPS operates with hazardous voltages.

WARNING! EVEN AFTER THE UNIT IS DISCONNECTED FROM THE MAINS POWER SUPPLY, COMPONENTS INSIDE THE UPS ARE STILL CONNECTED TO THE BATTERY WHICH ARE POTENTIALLY DANGEROUS. Before carrying out any kind of service and/or maintenance, disconnect the batteries. Verify that no current is present and no hazardous voltage exists in the capacitor or BUS capacitor terminals. Batteries must be replaced only by qualified personnel.
WARNING! THE BATTERY CIRCUIT IS NOT ISOLATED FROM THE INPUT VOLTAGE. HAZARDOUS VOLTAGES MAY OCCUR BETWEEN THE BATTERY TERMINALS AND THE GROUND. VERIFY THAT NO VOLTAGE IS PRESENT BEFORE SERVICING. When changing the batteries, replace with the same quantity and  the same type of batteries.Replace the fuse only by a fuse of the same type and of the same amperage in order to avoid fire hazards.

Installation

Delivery, Transportation, Positioning and Storage

  • Receipt of the UPS and visual inspection
    Upon receiving the UPS, carefully examine the packing container and the UPS for any sign of physical damage. In case of damage, notify immediately the carrier. The packing container of the UPS protects it from mechanical and environmental damage. To increase its protection, the UPS is wrapped with a plastic sheet. Preserve the packaging for later re-use.

  • Unpacking
    After examining the package, unpack the equipment by removing the packing and shipping materials. Cut the plastic poly-straps around the shipping container and remove the corrugated carton and the UPS foam on the top of the UPS. With one or two people on each side of the UPS, lift the UPS out of the pallet. Keep the UPS always in upright position and do not drop the equipment.

WARNING! THE PLASTIC POLY-STRAPS AROUND THE SHIPPING CONTAINER ARE UNDER TENSION. WHILE CUTTING, DO NOT FACE THEM AS THEY MAY SPRING BACK AND CAUSE INJURIES.

Examine the UPS for any sign of damage and ensure that the received UPS corresponds to the material indicated in the delivery note. Notify your carrier or supplier immediately if damage is apparent.
2.1.3 Storage of UPS
If you plan to store the UPS prior to use, keep the UPS in a dry, clean and cool storage room with an ambient temperature between (-15 °C to +60°C) and humidity of less than 95% non-condensing. The packing container has been removed protect the UPS from dust. Keep the UPS always in upright position and do not drop the equipment.

Site Planning and Positioning

  • Planning before the installation
    The appropriate place of installation for the unit is to be selected in such a way that the danger of damage to the UPS is minimized and a long service life of the device is thus ensured. Please observe the following instructions:

    • Install the UPS in the indoor area.
    • Leave 50cm of space on each side of the cabinet to enable cooling airflow and ensure that the circulation of air to the ventilation slits is not obstructed.
    • Avoid excessively high temperature and excessive moisture.
    • Make sure that the floor surface is solid and suitable for the wheeling and weight.
  • Positioning

  • PowerValue 11 (6-10 kVA) have wheels that make the positioning of the UPS simple after it has been unpacked. However, if the unpacking area is distant from the installation site, it is recommended to transport the UPS with a forklift before unpacking the UPS. It is recommended to install external battery cabinet(s) next to the UPS unit. Check before the installation that the battery voltage values in the type plate of the UPS and external battery cabinets are the same. Water condensing may occur if the UPS is unpacked in a very low temperature environment. In this case it is necessary to wait until the UPS is fully dried inside out before proceeding installation and use to avoid hazards and electric shock.

General Characteristics
Rear ViewABB-PowerValue-11-6-10-kVA-External-Battery-fig-1
\(2\)

Electrical Installation

Commissioning
The UPS must be commissioned by a fully trained and authorized field service engineer before being put into use. The commissioning of the UPS involves the connection of the UPS and batteries, the verification of the electrical installation and operating environment of the UPS, the controlled start-up and testing of the UPS and customer training.

WARNING!

  • OPERATIONS INSIDE THE UPS MUST BE PERFORMED BY A SERVICE ENGINEER FROM THE SUPPLIER OR FROM AN AGENT AUTHORIZED BY THE SUPPLIER.
  • DO NOT OPERATE IN CASE OF PRESENCE OF WATER OR MOISTURE.
  • BY OPENING OR REMOVING THE UPS-COVERS YOU ARE EXPOSED TO DANGEROUS VOLTAGES.
  • PHYSICAL INJURY OR DEATH MAY FOLLOW, OR DAMAGE MAY OCCUR TO THE UPS, OR THE LOAD EQUIPMENT IF THESE INSTRUCTIONS ARE IGNORED

To ensure correct operation of the UPS and its ancillary equipment it is necessary to provide the mains cables with appropriate fuse protection.
Recommended Cable Sections and Fuse Ratings
Follow the recommendations in Table 2 or respect the local standards.

Model 6kVA 10kVA

Protective earth conductor

Minimum cross section

| UL1015

6mm2 (8AWG)

| UL1015

10 mm2 (6AWG)

Input L, N, G

Minimum conductor cross section

| UL1015

3x6mm2 (8AWG)

| UL1015

3×10 mm2 (6AWG)

Input breaker| 40A/250VAC| 63A/250VAC
Output L,N, G

Minimum conductor cross section

| UL1015

3x 6mm2 (8AWG)

| UL1015

3x 10 mm2 (6AWG)

External Battery Cabinet

Positive Pole(+), Negative pole(-), Neutral Pole Minimum conductor cross section

| UL1015

2x 6mm2 (8AWG)

| UL1015

2x 10 mm2 (6AWG)

External Battery Cabinet Fuse

in Positive Pole(+), Negative pole(-), Neutral Pole

|

30A/240VDC

|

60A/240VDC

External Battery Cabinet Breaker

in Positive Pole(+), Negative pole(-), Neutral Pole

|

32A/240VDC

|

50A/240VDC

Torque for fixing above terminals| 3.95~4.97Nm (35~44 1b in)

Table 2: Recommended Cables and Fuses
It is suggested to install an external isolating device against current back feed between Mains input and UPS as indicated in Figure 2.ABB-
PowerValue-11-6-10-kVA-External-Battery-fig-1 \(3\)

Figure 2: External Backfeed Isolation

WARNING! AFTER THE DEVICE IS INSTALLED, ADD A LABEL WITH THE FOLLOWING WARNING ON THE EXTERNAL AC CONTACTOR: “RISK OF BACKFEED VOLTAGE. ISOLATE THE UPS BEFORE OPERATING ON THIS CIRCUIT AND CHECK FOR HAZARDOUS VOLTAGE”

The UPS unit has the following power connections:

  • Rectifier (In): 1 phase (input L), 1 Neutral (input N) and protective earth (input G) connection for the rectifier input
  • Load (Out): 1 phase (output L), 1 Neutral (output N) and protective earth (output G) connection for the load output
  • External battery: Plus (+), Minus (-) and protective earth (G) connection for the external batteries Paralleling: Parallel Jumper 1 and 2ABB-PowerValue-11-6-10-kVA-External-Battery-fig-1 \(4\)

Figure 3: Terminal block wiring diagram

  1. The output of the UPS may be energized even if the UPS is turned off. To ensure that the UPS has no power in the output, power off the UPS, and cut off the mains power supply. Wait the UPS shut down completely.
  2. Open the terminal block cover located on the rear panel of UPS (refer to diagram on Section 2.3.1).
  3. Do not use the wall jack because its rated current is higher than the UPS maximum input current.
  4. Install the protective earth (ground) wire (refer to Figure 3). It is recommended to use green or green/yellow wires.
  5. Connect the input and output wires to the corresponding terminals Use appropriate tools and terminal splices to guarantee a reliable contact between the wires and the terminal blocks.
    • Note:
    • If the UPS is single in a system, JP1 and JP2 must be connected.
    • If the UPS is used in parallel, the jumper between JP1 and JP2 must be removed.
    • The battery connectors are only used for the UPS using external batteries
  6. Install an output breaker between the output terminal of the UPS and the load. It is recommended to use a breaker with leakage current protection.
  7. Turn off all the loads. Then connect the load to the UPS and finally turn on the loads one by one.
  8. After completing the steps above, check that all wires are connected correctly and tightly.
  9. Turn On the mains power switch and turn the input breaker to the On position. The UPS will charge the batteries automatically. The UPS can be immediately used in inverter mode but it is recommended to charge the batteries completely to guarantee the maximum back up time.

Note: The power consumption in the start-up of inductive loads (such as monitors and laser printers) is very high. If such loads are connected to the UPS, the start-up power consumed by these devices should be considered when calculating the capacity of the UPS. If this is not taken into consideration, the UPS goes often in overload and may turn off easily depending on its dimensioning.

Battery Connections (Model without internal batteries)

WARNING! ANY INCOMPLIANCE MAY RESULT IN THE RISK OF ELECTRIC SHOCK. FOLLOW THE INSTRUCTIONS THE UPS CONTAINS HIGH DC VOLTAGES. A QUALIFIED PERSON MUST DO THE CONNECTIONS BETWEEN THE UPS AND THE EXTERNAL BATTERIES.

The nominal DC voltage of external battery pack is 240VDC. Each battery pack consists of 20 pieces of 12V maintenance free batteries in series. To achieve longer backup time, it is possible to connect several battery packs, but the principle of “same voltage, same type” should be strictly followed. The external battery pack must be independent for each UPS. Two or more UPS cannot use the same external battery pack. Follow the steps below to connect the battery packs.

  1. Ensure the UPS is not powered on and the mains input breaker is set in the “OFF” position.
  2. A DC breaker must be installed between the external battery pack and the UPS. The capacity of breaker must be higher than specified in the general specification.
  3. With the external battery pack breaker in “OFF” position, connect the 20 batteries in series.
  4. Connect the external battery pack to the battery terminals. Check the polarity if the connection is correct.
  5. Turn the breaker of the battery pack to the “ON” position. The UPS will power on and start to charge the battery pack.

Emergency Power Off (EPO)

The EPO connector gives the user the possibility to block the output of the UPS in case of an emergency. This connector can be configured as Normally Closed (NC) of Normally Opened (NO) through the USD or RS232 port. As a default the EPO is Normally Closed (NO) by a jumper in the rear panel. If the jumper is removed, the UPS output will not supply energy to the load until the EPO status is again modified.

To recover to normal status, the EPO connector should first be closed. Then, enter the LCD menu (refer to Section 0) to clear the EPO status. The UPS alarm will stop and the bypass mode will be recovered. To have the UPS in inverter mode, the selection has to be made by manual operation. The polarity of connector could be inversed by setting in LCD menu as from section 0. Contact your local supplier for further information before modifying the settings.

Installation Checklist

  • All packing materials and restraints have been removed from each cabinet.
  • Each cabinet in the UPS system is placed in the installed location. .
  • All conduits and cables are properly routed to the UPS and auxiliary cabinets.
  • All power cables are properly sized and terminated.
  • A ground conductor is properly installed. Battery cabinet installation instructions have been completed. Air conditioning equipment is installed and operating properly.
  • The area around the installed UPS system is clean and dust-free. Adequate workspace exists around the UPS and other cabinets.
  • Adequate lighting is provided around all UPS equipment. Any optional accessories are mounted in their installed location and properly wired.
  • Summary alarms and/or building alarms are wired appropriately. (OPTIONAL) Start-up and operational checks performed by authorized service personnel.
  • All network connections are completed.

OPERATION

This chapter describes how to operate the UPS through the LCD display.

WARNING! ONLY PERSONS WHICH HAVE BEEN TRAINED BY SERVICE TECHNICIANS OF THE SUPPLIER OR HIS AUTHORIZED SERVICE PARTNERS ARE ALLOWED TO OPERATE THE CONTROL PANEL OF THE UPS. ALL OTHER INTERVENTIONS ON THE UPS SYSTEM HAVE TO BE DONE ONLY BY SERVICE TECHNICIANS OF THE SUPPLIER.

The only user permitted operations are:

  • Operate the LCD display
  • Start up and shut down of the UPS of the user field (excluding the commissioning start up)
  • Operation of additional SNMP adapters and their software

Control Panel

The user-friendly control panel is composed of two parts:

  • Selection Keys
  • Power Management LCD Display (PMD)

Selection KeysABB-PowerValue-11-6-10-kVA-External-Battery-fig-1
\(7\)ABB-PowerValue-11-6-10-kVA-External-
Battery-fig-1 \(8\)

LCD Display
The LCD display gives the user a complete overview on the status of the UPS. It shows information on the input, output, battery, load parameters, working mode and also the settings on voltage, frequency and bypass presence.

UPS state| Normal LED (Green)| Battery LED (Yellow)| Bypass LED (Yellow)| Fault LED (Red)
---|---|---|---|---
Bypass mode with no output| –| –| C| D
Bypass mode with output| –| –| A| D
Turning on| B| B| B| B
Line mode| A| –| –| D
Battery mode| A| A| –| D
HE mode| A| –| A| D
Battery test mode| B| B| B| B
Fault mode| –| –| D| A
Warning mode| D| D| D| C

Figure 5: LED representation

  • A: Lightened constantly
  • B: LEDs 1 to 4 Lightened circularly
  • C: Flashing
  • D: Depends on the fault/warning status or other status
UPS condition Buzzer status
Fault active Continuous
Warning active Beep every second
Battery output Beep every 4 seconds, if battery low, buzzer Beep every second
Bypass output Beep every 2 minutes
Overload Beep twice every second

Figure 6: Definition of Alarms
When powering on, the LCD displays a welcome message for a few seconds and then enters the default page that shows the UPS status. From any screen, if the user does not press any button for more than 15 minutes, the default screen is displayed.
The status screen provides the following information:

  • Status summary, including operating mode and load information
  • Alarm status, if any are present (including fault and warning information)
  • Battery and charger status (including battery voltage, charge level and charger status)
  • Running information including parallel UPS and running time

For detailed information on how to operate the LCD, see Section 3.5.

Turning On the UPS

WARNING! SWITCH OFF THE CONNECTED LOADS BEFORE TURNING ON THE UPS. SWITCH ON THE LOADS ONE BY ONE AFTER THE UPS IS TURNED ON.

Turning on the UPS with mains

  1. Check that all cables are connected correctly and well-fixed mechanically. Check that the position of the breaker on the external battery pack is “ON”.
  2. Set input breaker to “ON” position. The fans are activated and the LCD shows a welcome screen. The UPS then performs a self-test and finally displays the UPS status screen.
  3. Press the power-on button continuously for more than 1 second. The alarm buzzer will sound for 1s and the UPS start-up will take place.
  4. After a few seconds, the UPS goes to Online mode. If the mains power is abnormal, the UPS will transfer to Battery mode without interruption of the output the UPS.

Turning on the UPS without mains (Cold start)

  1. Check that all cables are connected correctly and well-fixed mechanically. Check that the position of the breaker on the external battery pack
  2. Pressing the power-on button continuously for more than 100ms, the UPS is powered on. The fan are activated and the LCD shows a welcome screen. The UPS then performs a self-test and finally displays the UPS status screen.
  3. Pressing the power-on button continuously for more than 1s, the alarm buzzer sounds for 1s and the UPS start-up takes place.
  4. After a few seconds, the UPS goes to Battery mode. When the UPS is fed with power from the mains, the UPS transfers to Online mode without interruption in the output of the UPS.

Turning Off the UPS

WARNING! SWITCH OFF ALL OF THE CONNECTED LOADS BEFORE TURNING OFF THE UPS

Turning off UPS with mains

  1. To turn off the inverter of UPS, press the button continuously for more than 3s. The alarm buzzer will sound for 3s and the UPS will go to Bypass mode. Note: the output is still energized. 2 – In order to remove the UPS output power, disconnect the mains power supply. A few seconds later, the display will shut down and no output voltage will be available in the UPS output terminal.

Turning off UPS without mains

  1. To power off the UPS, press the power on/off button continuously for more than 3s.
  2. The alarm buzzer will sound for 3s. The output power will be immediately cut-off. 2 – After a few seconds, the display will shut down and no voltage will be present in the UPS output.

Operating Mode
Different symbols indicate the status and the operating mode of the UPS. Such symbols appear always in the position indicated in Figure 8.ABB-
PowerValue-11-6-10-kVA-External-Battery-fig-1 \(12\)ABB-PowerValue-11-6-10-kVA-External-Battery-fig-1
\(13\)

ECO Mode / High Efficiency Mode
If ECO mode (High Efficiency – HE Function) is enabled, after the UPS is turned on, the power used by the load is directly supplied from the mains power via internal filter. This guarantees a higher efficiency of the UPS. In case of mains failure, the UPS transfers to Online mode or Battery mode and the load is supplied continuously. This function can be enabled through the LCD settings in Bypass mode. Enter the power strategy Settings menu as indicated in Section 3.5.1.6. The overall efficiency in Eco mode is higher than 96% of UPS, saving energy and reducing the running costs.
Note:

  • The level of load protection is lower than in Online mode since the load is directly supplied from the mains.
  • The transfer time of the UPS output from Eco mode to Battery mode is about 10ms. This function is not suitable for sensitive loads and in regions where mains power is very unstable.

Converter Mode
In converter mode, the UPS runs with fixed output frequency (50Hz or 60Hz). This mode is commonly used with loads that are very sensible to frequency variations. In case of mains failure, the UPS transfers to Battery mode and the load is supplied continuously. This function can be enabled through the LCD settings in Bypass mode. Enter the power strategy Settings menu as indicated in Section 3.5.1.6.
Note: The load capacity of the UPS is de-rated to 60% in converter mode.

LCD Operation
Information regarding the status of the UPS, measurements, events and general information on the UPS are available through the LCD display. This chapter describes how to navigate through the display and how to adjust the user’s settings.

Navigation

  • From the UPS status screen, press or for less than 1s for information on alarm, parallel system and battery.
  • From the UPS status screen, press for more than 1s to enter the main menu. The main menu includes the following submenus: UPS status, event log, measurements, control, identification, settings.
  • See Figure 9 for details on how to navigate through the menus and submenus.ABB-PowerValue-11-6-10-kVA-External-Battery-fig-1 \(16\)

UPS Status
Contains general information on the status of the UPS.
Event log
Displays the last 50 events, alarms and faults occurred in the UPS. The alarms are indicated by the corresponding illustration, event code and operating time of UPS when the event occurred. To navigate through the events and alarms, press or for less than 1s.

Measurements
Several measurements are displayed in the menu such as output voltage, frequency, current, load capacity, input voltage and frequency. To navigate through the measurements, press or for less than 1s.
Control
From this menu, the user can give commands to the UPS. It is possible to change the UPS mode, perform battery tests, reset some status and restore settings. Pressing on the control submenu, the display would enter another menu tree with the following information:

  • Single UPS turn off: This command is used to turn off one UPS in a parallel system. The other UPS continue to run to supply the load in the parallel system.
  • Single UPS battery test: This command is used to control one UPS in a parallel system to do the battery test singularly. The other UPS do not perform the battery test.
  • Parallel UPS battery test: This command is used to perform the battery test in all UPS in a parallel system simultaneously.
  • Clear EPO status: Once the EPO status is enabled, the UPS output is cut-off. To recover the normal status, EPO connector must first be closed. Enter this menu to clear the status of EPO. The
  • UPS will stop alarming and will recover in Bypass mode. Note that the UPS needs be turned on by manual operation.
    • Example: Clearing the EPO status

Note: First make sure the EPO signal is inactive or the LCD will show that the EPO active status couldn’t be cleared.

  • Reset fault status: When a failure occurs, the UPS goes to Fault mode and the buzzer alarm sounds. After checking the reason of the failure and taking the appropriate corrective actions, enter this menu to reset the error status and recover the normal status. The UPS alarm will stop and will go to Bypass mode.
  • Restore factory settings: All the factory settings are recovered. Note that this operation can only be executed when the UPS is in Bypass mode.

Figure 11 gives an overview on how to navigate on the control menu.ABB-
PowerValue-11-6-10-kVA-External-Battery-fig-1 \(20\)

Figure 11: Control menu tree

Identification

  • Press on the Identification menu to navigate through its data. The identification information includes UPS serial number, firmware serial number and model type.
  • Press 1s to return to the last main menu.

User’s Settings
Contact your local distributor for further information before using the settings. Some settings can impact on the performance of the UPS and others can enable and disable functions within the UPS. Failures and reduced protection can occur if the equipment is not set in an adequate way. Note that most settings should be done only with the UPS in Bypass mode. Press in the Identification menu to enter the Setting menu. If the User password is enabled, the user must enter the password by pressing the buttons , , and . The setting menu is as indicated in Table 3

Submenu item Optional Values Default value
User password enabled/disabled disabled
Audio alarm enabled/disabled enabled
Rated output voltage 208/220/230/240V 230V
Output frequency autosensing/50/60Hz autosensing
Power strategy** normal/high efficiency/ converter normal
DC start enabled/disabled enabled
Site wiring fault alarm enabled/disabled enabled
Ambient temperature warning enabled/disabled enabled
Automatic battery tests period 0-31days 7days
Auto Restart enabled/disabled enabled
Automatic overload restart enabled/disabled enabled
Auto Bypass enabled/disabled enabled
Short circuit clearance enabled/disabled disabled
Bypass voltage low limit 110~215V 176V
Bypass voltage high limit 245~276V 264V
Bypass frequency low limit 1%~10% 10%
Bypass frequency high limit 1%~10% 10%
Language Simple Chinese English
HE voltage low limit 1%~10% 5%
HE voltage high limit 1%~10% 5%
Submenu item Optional Values Default value
--- --- ---
HE frequency low limit 1%~10% 5%
HE frequency high limit 1%~10% 5%
Battery quantity*** 19/20/21 20
Set running time Day:hour:minute:second 0000:0000:00~9999:23:59:59 Running

time
LCD contrast| -5~+5| 0

  • Password is USER when enabled.
  • Read Section 3.4, before using high efficiency or converter function.
  • Ensure the real battery quantity is same as the settings not to damage the batteries.ABB-PowerValue-11-6-10-kVA-External-Battery-fig-1 \(23\)

Example: Setting the rated output voltage value Paralleling the units
N+X is the most reliable power structure. N represents the minimum UPS number that the total load needs and X represents the number of redundant UPS. The larger is X, higher is the reliability of the system. With PowerValue 11, up to 4 UPS can be connected in parallel to obtain output power sharing and power redundancy.
Installation and operation

  1. Prepare the input and output wires, the output breaker and the parallel cable.

  2. Use a standard 25-pin communication cable (25 colors) ideally shorter than 3m.

  3. Remove the cover plate of the parallel port in the UPS

  4. Connect the UPS, one by one, with the parallel cable and re-screw the parallel port cover supplied with the UPS accessories.

  5. Strictly follow the Chapter 2 and the wiring requirements of single UPS to perform the wiring of each UPS. Connect the output wires of each UPS to an output breaker panel.

  6. Disconnect the Jumpers JP1 and JP2 of the terminal block, then connect each output breaker to a main output breaker and then to the loads.

    • Each UPS needs an independent battery pack. Please refer to the wiring diagram in the following diagram. The distance between the UPS in parallel and the breaker panel is should be lower than 20 meters. The difference between the wires of the input and the output of the UPS is required to be less than 20%.
      ABB-PowerValue-11-6-10-kVA-External-Battery-fig-1
\(25\)
  7. Confirm that the output breaker of each UPS is switched OFF.

  8. Switch on the input breaker of the each UPS. The UPS will start running in bypass mode. Observe the UPS displays to check if there are warnings or fault information. Measure the output voltage of each UPS separately to check if the voltage difference between them is lower than 1V. Ifthis difference is higher than 1V, check the wiring.

  9. Press the button of one UPS and each UPS will start to turn on. All UPS will transfer to inverter mode simultaneously. Measure the output voltage of each UPS separately to check if the voltage difference between them is lower than 0.5V. If this difference exceeds 0.5V, the UPS have to be regulated.

  10. Press the button of one UPS and observe that each UPS will turn off and transfer to Bypass mode. Switch on the output breaker of each UPS to parallel the output of all UPS.

  11. Press the button of one UPS and observe that each UPS will turn on. The UPS will then work in parallel Online Mode.

Adding an UPS to an existing parallel system
A main maintenance mechanical switch or static switch must be installed in a parallel system.

  1. Regulate the output voltage of the new UPS separately. Check if the output voltage difference between the new UPS and the parallel system is lower than 0.5V.
  2. Ensure that the bypass of the parallel system is normal and that the bypass setting is “enabled”. Remove the cover plate of the maintenance switch on the rear panel of each UPS. The UPS system will transfer to bypass automatically.
  3. Set the main maintenance switch or static switch from “UPS” to “BPS”. Switch off the main output breaker and the main input breaker, the UPS will shut down.
  4. Ensure the UPS are completely shut down. Add the new UPS and reinstall the new UPS parallel system by following steps 1) to 6) on Section 3.6.1.
  5. Switch on the main input breaker and the main output breaker. Set the main maintenance switch or static switch from “BPS” to “UPS”, then set the UPS maintenance switch from “BPS” to “UPS” and screw the maintenance cover plate back again. Press the button on one UPS. Each UPS will turn on and then they will all work in parallel in Online mode.

Removing a Single UPS from a parallel system
A main maintenance mechanical switch or static switch must be installed in a parallel system.

  1. Ensure the bypass of the parallel system is normal and that the bypass setting is “enabled”. Remove the cover plate of maintenance switch on the rear panel of each UPS. The UPS system will transfer to bypass automatically.
  2. Set the maintenance switch of each UPS from “UPS” to “BPS”.
  3. Set the main maintenance switch or static switch from “UPS” to “BPS”
  4. Switch off the main output breaker and the main input breaker. The UPS will shut down.
  5. Ensure the UPS are completely shut down and remove the chosen UPS from the system. Reinstall the new UPS parallel system by following steps 1) to 6) on Section 3.6.1.
  6. If the removed UPS or the remained UPS will be used in a standalone mode, then JP1 and JP2 on the terminal block should be connected with a short connection wire.
  7. Switch on the main input breaker and the main output breaker.
  8. Set the main maintenance switch or static switch from “BPS” to “UPS”, then set the UPS maintenance switch from “BPS” to “UPS”.
  9. Screw the maintenance cover plate back again. Press the button on one UPS. Each UPS will turn on and then they will all work in parallel in Online mode.

COMMUNICATION

Interface

  • USB
    The USB port present in the back of the UPS is compliance with USB 1.1 protocol.

  • Dry contact
    PowerValue 11 UPS has independent dry contact interf aces. Please contact your local supplier for details. Figure 17 and Table 4 describe the DB-9 connector.

Pin # Description I/O
1 UPS Failure Output
2 Summary Alarm Output
3 GND Input
4 Remote Shutdown Input
5 Common Input
6 Bypass Output
7 Battery Low Output
8 UPS ON Output
9 Line Loss Output

Intelligent Slot
PowerValue 11 is equipped with an intelligent slot for other optional cards for remote management of the UPS through internet / intranet. Please contact your local supplier for further information.

Monitoring Software
WinPower is a UPS monitoring software that allows the user to monitor the UPS. This software provides a remote and safe shutdown for multi multi-client systems in case of absence of power in the output of the UPS.ABB-
PowerValue-11-6-10-kVA-External-Battery-fig-1 \(27\)

Figure 18: Monitoring Software WinPower
Installation procedure:

  • Go to the website http://www.ups-software-download.com/.
  • Choose your operating system and follow the instructions described in the website to download the software.
  • When downloading the files from the internet, enter the serial No: 511C1-01220-0100-478DF2A.

MAINTENANCE

PowerValue 11 (6-10 kVA) UPS only requires minimal maintenance. The only requirement is to charge the UPS regularly in order to maximize the expected life of the battery. When being connected to the mains power, whether the UPS is turned on or not, the UPS keeps charging the batteries and also offers the protective function of overcharging and over-discharging.

WARNING! BATTERY REPLACEMENT SHOULD ONLY BE PERFORMED BY QUALIFIED PERSONNEL

  • If the battery service life (3~5 years at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this case please contact your dealer.
  • The UPS should be charged once every 4 to 6 months if it has not been used for a long time.
  • In high temperature regions, the battery should be charged and discharged every 2 months. The standard charging time should be of at least 12 hours.
  • Under normal conditions, the battery life lasts 3 to 5 years. In case the battery is not in good conditions, earlier replacement should be made.
  • Replace batteries with the same number and same type of batteries.
  • Do not replace the batteries individually. All the batteries should be replaced at the same time following the instructions of the battery supplier.

TROUBLESHOOTING

Fault identification and rectification
If the UPS system does not operate correctly, please attempt to solve the problem using the table below. If the problem still persists, consult your supplier supplier.

Problem Displayed Possible cause Remedy
Read EEPROM Error UPS internal fault Consult your supplier.
EPO Active EPO connector is open Check the EPO connector status
On Maintain Bypass Maintain bypass switch is open Check the maintain bypass

switch status
IP soft start failed| UPS internal fault| Consult your supplier.
Site Wiring Fault| Phase and neutral conductor at input of UPS system are reversed| Reverse mains power wiring.
Battery Disconnect| Battery pack is not connected correctly| Do the battery test to confirm.

Check the battery bank is connected to the UPS. Check the battery breaker is turned on.

Battery low| Battery voltage is low| If audible alarm sounds every second, the battery is

almost empty.

Output Overload| Overload| Check the loads and remove some non-critical loads.

Check if some loads have failures.

Fan Failure| Fan abnormal| Check if the fan is running normally.
Charger Fail| The charge fails| Consult your supplier.
Battery Over Voltage| Battery voltage is higher than normal value| Check if the battery quantity is correct.
Over Charge| Battery is over charged| The UPS will turn off the charger until the battery voltage is normal
Model Pin Error| UPS internal fault| Consult your supplier.
Ambient Over Temperature| The ambient temperature is too high| Check the environment ventilation.
Heat sink Over Temperature| Inside temperature of UPS is too high| Check the ventilation of UPS and the ambient temperature.
Ambient NTC abnormal| UPS internal fault| Consult your supplier.
Para Cable Male Loss| The parallel cable is disconnected| Check the parallel cable.
Para Cable Female Loss| The parallel cable is disconnected| Check the parallel cable.
Para Bat Differ| The battery packs of some UPSs are disconnected| Check if all the battery packs are connected.
Para Line Differ| The mains input of some UPSs is disconnected| Check the building wiring and input cable. Check if the input breaker is closed.

Ensure the UPS are connected to the same input

source.

Para Work Mode Differ| UPS are configured with different

power settings (Ex. one in Online mode and one in Converter mode).

| Modify the settings of the UPS. All UPS should be running in the same mode
Para Rate Power Differ| There are different UPS in a parallel system| UPS with different capacity (Ex. one 6kVA and one 10kVA) cannot be paralleled.
ECO In Para| ECO mode is enabled in a parallel

system

| Eco mode cannot be used in a parallel system.
IP Fuse Open| Input fuse break is opened| Check the input fuse status
Problem Displayed| Possible cause| Remedy
---|---|---
Inv Overload Fault| Overload| Check the loads and remove non-critical loads. Check if there are failures in the load.
Byp Overload Fault| Overload| Check the loads and remove non-critical loads. Check if there are failures in the load.
Output Short Circuit| Output short circuit| Remove all loads. Turn off the UPS.

Check if the UPS output and loads are short circuited. Ensure short circuit is removed

before turning on the UPS again.

Heat sink Over Temperature Fault| Inside temperature of UPS is too high| Check the ventilation of UPS and the ambient temperature.
Bus Over Voltage| UPS internal fault| Consult your supplier.
Bus Under Voltage| UPS internal fault| Consult your supplier.
Bus Unbalance| UPS internal fault| Consult your supplier.
Bus short| UPS internal fault| Consult your supplier.
Bus Soft start Fail| UPS internal fault| Consult your supplier.
Inv Over Voltage| UPS internal fault| Consult your supplier.
Inv Under Voltage| UPS internal fault| Consult your supplier.
Inv Soft start Fail| UPS internal fault| Consult your supplier.
Negative Power Fault| The load is purely inductive or capacitive| Remove non- critical loads.

Bypass supplies the load. Ensure there is no overload, then turn on UPS.

Cable male and female Loss fault| The parallel cable is disconnected| Check the parallel cable.
Fan lock fault| Fan blocked or disconnected over time| Check the fan status.
Back Feed| Output voltage is returned to input| Consult your supplier.
No indication, no warning tone even though system is connected to mains power supply| No input voltage| Check the building wiring and input cables. Check if the input breaker is closed.
BYPASS LED light up even

though the power supply is available

| Inverter not switched on| Press On-Switch to turn on the UPS.
BATTERY LED lights up, and

audible alarm sounding every 1 beep in every 4 seconds

| Input voltage and/or frequency are out of tolerance| Check input power source.

Check the building wiring and input cable. Check if the input breaker is closed.

Emergency supply period shorter than nominal value| Batteries are not fully charged / batteries defect| Charge the batteries for at least 12 hours and then check capacity.

Please have the following information at hand before calling the After- Sales Service Department:

  1. Model number, serial number
  2. Date on which the problem occurred
  3. LCD/LED display information, Buzzer alarm status
  4. Mains power condition, load type and capacity, environment temperature, ventilation condition
  5. Information on external battery pack (battery capacity, quantity)

TECHNICAL SPECIFICATION

GENERAL DATA 6 kVA 6 kVA B 10 kVA 10 kVA B
Output rated power [W] 5400 W 5400 W 9000 W 9000 W
Output power factor 0.9
Topology True online double conversion
Inbuilt batteries No Yes No Yes

INPUT

Nominal input voltage 200 / 208 / 220 / 230 / 240 VAC
Input voltage tolerance 110-276 VAC (depends on load level)
Input current THD <5% with full resistive load
Rated current (ref. 230V) 25.8 A
Frequency range 45-55 Hz / 54-66 Hz
Power factor ≥0.99

OUTPUT

Rated output voltage 208* / 220 / 230 / 240 VAC
Waveform Sinusoidal

Voltage tolerance

(referred to 230V)

| ±1%
Voltage distortion| ≤2% full linear load, ≤5% full non-linear load
Overload capability**

(inverter mode)

| 2 min.: 105-125% load / 30s.: 125-150% load / 1s.: >150%
Overload capability**

(bypass mode)

| 1 min.: 120-150% load / 10s.: >150% load / 1s.: >170%
Nominal frequency| 50 or 60 Hz x (1± 0.5 Hz on battery mode)
Crest Factor| 3:1

TRANFER TIME

Battery ßà inverter 0 ms
Bypass ßà inverter 0 ms
Inverter to Eco-mode 0 ms
Eco-mode to inverter <10 ms

EFFICIENCY

AC-AC ≥ 92%
In eco-mode ≥ 96%

ENVIRONMENT

Protection rating IP 20
UPS storage temperature -15 – +60°C

Batteries storage

temperature

| 0~35°C
Operating temperature| 0 – 45°C
Relative humidity| 0-95% (Non-condensing)
Altitude (above sea level)| <1000m for nominal power*

BATTERY

Type VRLA, vented lead-acid
Battery configuration
Backup time (100% load)
Charging current 4A
Recharge time
EXBAT max current 32A

COMMUNICATIONS

User interface LCD display
Communication cards SNMP (option), AS400 relay card (option)

STANDARDS

Safety IEC/EN 62040-1
Performance IEC/EN 62040-3
RoHS IEC/EN50581:2012
Manufacturing ISO 9001:2008, ISO 14001:2004

WEIGHT, DIMENSIONS

Weight 25.4 kg 80 kg 28.3 kg 84 kg
Dimensions WxHxD 260 x 708 x 558 mm 260 x 708 x 558 mm 260 x 708
x 558 260 x 708 x 558
  • Technical specifications are subject to change without notice. *The load capacity is de-rated to 90% when the output voltage is adjusted to 208VAC.
  • The overload capacity is de-rated in Online mode if the ambient temperature is higher than 35 ºC.
  • The load capacity is de-rated by 1% for every 100m above 1000m.