AKO 5753H072 Gas Transmitter with NBIoT Communication User Guide

June 1, 2024
AKO

AKO-LOGO

AKO 5753H072 Gas Transmitter with NBIoT Communication

AKO-5753H072-Gas-Transmitter-with-NBIoT-Communication-
PRODUCT

Specifications

  • Gas transmitter with NBIoT communication
  • Model: AKO-575400N / NE, AKO-575744N
  • Operating Voltage: 12 – 30 Vdc
  • Communication : RS485
  • Gas sensor for detecting gas concentration in ppm

Warning

  • Transmitters/detectors should be installed in a place protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical data.
  • The transmitters/detectors  are not suitable for areas classified as potentially explosive.
  • Transmitters /detectors supervise a point and not an area. If the gas leak does not reach the sensor, or the level of concentration in that point does not reach the foreseen values according to the type of gas no alarm will be activated. If perimeter supervision is required, several sensors should be installed around that area.
  • Avoid installing the device on metal walls or near devices that may produce radio emissions.
  • This device must be installed in a location where a minimum distance of 20 cm to the human body can be guaranteed, to ensure compliance with standards on human exposure to electromagnetic fields.
  • The AKO-575400NE device must NEVER be operating without having installed the external antenna. This device can be fitted with any antenna provided it has a gain of fewer than 9.2 dBi and there is a minimum distance of more than 20 cm between it and any person or animal. Any type of antenna used with this device must comply with the limits established for the radio interface in the Member States and the following documents: Commission Decision 2010/267/EU of 6 May 2010, ECC Decision (09)03 of 30 October 2009 and CEPT Report 30 of 30 October 2009.

Working conditions:

  • Avoid handling refrigerant gases near the sensor. If this is unavoidable, use Set Hold or Maintenance mode. Do not paint the sensor or place it near solvents or paints. Exposure to acetone vapours may generate false alarms.
  • The sensor should be installed away from: -Smoke outlets located in confined spaces or from engines, generators or motorised machinery (fork-lift trucks, etc.).
    • Particularly damp areas or areas with strong ventilation.
  • The detector should usually be installed in an area where gas may concentrate, near places where gas leaks could start
  • The gases currently used in industrial refrigeration, for which this transmitter has been designed, are heavier than air. They are therefore always concentrated in the lowest part of the refrigerated room or space. Please take this into consideration when choosing the installation site. It is advisable to leave a distance of around 50 cm free.

AKO-5753H072-Gas-Transmitter-with-NBIoT-Communication-
FIG-1

CAUTION: Always disconnect the power supply to do the wiring.

  • The wiring between the transmitter and the station must NEVER be installed in a conduit together with power, control or power supply cables.
  • Cables for wiring the relay contacts should have an adequate section depending on the unit to be connected.
  • Certain international standards maintain that the power supply of the alarm should originate from a different circuit than that used by the refrigeration and ventilation system. Please ensure that you comply with current local regulations.
  • If connecting to a MODBUS network the double connection strips included must be used (see box)

AKO-5753H072-Gas-Transmitter-with-NBIoT-Communication-
FIG-2

Description

  • Fixed: Gas pre-alarm activated. Flashing: Gas alarm activated.
  • Fixed: Set Hold mode activated Flashing: Maintenance mode activated
  • The display shows the type of gas detected.
  • Constant: NBIoT module in operation
  • Flashing: Malfunction in NBIoT module
  • Constant: Connected to the NBIoT network (Narrowband) Switched off: NOT connected to the NBIoT network or expired license.
  • The display shows the current gas concentration in ppm (parts per million).
  • The value displayed should be multiplied by 10. Gas alarm on mute
  • Unit in programming mode.
  • If the gas Pre-Alarm or Alarm sounds, pressing once will mute the alarm tone (See parameter b03). In the programming menu, it exits the parameter without saving changes, returns to the previous level or exits programming.
  • Pressing for 3 seconds activates or deactivates Set Hold mode. Pressing for 6 seconds activates or deactivates maintenance mode. In the programming menu it allows scrolling around the different levels, or during the setting of a parameter, changing its value.
  • Pressing once (< 1 second) will show the type of gas detected, the date and time in sequential order.
    Pressing for 3 seconds displays the Pre-Alarm and Alarm levels that have been configured.
    In the programming menu it allows scrolling around the different levels, or during the setting of a parameter, changing its value.
    Pressing for 3 seconds accesses the configuration of alarm and pre-alarm levels.
    Pressing it for 6 seconds accesses the advanced programming menu.
    In the programming menu, it accesses the level shown on the display or, during the setting of a parameter, accepts the new value.

Forces data transfer to the cloud via NBIoT connectivity.

Operation

Without alarms

  • The display shows the current gas concentration in ppm.
  • Parameter b02 allows you to fix a value below which the display will always show zero.
  • The transmitter regularly sends to the cloud (akonet. cloud) the gas concentration data and other operation information at specific intervals based on the akonet. cloud parameter œcontinual log interval.
  • Any change in the configuration of the transmitter or its operation (mode changes, errors, etc.) is sent to the cloud instantly.

Alarms

  • The transmitter emits an acoustic alarm, and the alarm indicator flashes and activates the relays when certain gas concentration levels are exceeded. If the transmitter is connected to a station, the station will emit an acoustic alarm. The relays will be activated on both devices.
  • Two alarm levels are depending on the concentration of gas detected: Pre-Alarm and Alarm. Both are factory preset but can be modified through parameters AL3 and AL6. These values comply with domestic and international regulations. However, please ensure that these values comply with current local regulations. To modify these values, parameter AL1 should be configured to 1. Activations and deactivations of pre-alarms and alarms are sent to the cloud instantly.

Default parameters

  • To set the device to factory default, switch off the power supply and switch it on again, and press the sequence and SET within 2 minutes.

The display shows the message dFp (default parameters) with a choice of two options:

  • 0: Parameters are not modified
  • 1: All parameters are reset to their default values.

Signing up to akonet.cloud
For the transmitter to be able to send operating data to akonet.cloud, it must be registered. To do this, go to https://akonet.cloud (requires registration), click on “Add new device ” and continue with one of these two methods:AKO-5753H072-Gas-Transmitter-with-NBIoT-Communication-
FIG-21

  • A. -Enter the serial number (S/N) and validation code / IMEI that appear on the tag and press “Search”.
  • B. -Capture the QR code that appears on the tag using the option (requires having a camera on your PC, tablet or mobile phone).

These data are found on the tag on the right-hand side of the transmitter. More information can be found in the akonet.cloud user guide at: https://enhelpakonet.ako.com/
To access akonet. cloud, enter this address in your browser (the use of Google Chrome is recommended): https://akonet.cloud.

WARNING: Before activating the device, make sure that there is enough reception at the installation location. Activated devices may not be returned.

Forcing transmission

  • When the steps of the configuration wizard and the registration process are completed in akonet.cloud, you must force a first transmission to verify the level of reception:
  • Press and hold the ESC and SET keys for 3 seconds.
  • After a moment, the display shows the quality of the NBIoT signal received:

AKO-5753H072-Gas-Transmitter-with-NBIoT-Communication-
FIG-22

WARNING: The transmitter does not start transmitting data to akonet. cloud until the first transmission is forced.

Simplified declaration of conformity

  • AKO Electromecánica S.A.L. hereby declares that the radioelectric device types AKO-575xxxx (Gas transmitter with NBIoT communica-tion) conform to the provisions set forth by Directive 2014/53/EU.
  • The full text of the EU conformity declaration is available at the following internet address: http://help.ako.com/manuales/declaracion-ue-de-conformidad

Parameters
The unit operating parameters are organised in different groups or families according to their function. The Def. column indicates the default parameters set in the factory. In order to access the programming menu, hold the SET key for 6 seconds, or until ‘’PRG’’ appears on the display. To modify the Pre- Alarm and Alarm levels, press SET for 3 seconds or until “Al3” appears on the display (Only if AL1=1).

This allows you to scroll through the different levels, or
when setting a parameter, to change its value.

  • SET: This accesses the level shown on the display or, when setting a parameter, it accepts the new value.
  • ESC: This exits the parameter without saving changes, returns to the previous level, or exits programming.
Level 1 Level 2 ALARM CONFIGURATION
Description Values Def.
AL AL1 Alarm levels: 0: According to regulation 1: Set by user
AL2 Pre-Alarma 0: Deshabilitada; 1: Habilitada 0
AL3 Pre-Alarm Level (1) 575744N
Other models 500
AL4 Pre-Alarm Differential PPM
AL5 Pre-Alarm Delay (0: Disabled) min.
AL6 Alarm Level (1) 575744N
Other models 1000 2000
AL7 Alarm Differential PPM
AL8 Alarm Delay (0: Disabled) min.
ep Exit to level 1
    BASIC CONFIGURATION
Description Values Def.
bcn Gc1 Type of gas to be measured (Reading only)

Gc2

| Gas to be measured with the Universal sensor (Only if Gc1=brd1) ALL; 125; 134A; 404A; 407A; 407F; 410A; 448A; 449A; 513A; 452A; 32; 23; 455A (2)| |

ALL

|
b01| Display 0: Measurement in PPM 1: Type of gas to be measured| 0| 0| 1

b02

| Minimum value to be shown on the display (Lower values are shown as 0) Does not affect the values shown by communication (AKONet or CAMM module)|

PPM

|

0

|

0

|

250

b03

| Function of the mute key (Applicable to Alarm and Pre-Alarm) 0: Disabled 1: Deactivate acoustic alarm

2: Deactivate relay 3: Deactivate both

|

0

|

1

|

3

b04| Acoustic alarm 0: Disabled 1: Enabled| 0| 1| 1
b10| Access code (password) function        0: Disabled;

1: Block access to parameters            2: Block keypad

| 0| 0| 2
b11| Access code (password)| 0| 0| 99
b20| MODBUS address| 1| (3)| 247
b21| MODBUS speed      0: 9600 bps    1: 19200 bps

2: 38400 bps 3: 57600 bps

| 0| 0| 3
b22| STOP bits for MODBUS communication 1: 1 STOP bit, 2: 2 STOP bits| 1| 1| 2
b23| MODBUS communication parity 0: No parity, 1: Odd, 2: Even| 0| 0| 2
EP| Exit to level 1
Level 1| Level 2| INPUT AND OUTPUT CONFIGURATION
---|---|---
Description| Def.| Def.| Max.
{n0| {00| Reset to zero of the sensor (Calibration only) 0: Disabled 1: Reset to zero activated| 0| –| 1
{01| Setting the sensor (Calibration only) 0: Disabled 1: Setting activated| 0| –| 1
{11| Polarity of digital input 1 (Remote Mute)

0: Activates on opening contact; 1: Activates on closing contact

| 0| 0| 1
{21| Polarity of digital input 2 (Remote Set Hold)

0: Activates on opening contact; 1: Activates on closing contact

| 0| 0| 1
o00| Type of output 4/20 mA (Reading only) 0: Calibrated for alarm station; 1: Linear| 0| 0| 1
ep| Exit to level 1
 |  | INFORMATION (Reading only)
Description| Def.| Def.| Max.
tid| PU| Programme version| –| –| –
PR| Programme revision| –| –| –
BU| Bootloader version| –| –| –
BR| Bootloader revision| –| –| –
PAR| Parameter map revision| –| –| –
PCR| CRC value of the programme| –| –| –
BCR| CRC value of the bootloader| –| –| –
EP| Exit to level 1
MESSAGES

pal| Gas pre-alarm activated. Flashing together with the gas concentration.
al| Gas alarm activated. Flashing together with the gas concentration.
scn| Initialisation process of the gas sensor. This may last for up to 3 minutes.

es

| Error or malfunction of the sensor. The Pre-Alarm relay is activated, the transmitter emits 3 alert tones every 2 minutes and the  icon flashes. Deactivate the power supply and activate it again. If after a few seconds the error persists, please contact your technical support centre.
tsH| The sensor has reached its maximum working temperature.
tSl| The sensor has reached its minimum working temperature.

  1. In order to modify these levels, parameter AL1 should be configured to 1.
  2. R-450A, R-442A, R-454A, R-454C, R-1234YF, R-1234ZE are detected using GC2=ALL.
  3. The MODBUS address will be shown on the transmitter label by default.

Technical specifications

  • Power supply. …………………………………………………………………………………………………….12 – 30 Vdc
  • Consumption Typical. ……………………………………………………………………………………………….75 mA
  • Maximum …………………………………………………………………………………………..125 mA
  • Pre-Alarm/Alarm relay ………………………………………………………………….. SPDT 30 Vdc, 2 A, cos j =1
  • Working ambient temperature AKO-575744N. ……………………………………………..-40 ºC to 50 ºC
  • Other models …………………………………………………-30 ºC to 50 ºC
  • Storage ambient temperature AKO-575744N ………………………………………………-40 ºC to 60 ºC
  • Other models …………………………………………………-30 ºC to 60 ºC
  • Range of maximum moisture permitted ……………………………….. 0 – 95 % HR (without condensation)
  • Protection degree AKO-575400N E……………………………………………………………………………….. IP65
  • Other models …………………………………………………………………………………… IP68
  • Type of sensor …………………………………………………………. NDIR (Non-Dispersive Infrared Technology)
  • Display range AKO-575744N ……………………………………………………………….0 – 10000 x1 ppm
  • Other models ……………………………………………………………………0 – 2000 x1 ppm
  • Estimated working life ……………………………………………………………………………………………… 5 years
  • Dimensions ………………………………………………………………………………………………………………….. 202 mm (W) x 82 (H) x 55.5 mm (D)
  • Maximum transmission power ……………………………………………………………..23.5 dBm conducted
  • Antenna AKO-575400NE …………………………………………………………………………………… External
  • Other models ………………………………………………………………………………………..Internal
  • Bands ………………………………. NBIoT (Narrow band) LTE Cat NB1 | B2, B3, B4, B8, B12, B13, B20

QR SCAN

akonet.cloud

AKO ELECTROMECÁNICA , S.A.L.

  • Avda. Roquetes, 30-38
  • 08812
  • Sant Pere de Ribes.
  • Barcelona
  • Spain.

www.ako.com
We reserve the right to supply materials that might vary slightly to those described in our Technical Sheets. Updated information is available on our website.

FAQ

  • How do I mute the alarm tone?
    • If the gas Pre-Alarm or Alarm sounds, press the button once to mute the alarm tone.
  • How can I set the device to factory default?
    • To set the device to factory default, switch off the power supply and press N, Q, and SET within 2 minutes.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AKO User Manuals

Related Manuals