AKO-D14730 Universal Controller User Guide

June 1, 2024
AKO

AKO-D14730 Universal Controller

Warnings

  • If the device is used without following the manufacturer’s instructions, it may fail to meet its safety requirements. Only sensors supplied by AKO should be used for the device to operate correctly.
  • The equipment should be installed in a place that is protected from vibrations, water and corrosive gases, where the ambient temperature does not exceed the value indicated in the technical specifications.
  • For the reading to be correct, the sensor should be placed somewhere without heat sources other than the temperature to be measured or monitored.
  • The power circuit should be equipped with a switch for disconnection of at least 2 A, 230 V, situated near the appliance. The cables will be fed in from the rear and will be types H05VV‑F or H05V-K.
  • The cross-section to be used will depend on current local regulations, but should never be less than 1 mm2.
  • Cables for relay contact wiring should have a cross-section of 2.5 mm2.
  • Between -40°C and +20°C, if the NTC sensor is extended to 1000 m with at a cable of least 0.5 mm², the maximum deviation will be 0.25ºC (cable for sensor extension ref. AKO-15586).
    ATTENTION : The equipment is not compatible with AKO-14917 (external communication module) and AKO-14918 (programming key).

Description

Universal controller compatible with Pt1000, NTC, PTC, 4-20 mA, 0-10 V and 0.5-4.5 V inputs. It has one relay that can be configured as an alarm or an ON/OFF control. It has one analogue output (4-20 mA, 0-10 V).
The AKO-D14730-C model also has MODBUS communication.

Installation

AKO-D14730-Universal-Controller-FIG- \(2\)

Operation

AKO-D14730-Universal-Controller-FIG-
\(3\)

  1. Display, shows the value measured by the probe. During programming: indicates the setting or its value.
  2. Shows the status of relay R1: ON= Activated, OFF= Deactivated.
  3. Shows the status of analogue output R2: ON= Output ≥ 4 mA or 0 V, OFF= Output ≤ 4 mA or 0 V.
  4. ESC key: Deactivates alarms but they remain signalled (according to parameter A16). In the programming menu, it exits the parameter without saving changes, returns to the previous level or exits programming.
  5. N up key: In the programming menu, it allows scrolling through the different levels, or when establishing a setting, changing its value.
  6. Q / m down key: Pressing it for 5 seconds activates stand-by mode, and pressing it for 2 seconds returns the device to normal mode. In stand-by mode, the equipment does not carry out any actions and the display only shows the m indicator. The programming menu allows the user to scroll through the different levels or, when establishing a setting, to change its value.
  7. SET key: Pressing it for 5 seconds allows the user to change the R1 relay setpoint. Pressing it for 10 seconds accesses the programming menu. In the programming menu, the user can access the level shown on the display or, when setting a parameter, accept the new value.
  8. Alarm activated
  9. Stand-by active mode: the rest of the display is switched off.
  10. Programming mode active.

Types of regulation
The type of regulation is set via setting P31.

Relay regulation

  • Regulation occurs by activating/deactivating relay R1.
  • Regulation via analogue output R2, relay R1 set as an alarm
  • Regulation occurs by modulating the analogue output R2. This output must be connected to a variable-frequency drive that controls the compressor. Relay R1 is set as an alarm relay.
  • Regulation through analogue output R2, relay R1 activates and deactivates the frequency inverter
  • Regulation occurs by modulating the analogue output R2. This output must be connected to a variable-frequency drive that controls the compressor. Relay R1 controls the activation and deactivation of the variable-frequency drive.

Types of operation
The type of operation is set via setting P0.

Relay regulationAKO-D14730-Universal-Controller-FIG-
\(4\)

Regulation through analogue outputAKO-D14730-Universal-Controller-FIG-
\(5\)

We reserve the right to supply materials slightly different to those described in our Data Sheets. Up-to-date information on our website.

Table of settings

The Def. column indicates the ex-works configured default settings.

Level 1|
---|---
REGULATION AND CONTROL
 | Description| Unit| Min.| Def.| Max.

rE

| SP| Setpoint|  | A| 0.0| L
C0| Sensor 1 calibration (offset)|  | -20.0| 0.0| 20.0
C1| SP differential (Hysteresis)|  | 0.1| 2| 20
C2| Top lock of the SP (R1)|  | C3| L| L
C3| Lower lock of the SP (R1)|  | A| A| C2

C6

| Status of relay R1 (options 0 to 3) or analogue output R2 (option 4) in case of probe failure: 0=OFF; 1=ON;

2=Average according to last 24 h prior to sensor error;

3=ON-OFF according to C7 and C8 (in heat mode always OFF);

4=% of fixed analogue output during sensor error (according to A17)

|  |

0

|

4

|

4

C7| Time of relay R1 in ON in the event of damaged sensor

(If C7=0 and C8¹0, the relay will always be OFF disconnected)

| min.| 0| 10| 120
C8| Relay R1 time in OFF in the event of fault in sensor

(If C8=0 and C7¹0, the relay will always be ON connected)

| min.| 0| 5| 120
C12| Variation from SP by digital input (0=deactivated)|  | C3-SP| 0.0| C2-SP
C17| OFF/ON time delay for relay R1 (from last disconnection)| min.| 0| 0| 120
C18| ON/OFF time delay for relay R1 (from last connection)| min.| 0| 0| 120
EP| Output to level 1
DEFROST
 | Description| Unit| Min.| Def.| Max.

DEF

| d0| Frequency of disconnection of relay R1 (time between two starts)| h.| 0| 6| 120
d1| Disconnection period of relay R1 (0=defrost disabled)| min.| 0| 0| 120
EP| Output to level 1
ALARM CONTROL
 | Description| Unit| Min.| Def.| Max.

AL

| A0| Configuration of alarms 0=Relative to SP; 1=Absolute|  | 0| 1| 1
A1| Alarm for maximum in sensor 1 (must be higher than SP)|  | A2| B| B
A2| Alarm for minimum in sensor 1 (must be lower than SP)|  | A| A| A1
A3| Delay of alarms in the start-up| min.| 0| 0| 250
A5| Delay of alarms when the A1 or A2 value is reached| min.| 0| 30| 250
A6| Delay of the external alarm on receiving a signal in digital input (P35=1)| min.| 0| 0| 120
A9| Polarity alarm relay R1 (only if P31=1),

0=Relay ON in alarm (OFF without alarm); 1= Relay OFF in alarm (ON without alarm)

| 0| 0| 1
A10| Differential alarms (A1 and A2)|  | 0.1| 1.0| 20.0
A16| Disconnection of alarm relay R1 after pressing the ESC key , 0=Yes, 1=No|  | 0| 0| 1
A17| Percentage of analogue output with damaged sensor| %| 0| 0| 100
EP| Output to level 1
GENERAL CONFIGURATION
 | Description| Unit| Min.| Def.| Max.

CNF

| P0| Type of operation , 0=Direct (cold), 1=Inverse (heat)|  | 0| 0| 1
P1| Delay of all functions on receiving power supply| min.| 0| 0| 255
P2| Access code (password) function

0=Inactive; 1=Access to settings locked; 2=Keypad locked

|  | 0| 0| 2
P7| Display mode  0=Whole numbers         1=One decimal|  | 0| 1| 1
P8| Display units with a temperature probe               0=ºC 1=ºF|  | 0| 0| 1
P9| Selection of sensor type 0=NTC; 1=PTC; 2=PT1000; 3= 4-20 mA; 4=0.5-4.5 V; 5=0-10 V|  | 0| 0| 5
P12| Digital input polarity             0=Activates when contact closes;

1=Activates when contact opens

|  | 0| 0| 1

P31

| Types of regulation  0=Control by relay; 1=Control by analogue output with alarm relay R1;

2=Control by analogue output with relay R1 as ON/OFF for variable-frequency drive

|

0

|

1

|

2

P32| Sensor value at 20 mA / 4.5 V / 10 V (If P9=3-5)|  | -999| 100| 999
P33| Sensor value at 4 mA / 0.5 V / 0 V (If P9=3-5)|  | -999| 0| 999
P35| Configuration digital input 0=Deactivated; 1=External alarm; 2=SP variation (SP+C12); 3=Inversion of regulation cycle|  | 0| 0| 3
P36| Type of analogue output 0=4-20 mA; 1=0-10 V|  | 0| 0| 1
EP| Output to level 1
ACCESS CONTROL AND INFORMATION
 | Description| Unit| Min.| Def.| Max.

tid

| b20| Address for units with communication|  | 1| *| 247
b21| Communication speed: 0:9600 bps; 1:19200 bps; 2:38400 bps; 3:57600 bps| 0| 0| 3
L5| Password|  | 0| 0| 99
PU| Programme version|  | –| –| –
Pr| Check|  | –| –| –
PSr| Programme sub-review (Information)|  | –| –| –

See equipment label

  • A= -50 if P9=0, 1, 2 or P33 if P9=3, 4, 5
  • B= 99,9 if P9=0, 2; 150 if P9=1 or P32 if P9=3, 4, 5

When changing the type of probe (P9), the operating values of the following settings will change: SP= 0.0, C2= B, C3= A, A1= B, A2= A, where A and B vary depending on the type of probeAKO-D14730-Universal-Controller-FIG-
\(6\)

  • D: Message shown on display.
  • R: Activates the alarm relay.

Wiring

AKO-D14730-Universal-Controller-FIG- \(7\)

  • A. Sensor supply output = +15 VCC if P9=3 or 5 or +5 VCC if P9=4.
  • B. Option with sensors powered by external power supply.

Technical specifications

  • Power supply…………………………………………….100-240 V~ ±10%, 50/60 Hz, 7 VA
  • Maximum voltage in the SELV circuits…………………………………………………….. 20 V
  • Inputs:………………………………1 NTC/PTC/Pt1000/4-20 mA/0.5-4.5 V/0-10 V input …………………………………………………………………………………………..1 digital input
  • Outputs:……………………………………. 1 SPDT relay, EN60730-1: 16 (10) A 250 V~, 100,000 operations UNE-EN IEC 60079-15:2021 ……………………………………………………………………. 1 analogue 4-20 mA / 0-10 V
  • Range of measurement………..NTC/Pt1000.-50.0ºC to +99.9ºC (-58.0ºF to 211ºF)
  • PTC…………………………..-50.0ºC to +150ºC (-58.0ºF to 302ºF) 4-20 mA / 0.5-4.5 V / 0-10 V…………………………-999 to 999
  • Resolution S1 NTC……………………………………………………………….. 0.1ºC (0.1ºF)
  • PTC -50ºC to 100ºC………………………………………………….. 0.1ºC > 100ºC……………………………………………………………… 1ºC
  • Pt1000…………………………………………………………………….. 0.1ºC
  • 4-20 mA / 0.5-4.5 V / 0-10 V -99.9 to 99.9……………….. 0.1
  • ≤ -100 / ≥ 100……………….1
  • Thermometric precision of equipment (S1) NTC/PTC………………………….. ± 0.5 ºC
  • Pt1000………………………………. ± 1 ºC
  • 4-20 mA/0.5 – 4.5 V/0-10 V….. ± 1%
  • Working environment…………………………………………..-10 to 50ºC, humidity <90%
  • Storage environment……………………………………………-30 to 70ºC, humidity <90%
  • Protection rating of front part……………………………………………………………….. IP65
  • Fixing……………………………………………………………….Panel mounting with anchors
  • Panel cavity dimensions………………………………………………………………71 x 29 mm
  • Front part dimensions…………………………………………………………………79 x 38 mm
  • Depth…………………………………………………………………………………………… 61 mm
  • Connections: ….. Terminal to screw for cables with a cross-section of up to 2.5 mm2
  • Control device classification: Built-in assembly, with Type 1.B automatic operation action feature, for use in clean situations, logical support (Software) class A and continuous operation. Degree of contamination 2 acc. to UNE-EN 60730-1.
  • Double power input insulation, secondary circuit and relay output.
  • Rated impulse-withstand voltage……………………………………………………….. 2500 V

Pressure ball test temperature:

  • Accessible parts…………………………………………………………………………….. 75ºC
  • Parts positioning active elements…………………………………………………….. 125ºC
  • EMC test declared voltage and current………………………………………..207 V, 17 mA
  • Radio interference suppression test current………………………………………….270 mA

Probe extensions:

  • NTC……………….. Extendable up to 100 metres with AKO-15586H extension cable
  • PTC………………… Extendable up to 100 metres with AKO-15586H extension cable
  • PT1000…………….. Extendable up to 30 metres with AKO-15586H extension cable
  • 4-20mA………….. Extendable up to 200 metres with AKO-15586H extension cable
  • 0.5–4.5V………… Extendable up to 100 metres with AKO-15586H extension cable
  • 0–10V……………. Extendable up to 100 metres with AKO-15586H extension cable

The AKO-15586H extension cable has an impedance of maximum cable distance 0.0172 Ohms * mm2/m.

AKO ELECTROMECÁNICA, S.A.L.
Avda. Roquetes, 30-38 08812
Sant Pere de Ribes.
Barcelona
Spain.
www.ako.com

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

AKO User Manuals

Related Manuals