KNX 2015 00 Dimming Actuator 4-Gang Standard Instruction Manual

June 13, 2024
KNX

KNX 2015 00 Dimming Actuator 4-Gang Standard

Product Information

The Dimming Actuator is a 4-gang device designed for controlling lighting levels. It is available in two variants: the Standard Order no. 2015 00 and the Komfort Order no. 2025 00. The device is part of the KNX system and complies with KNX directives. It can be updated with firmware using the Gira ETS Service App. The device is also KNX Data Secure capable, offering protection against manipulation in building automation.

Safety Instructions

  • Electrical devices should only be mounted and connected by electrically skilled persons to avoid serious injuries, fire, or property damage.
  • Always disconnect the device or load before carrying out any work on it, taking into account all circuit breakers supporting dangerous voltages.
  • The device is not suitable for disconnection from the supply voltage, as mains potential may still be applied to the load when the output is switched off. Switch off all associated circuit breakers before performing any work.
  • Ensure that the set operating mode and load type match to prevent destruction of the dimmer and load. Set the correct dimming principle before connecting or exchanging the load.
  • When operating with inductive transformers, each transformer must be fused on the primary side according to the manufacturer’s instructions. Only use safety transformers according to EN 61558-2-6.

Device Components

  1. Button field for manual operation
  2. Programming button and LED
  3. KNX connection
  4. Status LEDs for outputs
  5. Load connections

Function

The device is designed for use in the KNX system and requires detailed technical knowledge obtained from KNX training courses. It can be updated with firmware using the Gira ETS Service App. The device is also KNX Data Secure capable, offering protection against manipulation in building automation. Planning, installation, and commissioning are performed with the ETS software, version 5.7.3 and above.

Intended Use

  • When connecting inductive or electronic transformers, follow the data provided by the transformer manufacturer regarding loads and the dimming principle.
  • HV-LED and compact fluorescent lamps generate high pulsed currents when operated in the leading edge phase control.
  • While the dimmers account for the electronic characteristics of most LED lamps on the market, it cannot be guaranteed that desired results will be achieved in all individual cases.

Product Usage Instructions

The Dimming Actuator is delivered in Construction site mode, where the outputs can be operated using the button field.

Dimming actuator, 4-gang Standard Order no. 2015 00
Dimming actuator, 4-gang Komfort Order no. 2025 00

Safety instructions

Electrical devices may only be mounted and connected by electrically skilled persons.

  • Serious injuries, fire or property damage possible. Please read and follow manual fully.
  • Danger of electric shock. Always disconnect before carrying out work on the device or load. In so doing, take all the circuit breakers into account, which support danger-ous voltages to the device and or load.
  • Danger of electric shock. Device is not suitable for disconnection from supply voltage because mains potential even is applied on the load when the output is switched off. Always disconnect before carrying out work on the device or load. To do so, switch off all associated circuit breakers.
  • Risk of destruction of the dimmer and load if the set operating mode and load type do not match. Set the correct dimming principle before connecting or exchanging the load.
  • Fire hazard. For operation with inductive transformers, each transformer must be fused on the primary side in accordance with the manufacturer’s instructions. Only safety transformers according to EN 61558-2-6 may be used.
  • This manual is an integral part of the product, and must remain with the end cus-tomer.

Device components

  1. Button field for manual operation
  2. Programming button and LED
  3. KNX connection
  4. Status LEDs for outputs
  5. Load connections

Function

System information

  • This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
  • The function of this device depends upon the software. Detailed information on load-able software and attainable functionality as well as the software itself can be ob-tained from the manufacturer´s product database.
  • The device can be updated. Firmware can be easily updated with the Gira ETS Ser-vice App (additional software).
  • The device is KNX Data Secure capable. KNX Data Secure offers protection against manipulation in building automation and can be configured in the ETS project. De-tailed specialist knowledge is required. A device certificate, which is attached to the device, is required for safe commissioning. During mounting, the device certificate must be removed from the device and stored securely.
  • Planning, installation and commissioning of the device are carried out with the aid of the ETS, version 5.7.3 and above.
    • Operation in KNX system for Standard and Comfort devices.
    • Operation in Gira One system for Standard devices only.

Intended use

  • Switching and dimming of incandescent lamps, HV halogen lamps, dimmable HV-LED lamps, dimmable compact fluorescent lamps, dimmable inductive transformers with LV halogen or LV LED lamps, dimmable electronic transformers with LV halogen or LV LED lamps
    • Operating in KNX systems
    • Mounting on DIN rail according to EN 60715 in sub-distribution unit
  • If inductive or electronic transformers are connected, observe the data of the transformer manufacturer on loads and the dimming principle.
  • HV-LED and compact fluorescent lamps generate high pulsed currents, when they are operated in the leading edge phase control.
  • Our dimmers take into account the different electronic characteristics of most LED lamps found on the market. However, it cannot be guaranteed that in indi-vidual cases the desired results may not be achieved.

Product characteristics

  • Outputs can be operated manually, construction site mode

  • Feedback in manual mode and in bus mode

  • Disabling of individual outputs via bus

  • Status feedback

  • KNX Data Secure compatible

  • Updateable with ETS Service App
    Only for “Comfort” version:

  • Disabling of individual outputs manually or by bus

Dimming operation characteristics

  • Automatic or manual selection of the dimming principle suitable for the load
  • Protected against no-load, short-circuit and overheating
  • Feedback of the switching position and the dimming value
  • Parameterisable switch-on and dimming behaviour
  • Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
  • Light scene operation
  • Status indicator of the outputs via LED
  • Mains failure longer than approx. 5 seconds leads to switch-off of the dimming actuator. Depending on the parameter setting, the connected load is calibrated after mains voltage return.
  • Power extension possible by means of power boosters.

Only for “Comfort” version:

  • Signal in the event of a short-circuit
  • Increase in output power possible through parallel switching of multiple out-puts
  • Operating hours counter
    Delivery state: Construction site mode, outputs can be operated using button field.
    Flickering of the connected lamps due to undershoot of the specified minimum load or through centralised pulses from the power stations. This does not rep- resent any defect in the device.

Logic function characteristics
Only for “Comfort” version:

  • Logic gate
  • Transformer (conversion)
  • Disabling element
  • Comparator
  • Limit value switch

Operation

Operating elements

  • Status LEDs for outputs

    • on: output switched on, 1…100%
    • flashes at 1 Hz: short-circuit or manual mode
    • flashes at 2 Hz: overload, mains voltage failure or firmware update
  • Button ǃ
    – Manual operation

  • LED ǃ
    – on: continuous manual mode

  • LED ON|+

    • on: selected output on, 1…100%
    • flashes: Firmware update
  • Button ON|+
    – Switch on/increase brightness

  • Button OFF|−
    Switch off/reduce brightness

  • LED OFF|−

    • on: Selected output off
    • flashes: Firmware update
  • Button ALL OFF
    Switching off all outputs

Operating modes

  • Bus operation: operation via push-button sensors or other bus devices

  • Temporary manual control: manual control locally with keypad, automatic re-turn to bus control

  • Continuous manual mode: Exclusively manual operation on the device
    No bus operation is possible in manual mode.

  • After a bus failure and restoration the device switches to bus operation.

  • The manual mode can be disabled in ongoing operation via a bus telegram. Switching on temporary manual operation mode

  • Operation using the button field is programmed and not disabled.

    • Press button (6) briefly.
      LED (7) flashes, LED A1… (4) of the first configured output flashes. Short- time manual operation is switched on.
  • After 5 s without a button actuation, the actuator returns automatically to bus operation.

Switching off temporary manual operation mode

The device is in short-term manual mode.

  • No button-press for 5 s.
    or –

  • Press (6) button briefly as many time as necessary until the actuator leaves the short-time manual mode.
    Status LED A1… (4) no longer flash, but rather indicate the output status. Short-time manual operation is switched off.
    When switching off the manual control, the outputs, depending on the pro- gramming, switch to the active position, e.g. forced position, logic operation.

Switching on permanent manual operation mode
Operation using the button field is programmed and not disabled.

Press the (6) button for at least 5 s.
LED (7) is off.
Continuous manual mode is switched off. Bus operation is switched on. When switching off the manual control, the outputs, depending on the pro-gramming, switch to the active position, e.g. forced position, logic operation.

Operating the outputs
The device is in continuous or short-term manual mode.

  • Press the button (6) briefly as many times as necessary until the desired output is selected.
    • The LED of the selected output A1… (4) flashes.
    • The LEDs ON|+ (8) and OFF|− (11) indicate the status.
  • Operate output with ON|+ (9) button or OFF|− (10) button.
    • Short: switch on/off.
    • Long: dim brighter/darker.
    • Release: Stop dimming.
    • The LEDs ON|+ (8) and OFF|− (11) indicate the status.
      Short-term manual mode: After running through all of the outputs the device exits manual mode after another brief actuation.

Switching off all outputs
The device is in continuous manual mode.

Press the button ALL OFF (7). All outputs are shut off.

Information for electrically skilled persons

DANGER!
Mortal danger of electric shock. Disconnect the device. Cover up live parts.

Mounting and electrical connection

Connecting the device

  • Connect bus line with KNX device connection terminal observing the correct polarity.
  • Attach the cover cap to the KNX connection as protection against hazardous voltages.

CAUTION!

Danger of destruction. 400 V are shorted when outputs switched in parallel are con-nected to different outer phase conductors.
The device will be destroyed.
Always connect outputs switched in parallel to the same outer phase conductor.

  • Delivery state: The outputs can be operated with manual control.
    In the “Universal” operating mode, the dimming actuator only calibrates itself again after disconnection of the load and also after commissioning using the ETS.

  • Capacitive-inductive mixed load is not permitted.

  • For LED leading edge phase control: Connect a maximum of 2 electronic transformers per output.

  • Connect 600 Watt LED lamps or compact fluorescent lamps at most per
    16 ampere circuit breaker. When connecting transformers, observe the data of the transformer manufacturer.

Only for “Comfort” version:

  • Several dimmer outputs can be combined for dimming greater lamp loads. Only utilise parallel-switched outputs up to 95 % each. Do not connect any compact fluorescent lamps to dimmer outputs switched in parallel.
  • Observe delivery state. Before connecting parallel outputs and switching on, program the dimming actuator with ETS to the changed output configuration.
  • Do not expand parallel-switched dimmer outputs with power packs.

KNX 2015 00 Dimming Actuator 4-Gang Standard-FIG4
Image 3: Comfort variant of the device connection with dimmer outputs switched in parallel (connection example)

  • Connect the lamp loads according to the connection example
Commissioning

Safe-state mode
The safe-state mode stops the execution of the loaded application program.

Only the system software of the device is still functional. ETS diagnosis func-tions and programming of the device are possible. Manual operation is not possible.

Activating safe-state mode

  • Switch off the bus voltage or remove the KNX device connection terminal.
  • Wait about 15 s.
  • Press and hold down the programming button.
  • Switch on the bus voltage or attach the KNX device connection terminal. Re-lease the programming button only after the programming LED starts flashing slowly.
    The safe-state mode is activated.
    By briefly pressing the programming button again, the programming mode can also be switched on and off in the safe-state mode as usual. If the program- ming mode is active, the programming LED stops flashing.

Deactivating safe-state mode

Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.

Master reset
The master reset restores the basic device settings (physical address 15.15.255, firmware remains in place). The device must then be recommissioned with the ETS. Manual operation is possible.
In secure operation: A master reset deactivates device security. The device can then be recommissioned with the device certificate.

Performing a master reset
Precondition: The safe-state mode is activated.

  • Press and hold down the programming button for > 5 s.
    • The programming LED flashes quickly.
    • The device performs a master reset, restarts and is ready for operation again after approx. 5 s.

Restoring the device to factory settings

Devices can be reset to factory settings with the Gira ETS Service App. This function uses the firmware contained in the device that was active at the time of delivery (de-livered state). Restoring the factory settings causes the devices to lose their physical address and configuration.

Technical data

KNX

  • KNX medium TP256

  • KNX commissioning mode S-mode

  • Rated voltage KNX DC 21 … 32 V SELV

  • Current consumption KNX 6 … 15 mA

  • Connection mode KNX Device connection terminal

  • Rated voltage DC 21 … 32 V SELV

  • Current consumption 6 … 15 mA
    Dimming outputs

  • Rated voltage AC 110 … 230 V ~

  • Mains frequency 50 / 60 Hz

  • Power loss max. 7 W

  • Standby power approx. 0.16 W per channel

  • Ambient temperature -5 … +45 °C

  • Storage/transport temperature -25 … +70 °C
    Connected load per channel depends on the connected lamps and the set load type: (see figure 4), (see figure 5)

KNX 2015 00 Dimming Actuator 4-Gang Standard-FIG7KNX 2015 00 Dimming Actuator 4-Gang Standard-
FIG6

Capacitive-inductive mixed load is not permitted.

Power boosters:    See power booster instructions
Connection

  • Single stranded 0.5 … 4 mm²
  • Finely stranded without conductor sleeve 0.5 … 4 mm²
  • Finely stranded with conductor sleeve 0.5 … 2.5 mm²
  • Connection torque, screw terminals max. 0.8 Nm
  • Installation width 72 mm / 4 HP

Troubleshooting

  • Connected LED lamps or compact fluorescent lamps switch off in the lowest dimming position or flicker

    • The set minimum brightness is too low. Increase minimum brightness.
  • Connected LED lamps or compact fluorescent lamps flicker
    Cause 1: Lamps are not dimmable.

    • Check manufacturer’s instructions. Exchange lamps for another type.
  • Cause 2: Dimming principle and lamps do not optimally match.

    • For HV-LED: Check operation in another dimming principle, reduce connected load as well if necessary.
    • For LV-LED: Check the lamp operating device and replace as necessary. With the “Universal” setting: Define the dimming principle manually.
  • Connected HV-LED lamps or compact fluorescent lamps in the lowest dimming position are too bright; dimming range is too small

    • Cause 1: The set minimum brightness is too high.
      Reduce minimum brightness.

    • Cause 2: HV-LED trailing edge phase control dimming principle does not optimally match the connected lamps.
      Check operation in the “HV-LED leading edge phase control” setting, reduce connected load as well if necessary.
      Exchange lamps for another type.

Output has switched off.
Cause 1: Overheating protection has tripped.

  • Disconnect all outputs from the mains, switch-off the corresponding circuit breakers.
  • HV-LED trailing edge phase control: Reduce the connected load. Exchange lamps for another type.
  • HV-LED leading edge phase control: Reduce the connected load. Check the operation in the “HV-LED trailing edge phase control” setting. Exchange lamps for another type.
  • Let device cool down for at least 15 minutes. Check installation situation, en-sure cooling, e.g. provide distance from surrounding devices.

Cause 2: Overvoltage protection has tripped.

HV-LED trailing edge phase control: Check the operation in the “HV-LED lead- ing edge phase control” setting, reduce the connected load as well if neces- sary.

Exchange lamps for another type.

The response of the surge protection can be signalled by sending a short-cir- cuit telegram or can be determined by polling the “short-circuit” communication object.

Cause 3: short-circuit in output circuit

Disconnect all outputs from the mains.
Eliminate short-circuit.
Switch on mains voltage to the outputs again. Switch the affected output off and on again.

When a short-circuit occurs the affected output switches off. Automatic restart when short-circuit is eliminated within 100 ms (inductive load) or 7 seconds (capacitive or ohmic load). After that lasting switch-off.

When a short-circuit occurs during the calibration process, the load calibrates itself again after the short-circuit is eliminated.

Cause 4: load failure.
Check load, replace lamp. For inductive transformers, check primary fuse and replace if necessary.

  • Manual control with button field not possible

    • Cause 1: Manual control has not been programmed.
      Program manual control.

    • Cause 2: Manual control via bus disabled.
      Enable manual control.

  • None of the outputs can be operated.

    • Cause 1: All of the outputs are disabled.
      Cancel disabling.

    • Cause 2: Manual mode active.
      Deactivate manual mode (switch off continuous manual mode).

    • Cause 3: Application software missing or faulty.
      Check programming and correct.

  • All outputs off and not possible to switch on

    • Cause 1: bus voltage failure.
      Check bus voltage.

    • Luminaires flicker or buzz, proper dimming not possible, device buzzes Cause: wrong dimming principle set.

  • LED lamp is dimly lit when dimmer is switched off Cause: LED lamp is not optimally suited for this dimmer.

    • Use a compensation module, see accessories.
    • Use another type of LED lamp or an LED lamp of another manufacturer.

Accessories

Compensation module LED

Warranty

The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error de-scription to your responsible salesperson (specialist trade/installation company/elec-trical specialist trade). They will forward the devices to the Gira Service Center.

Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-
Systeme

Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald

Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 – 602-0
Fax +49(0)21 95 – 602-191

www.gira.de

[email protected]

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

KNX User Manuals

Related Manuals