KNX 390041SR LED Universal Dimming Actuator 4-Gang Instruction Manual
- June 6, 2024
- KNX
Table of Contents
LED universal dimming actuator, 4-gang
LED universal dimming actuator, 4-gang Art. no.: 390041SR
Operating instructions
Safety instructions
Electrical devices may only be mounted and connected by electrically skilled
persons.
Serious injuries, fire, or property damage are possible. Please read and
follow the manual fully. The danger of electric shock. Always disconnect
before carrying out work on the device or load. The danger of electric shock.
The device is not suitable for disconnection from the supply voltage. The load
is not electrically isolated from the mains even when the output is switched
off. Risk of the destruction of the dimmer and load if the set operating mode
and load type do not match. Set the correct dimming principle before
connecting or exchanging the load. Fire hazard. For operation with inductive
transformers, each transformer must be fused on the primary side in accordance
with the manufacturer’s instructions. Only safety transformers according to EN
61558-2-6 may be used. These instructions are an integral part of the product
and must remain with the end customer.
Device components
Figure 1: Device components
- Button field for manual operation
- Programming button and LED
- KNX connection
- Status LEDs for outputs
- Load connections
Function
System informatio
This device is a product of the KNX system and complies with the KNX
directives. Detailed technical knowledge obtained in KNX training courses is a
prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on
loadable software and attainable functionality, as well as the software
itself, can be obtained from the manufacturer´s product database.
The device can be updated. Firmware can be easily updated with the Jung ETS
Service App (additional software).
The device is KNX Data Secure capable. KNX Data Secure offers protection
against manipulation in building automation and can be configured in the ETS
project. Detailed specialist knowledge is required. A device certificate,
which is attached to the device, is required for safe commissioning. During
mounting, the certificate must be removed from the device and stored securely.
Planning, installation, and commissioning of the device are carried out with
the aid of the ETS, version 5.7.3 and above.
Intended use
- Switching and dimming of incandescent lamps, HV halogen lamps, dimmable HV-LED lamps, dimmable compact fluorescent lamps, dimmable inductive transformers with LV halogen or LV LED lamps, dimmable electronic transformers with LV halogen or LV LED lamps
- Operating in KNX systems
- Mounting on DIN rail according to EN 60715 in sub-distribution unit
- If inductive or electronic transformers are connected, observe the data of the transformer manufacturer on loads and the dimming principle.
- HV-LED and compact fluorescent lamps generate high pulsed currents when they are operated in the leading edge phase control.
- Our dimmers take into account the different electronic characteristics of most LED lamps found on the market.
- However, it cannot be guaranteed that in individual cases the desired results may not be achieved.
Product characteristics
- Outputs can be operated manually, construction site mode
- Feedback in manual mode and in bus mode
- Disabling of individual outputs manually or by bus
- Status feedback KNX Data Secure compatible
- Updateable with ETS Service App
Dimming operation characteristics
- Automatic or manual selection of the dimming principle suitable for the load
- Protected against no-load, short-circuit, and overheating
- Signal in the event of a short-circuit
- Feedback of the switching position and the dimming value
- Parameterisable switch-on and dimming behavior
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
- Light scene operation
- Status indicator of the outputs via LED Operating hours counter Mains failure longer than approx. 5 seconds leads to the switch-off of the dimming actuator.
- Depending on the parameter setting, the connected load is calibrated after the resumption of the power supply.
- An increase in output power is possible through parallel switching of multiple outputs
- Power extension is possible by means of power boosters.
- Delivery state: Construction site mode, outputs can be operated using button field.
- Flickering of the connected lamps due to undershooting of the specified minimum load or through centralized pulses from the power stations. This does not represent any defect in the device.
Logic function characteristics
- logic gates
- Transformer (conversion)
- Disabling element comparator
- Limit value switch
Operation
Operating elements
Status LEDs for outputs|
- on: output switched on, 1…100
- flashes slowly (1 Hz): short-circuit or manual mode
- flashes quickly (2 Hz): overload, mains voltage failure or firmware update
(6) Button
Manual operation
(7)LED
on: continuous manual mode
8)LED / on:
selected output on, 1…100%
flashes: Firmware update
(9)Button on/
Switch on/increase brightness
(10) Button off/
Switch off/reduce the brightness
(11) LED off/
on: Selected output off
flashes: Firmware update
(12) Button ALL OFF
Switching off all outputs
The LEDs (4) optionally indicate the states of the outputs only temporarily (parameter-dependent).
Operating modes
Bus operation: Operation via push-button sensors or other bus devices
Temporary manual control: manual control locally with keypad, automatic return
to bus
control
Continuous manual mode: Exclusively manual operation on the device
No bus operation is possible in manual mode.
After a bus failure and restoration the device switches to bus operation.
The manual mode can be disabled in ongoing operation via a bus telegram.
Switching on the temporary manual control
Operation using the button field is programmed and not disabled.
Press button (6) briefly.
LED (7) flashes, LED A1… (4) of the first configured output flashes.
Short-time manual operation is switched on.
** After 5 s without a key-press, the actuator returns automatically to bus
operation.
Switching off temporary manual operation
The device is in short-term manual mode. No button-press for 5 s.
– or Press **(6) button briefly as many times as necessary until the
actuator leaves the short-time manual mode.
Status LED ** A1... (4) no longer flash, but rather indicate the output
status.
Short-time manual operation is switched off.
When switching off the manual control, the outputs, depending on the
programming, switch to the active position, e.g. forced position, logic
operation.
Switching on permanent manual control
Operation using the button field is programmed and not disabled.
Press the **button for at least 5 s. LED (7) lights, LED A1… (4) of the
first configured output flashes.
Continuous manual mode is switched on.
Switching off permanent manual control
The device is in continuous manual mode. Press the (6) button for at
least 5 s.
LED (7) is off.
Continuous manual mode is switched off. Bus operation is switched on.
When switching off the manual control, the outputs, depending on the
programming, switch to the active position, e.g. forced position, logic
operation.
Operating the outputs
The device is in continuous or short-term manual mode
Press the button **** (6) briefly as many times as necessary until the desired
output is selected.
The LED of the selected output A1… (4) flashes.
The LEDs (8 ) and oo f( ) indicate the status.
Switching off all outputs
The device is in continuous manual mode.
Press the button ALL OFF (7).
All outputs are shut off.
Disabling outputs
The device is in continuous manual mode. The bus control can be disabled
(ETS parameter).
Press the button **(6) repeatedly until the LED A1… (4) of the desired
output flashes.
Press the/on ( ) and / off ( ) buttons simultaneously for approx. 5 s.
The selected output is disabled.
The status LED A1... (4) of the selected output flashes quickly.
A disabled output can be operated in manual mode.
Re-enabling outputs**
The device is in continuous manual mode. One or more outputs were disabled in
manual mode.
Press the button **(6) repeatedly until the output to be unlocked is
selected.
Press the/ (9) and / (10) buttons simultaneously for approx. 5 s.
Disabling is deactivated.
LED A1** … (4) of the selected output flashes slowly.
Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
5.1 Fitting and electrical connection
Fitting the device
Insecure operation (preconditions):
– Secure commissioning is activated in the ETS.
–Device certificate entered/scanned or added to the ETS project. A high-
resolution camera should be used to scan the QR code.
–Document all passwords and keep them safe.
Observe ambient temperature. Ensure adequate cooling.
- Maintain a distance of 18 mm, 1 module when operating multiple dimmers or power units within the same control cabinet.
- Mount devise on DIN rail.
- Insecure operation: The device certificate must be removed from the device and stored securely.
Connecting the device
- Connect bus line with KNX connecting terminal according to their correct polarity.
- Attach the cover cap to the KNX connection as protection against hazardous voltages.
CAUTION!
The danger of destruction. 400 V is shorted when outputs switched in parallel
are connected to different outer phase conductors.
The device will be destroyed. Always connect outputs switched in parallel to
the same outer phase conductor.
Delivery state: The outputs can be operated with manual control.
In the “Universal” operating mode, the dimming actuator only calibrates itself
again after disconnection of the load and also after commissioning using the
ETS.
Inductive capacitive mixed load is not permitted.
For LED leading edge phase control: Connect a maximum of 2 electronic
transformers per output.
Connect 600 Watt LED lamps or compact fluorescent lamps at most per
16-ampere circuit breaker. When connecting transformers, observe the data of
the transformer manufacturer.
Several dimmer outputs can be combined for dimming greater lamp loads.
Only utilize parallel-switched outputs up to 95 % each. Do not connect any
compact fluorescent lamps to dimmer outputs switched in parallel.
Observe delivery state. Before connecting parallel outputs and switching
on, program the dimming actuator with ETS to the changed output configuration.
**** Do not expand parallel-switched dimmer outputs with power packs.
Connect the lamp loads according to the connection example.
Commissioning
Load physical address and application program
Press the programming button.
The programming LED lights up.
Load physical address and application program using the ETS.
Safe-state mode
The safe state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis
functions and programming of the device are possible. Manual operation is not
possible.
Activating the safe-state mode
- Switch off the bus voltage or remove the KNX device connection terminal.
- Wait about 15 s.
- Press and hold down the programming button.
- Switch on the bus voltage or attach the KNX device connection terminal. Release the programming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
With a new brief press of the programming button, the programming mode can be
switched on and off as usual also in the safe-state mode. If the Programming
mode is active,
the programming LED stops flashing.
Deactivating safe-state mode
Switch off bus voltage (wait for approx. 15 s) or carry out ETS programming.
Master reset
The master reset restores the basic device setting (physical address
15.15.255, firmware remains in place). The device must then be recommissioned
with the ETS. Manual operation is possible.
During secure operation: A master reset deactivates device security. The
device can then be recommissioned with the device certificate.
Performing a master reset
Precondition: The safe-state mode is activated.
Press and hold down the programming button for > 5 s. The programming LED
flashes quickly.
The device performs a master reset, restarts, and is ready for operation again
after approx. 5
Restoring the device to factory settings
Devices can be reset to factory settings with the Jung ETS Service App. This
function uses the firmware contained in the device that was active at the time
of delivery (delivery state). Restoring the factory settings causes the
devices to lose their physical address and configuration.
Technical data
Rated voltage
Mains frequency
Power loss
Standby power
Ambient temperature
Storage/transport temperature
Connected load per channel depends on the connected lamps and the set load
type: (Figure 5)| AC 110 … 230 V ~
50 / 60 Hz
max. 7 W
approx. 0.16 W per channel
-5 … +45 °C
-25 … +70 °C
ETS parameter load type
---|---
UNI universal (with automatic calibration procedure)
LJconv. transformer (inductive / leading edge phase control)
LED (leading edge phase control)
Electr. transformer (capacitive / trailing edge phase control)
LED (trailing-edge phase control)
**** Inductive capacitive mixed load is not permitted.
Power boosters Connection single-stranded
Finely stranded without conductor sleeve
Finely stranded with conductor sleeve
Connection torque screw terminals
Fitting width
KNX
KNX medium
Commissioning mode
Rated voltage KNX
Current consumption KNX
Connection mode KNX| 0.5 … 4 mm²
0.5 … 2.5 mm²
Max. 0.8 Nm
72 mm / 4 module
TP256
S-mode
DC 21 … 32 V SELV
6 … 15 mA
device connection terminal
---|---
Troubleshooting
Connected LED lamps or compact fluorescent lamps switch off in the lowest
dimming position or flicker
The set minimum brightness is too low.
Increase minimum brightness.
Connected LED lamps or compact fluorescent lamps flicker
Cause 1: Lamps are not dimmable.
Check manufacturer’s instructions.
Exchange lamps for another type.
Cause 2: Dimming principle and lamps do not optimally match.
For HV-LED: Check operation in another dimming principle, reduce connected
load as well if necessary.
For LV-LED: Check the lamp operating device and replace as necessary.
With the “Universal” setting: Define the dimming principle manually.
Connected HV-LED lamps or compact fluorescent lamps in the lowest dimming
position are too bright; the dimming range is too small
Cause 1: The set minimum brightness is too high.
Reduce minimum brightness.
Cause 2: HV-LED trailing-edge phase control dimming principle does not
optimally match the connected lamps.
Check operation in the “HV-LED leading edge phase control” setting, reduce
connected load as well if necessary.
Exchange lamps for another type.
Output has been switched off.
Cause 1: overheating protection has tripped.
Disconnect all outputs from the mains, and switch off the corresponding
circuit breakers.
HV-LED trailing-edge phase control: Reduce the connected load. Exchange lamps
for another type.
HV-LED leading edge phase control: Reduce the connected load. Check the
operation in the “HV-LED trailing-edge phase control” setting. Exchange lamps
for another type.
Let the device cool down for at least 15 minutes. Check installation
situation, ensure cooling, e.g. provide distance from surrounding devices.
Cause 2: Surge protection has triggered.
HV-LED trailing-edge phase control: Check the operation in the “HV-LED leading
edge phase control” setting, and reduce the connected load as well if
necessary.
Exchange lamps for another type.
The response of the surge protection can be signaled by sending a short-
circuit telegram or can be determined by polling the “short-circuit”
communication object.
Cause 3: short-circuit in the output circuit
Disconnect all outputs from the mains.
Eliminate short-circuit.
Switch on the mains voltage of the outputs again. Switch the affected output
off and on again.
When a short-circuit occurs the affected output switches off. Automatic
restart when a short circuit is eliminated within 100 ms (inductive load) or 7
seconds (capacitive or ohmic load). After that lasting switch-off.
** When a short-circuit occurs during the calibration process, the load
calibrates itself again after the short-circuit is eliminated.
Cause 4: load failure.
Check load, and replace a light bulb. For inductive transformers, check the
primary fuse and replace if necessary.
Manual control with button field not possible
Cause 1: Manual control has not been programmed.
Program manual control.
Cause 2: Manual control via bus disabled.
Enable manual control.
None of the outputs can be operated.
Cause 1: All of the outputs are disabled cancer disabling.
Cause 2: Manual mode active.
Deactivate manual mode (switch off continuous manual mode).
Cause 3: Application software missing or faulty.
Check programming and correct.
All outputs are off and not possible to switch on
Cause 1: bus voltage failure.
Check bus voltage.
Luminaires flicker or buzz, proper dimming is not possible, device buzzes
** Cause: wrong dimming principle set
Installation or commissioning error. Disconnect device and luminaire, switch
off the circuit breaker.
Check installation and correct.
If the wrong dimming principle has been preselected: Set the correct dimming
principle.
If the dimming actuator calibrates itself incorrectly, e.g. with highly
inductive mains or long load cables: preselect the correct dimming principle
with commissioning.
LED lamp is dimly lit when the dimmer is switched off Cause: the LED lamp is
not optimally suited for this dimmer.
Use a compensation module, see accessories.
Use another type of LED lamp or an LED lamp of another manufacturer.
Accessories
Connection cover……………………. 2050 K
Compensation module LED………………… KMLED230U
Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
ALBRECHT JUNG GMBH & CO. KG
Volmestraße 1
58579 Schalksmühle
GERMANY
Telefon: +49 2355 806-0
Telefax: +49 2355 806-204
kundencenter@jung.de
www.jung.de
References
- JUNG - LED universal dimming actuator, 4-gang Actuators for rail mounting Devices for rail mounting KNX OVERVIEW
- JUNG - Switches and systems
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>