KNX 5062 00 Gira Switching Actuator Instruction Manual
- June 10, 2024
- KNX
Table of Contents
KNX 5062 00 Gira Switching Actuator
Product Information
The Switching actuator 2-gang / blind actuator, 1-gang 16 A with binary input, 3-gang (Order no. 5062 00) is a product of the KNX system and complies with the KNX directives. It is a switching actuator with two relay outputs and a binary input for controlling blinds or other loads. The device is KNX Data Secure capable and can be easily updated with the Gira ETS Service App (additional software). Planning, installation, and commissioning of the device are carried out with the aid of the ETS, version 5.7.3 and above.
Safety instructions
- Electrical devices may only be mounted and connected by electrically skilled persons.
- Serious injuries, fire or property damage possible. Please read and follow manual fully.
- Danger of electric shock. Device is not suitable for disconnection from supply voltage.
- Danger of electric shock. Make sure during the installation that there is always sufficient insulation between the mains voltage and the bus. A minimum distance of at least 4 mm must be maintained between bus conductors and mains voltage cores.
- Danger of electric shock on the KNX installation. Do not connect any external voltage to the inputs. The device might be damaged, and the SELV potential on the KNX bus line will no longer be available.
- For parallel connection of several motors to an output it is essential to observe the corresponding instructions of the manufacturers, and to use a cut-off relay if necessary.
- The motors may be destroyed.
- Use only Venetian blind motors with mechanical or electronic limit switches. Check the limit switches for correct adjustment. Observe the specifications of the motor manufacturers. Device can be damaged.
- This manual is an integral part of the product, and must remain with the end customer.
Device components
- Programming LED
- Programming button
- Control cable (KNX connection and extension inputs)
- Connection of load (relay outputs)
- red (RD) KNX +
- black (BK) KNX –
- green (GN) Input 1 (push-button, switch, contact, condensation/leakage sensor)
- yellow (YE) Input 2 (push-button, switch, contact, condensation/leakage sensor)
- white (WH) Input 3 (push-button, switch, contact, condensation/leakage sensor, NTC temperature sensor)
- brown (BN) COM inputs 1…3
Product Usage Instructions
Before using the Switching actuator 2-gang / blind actuator, 1-gang 16 A with binary input, 3-gang, please read the safety instructions carefully. Electrical devices may only be mounted and connected by electrically skilled persons. Serious injuries, fire, or property damage are possible if the manual is not followed properly. To connect the device, please follow the connection assignment of the control cable as shown in Image 2 in the user manual. The red (RD) and black (BK) wires are for KNX connection and extension inputs. The green (GN), yellow (YE), and white (WH) wires are for KNX Input 1, Input 2, and Input 3 respectively. The brown (BN) wire is for COM inputs 1-3.
When installing the device, make sure there is always sufficient insulation between the mains voltage and the bus. A minimum distance of at least 4 mm must be maintained between bus conductors and mains voltage cores. Do not connect any external voltage to the inputs to avoid damaging the device and losing the SELV potential on the KNX bus line. If you want to parallel connect several motors to an output, observe the corresponding instructions of the manufacturers and use a cut-off relay if necessary. Use only Venetian blind motors with mechanical or electronic limit switches and check the limit switches for correct adjustment. Observe the specifications of the motor manufacturers to avoid damaging the device. The device can be updated easily with the Gira ETS Service App (additional software). The firmware can be updated with this app. The device is KNX Data Secure capable and can be configured in the ETS project. During mounting, the device certificate must be removed from the device and stored securely.
Function
System information
This device is a product of the KNX system and complies with the KNX
directives. Detailed technical knowledge obtained in KNX training courses is a
prerequisite to proper understanding.
The function of this device depends upon the software. Detailed information on
loadable software and attainable functionality as well as the software itself
can be obtained from the manufacturer´s product database. The device can be
updated. Firmware can be easily updated with the Gira ETS Service App
(additional software). The device is KNX Data Secure capable. KNX Data Secure
offers protection against manipulation in building automation and can be
configured in the ETS project. Detailed specialist knowledge is required. A
device certificate, which is attached to the device, is required for safe
commissioning. During mounting, the device certificate must be removed from
the device and stored securely. Planning, installation and commissioning of
the device are carried out with the aid of the ETS, version 5.7.3 and above.
Intended use
- Operating in KNX systems
- Switching electrical loads via relay contacts with common reference potential
- Switching of electrically-driven Venetian blinds, roller shutters, awnings and similar hangings
- Reading in switching states of installation switches or push-buttons and other potential-free contacts at inputs 1…3
- Signal evaluation of condensation and leakage sensors at inputs 1…3 (see accessory).
- Acquisition of temperature values via NTC temperature sensor at input 3 (see accessories)
- Mounting in appliance boxes according to DIN 49073
Product characteristics
- Outputs can be operated via KNX telegrams or extension inputs
- Three extension inputs for connecting potential-free contacts or dew/leakage sensors. NTC temperature sensor can be connected to input 3.
- Supply via KNX, no additional power supply necessary
- KNX Data Secure compatible
- Updatable with Gira ETS Service App
Characteristics switch operation
- Operation as NO or NC contacts
- Feedback function
- Logic and restraint function
- Central switching functions with collective feedback
- Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
- Scene function
- Operating hours counter
Characteristics blinds operation
- Operating modes “Venetian blind with slats”, “Roller shutter/awning”, “Venting louvre/roof window”
- Blind/shutter position directly controllable
- Slat position directly controllable
- Feedback of movement status, blind/shutter position and slat position
- Forced position through higher-level controller
- Safety function: 3 independent wind alarms, rain alarm, frost alarm
- Sun protection function with heating/cooling operation
- Disabling function (lock-out protection)
- Scene function
Extension input characteristics
- Switching operating function
- Dimming operating function (incl. colour temperature dimming)
- Shutter/Venetian blinds operating function
- Value transmitter operating function (1-byte, 2-byte, 3-byte and 6-byte incl. RGBW and colour temperature presets)
- Scene extension operating function
- 2-channel operation operating function
- Controller extension operating function
- Disabling functions
- Debounce time adjustable
Logic function characteristics
- Logic gate
- Transformer (conversion)
- Disabling element
- Comparator
Information for electrically skilled persons
DANGER!
Mortal danger of electric shock. Disconnect the device. Cover up live parts.
Mounting and electrical connection
DANGER!
When connecting the bus/extensions and mains voltage wires in a shared
appliance box, the KNX bus line may come into contact with the mains voltage.
This endangers the safety of the entire KNX installation. People at remote
devices may also receive an electric shock. Do not place bus/extensions and
mains voltage terminals in a shared connection compartment. Use an appliance
box with a fixed partition wall or separate appliance boxes.
Connecting and fitting the device
In secure operation (preconditions):
- Secure commissioning is activated in the ETS.
- Device certificate entered/scanned or added to the ETS project. A high resolution camera should be used to scan the QR code.
- Document all passwords and keep them safe.
- Mounting in suitable appliance box (recommendation: electronic device box with partition). Observe cable routing and spacing (see figure 3)!
- Appliance box
- Partition
- potential-free contacts (e.g. series push-button)
- NTC temperature sensor (optional)
Minimum spacing between the mains voltage and bus/extension wires: 4 mm (see figure 4)
Observe ambient temperature. Ensure adequate cooling.
- Connect bus line, observing the correct polarity.
- Connect load as shown in the connection example (see figure 5).
- If required, connect potential-free contacts or condensation/leakage sensors to inputs 1…3, or NTC temperature sensors to input 3 (see figure 2).
- Install the device in the appliance box.
- In secure operation: The device certificate must be removed from the device and stored securely.
- The COM reference potential must not be connected together with COM connections of other devices!
Commissioning
NOTICE!
Incorrect load control due to undefined relay state at delivery. Risk of
destruction of connected drive motors. During commissioning, before switching
on the load, ensure that all relay contacts are open by applying the KNX bus
voltage. Observe commissioning sequence!
- Switch on the KNX bus voltage.
- Wait about 10 s.
- Connect the load circuit.
Delivery state: The output is set as a Venetian blind output. Operation of the blind output possible via input 1 (UP) and input 2 (DOWN). Input 3 has no function.
Function of Inputs in the as-delivered state
Input | Push-button (NO con- tact) | Function |
---|---|---|
1 | Press briefly (< 0.4 s) | Stop |
1 | Press briefly (< 0.9 s) | Adjusting the slats UP |
1 | Press for a long time (> 0.9 s) | Raise |
2 | Press briefly (< 0.4 s) | Stop |
2 | Press briefly (< 0.9 s) | Adjusting the slats DOWN |
2 | Press for a long time (> 0.9 s) | Lower |
3 | — | — |
Load physical address and application program
- For switched loads, configure the outputs as a switching output.
- For Venetian blind operation, configure the outputs as a Venetian blind output.
- In Venetian blind operation: measure blind/shutter and slat travel times and enter them in the parameter setting.
- Press the programming button.The programming LED lights up.
- Load physical address and application program using the ETS.
Safe-state mode
The safe-state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis
functions and programming of the device are possible.
Activating safe-state mode
- Switch off the bus voltage or disconnect the device from the KNX.
- Wait about 10 s.
- Press and hold down the programming button.
- Switch on the bus voltage or connect the device to KNX. Release the programming button only after the programming LED starts flashing slowly.
The safe-state mode is activated. By briefly pressing the programming button again, the programming mode can also be switched on and off in the safe-state mode as usual. If the programming mode is active, the programming LED stops flashing.
Deactivating safe-state mode
Switch off bus voltage (wait approx. 10 s) or carry out ETS programming.
Master reset
The master reset restores the basic device settings (physical address
15.15.255, firmware remains in place). The device must then be recommissioned
with the ETS. In secure operation: A master reset deactivates device security.
The device can then be recommissioned with the device certificate.
Performing a master reset
Precondition : The safe-state mode is activated.
Press and hold down the programming button for > 5 s. The programming LED
flashes quickly. The device performs a master reset, restarts and is ready for
operation again after approx. 5 s.
Restoring the device to factory settings
Devices can be reset to factory settings with the Gira ETS Service App. This
function uses the firmware contained in the device that was active at the time
of delivery (delivered state). Restoring the factory settings causes the
devices to lose their physical
address and configuration.
Technical data
KNX
- KNX medium TP256
- Commissioning mode S-mode
- Rated voltage KNX DC 21 … 32 V SELV
- Current consumption KNX 5 … 18 mA
- Connection mode KNX Device connection terminal on control cable
Outputs
- Connection mode Screw terminals
- Switching voltage AC 250 V ~
- Switching current per device Σ 16 A
- Fluorescent lamps Σ 16 AX
- Switch-on current 200 μs max. 800 A
- Switch-on current 20 ms max. 165 A
Power consumption per output
- Ohmic load 2500 W
- Capacitive load max. 16 A (140 μF)
- Motors 1380 VA
- Incandescent lamps 2300 W
- HV halogen lamps 2300 W
- HV-LED lamps max. 400 W
- LV halogen lamps with electronic transformers 1500 W
- LV halogen lamps with inductive transformer 1200 VA
- Compact fluorescent lamps uncompensated 1000 W
- Compact fluorescent lamps parallel compensated 1160 W (140 μF)
Reduction of switching current per device (referred to Σ 16 A)
- per 5 °C in excess of 35 °C -10%
- when installed in wooden or dry construction walls -15%
- when installed in multiple combinations -20%
Clampable conductor cross-section
- Single stranded 0.5 … 4 mm²
- Finely stranded without conductor sleeve 0.5 … 4 mm²
- Finely stranded with conductor sleeve 0.5 … 2.5 mm²
- Connection torque, screw terminals max. 0.8 Nm
Ambient conditions
- Ambient temperature -5 … +45 °C
- Storage/transport temperature -25 … +70 °C
- Dimensions (W × H × D) 48 x 50 x 28 mm
Inputs
- Control cable (preterminated) YY6x0.6
- Input type Potential-free
- Number 3
- Total length of extension device cable max. 10 m
- Cable type (preferably) J-Y(St)Y
- Poll voltage, extension inputs approx. 5 V
Accessories
- Remote sensor (NTC temperature sensor) 1493 00
- Condensation sensor 5069 00
- Leakage sensor 5068 00
Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade. Please submit or send faulty devices postage paid together with an error description to your responsible salesperson (specialist trade/installation company/electrical specialist trade). They will forward the devices to the Gira Service Center.
Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-
Systeme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 – 602-0
Fax +49(0)21 95 – 602-191
www.gira.de
info@gira.de