MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps Installation Guide

June 13, 2024
Mitsubishi Electric

HYDRONICS & IT COOLING SYSTEMS S.p.A.
AWR-HT AIR SOURCE REVERSIBLE
HEAT PUMPS FOR OUTDOOR
INSTALLATION

AWR-HT Air Source Reversible Heat Pumps

Air source reversible heat pump with scroll compressors, from 34 to 181 kW

Committed to achieve premium sustainability and efficiency targets, AWR-HT is the new compact heat pump able to produce high temperature water for domestic use, but also chilled water for air conditioning in Summer.
With this solution the space heating can be easily provided by using radiators, without any major changes on the already existing distribution system.
AWR-HT is a ready-to-use heat pump. Neither probes nor connections pipes to wells are needed, making this heat pump an ideal solution for both new and replacement constructions.
THE PERFECT HEAT PUMP FOR EVERY NEED

| The unit works as a heat pump by exploiting the heat of the air-source air via the finned coil heat exchanger and then heats the water
delivered to the distribution system via a plate heat exchanger.
The unit can supply water up to 65°C, ideal for space heating and residential applications, operating over a wide outdoor air temperature range, ideal for space heating and residential applications.
---|---
| The unit operates as a simple chiller and transfers the excess heat from the inside environment (heat of condensation) to the air via a finned coil heat exchanger.

COMFORT APPLICATIONS

  • Commercial premises
  • Office buildings
  • Hotels and resorts
  • Healthcare facilities
  • Retail and department stores
  • Sports and leisure installations

ACOUSTIC VERSION

| Premium efficiency version| Class A enhanced
---|---|---
| Premium efficiency version| Class A enhanced, low-noise

HEAT RECOVERY CONFIGURATIONS

| Standard unit| Unit for the production of chided water.| Baseline
---|---|---|---
| Partial heat recovery| A super heater on the compressor discharge line
recovers approximately 20% of the unit’s capacity.| 60°C

AWR-HT, the easiest and most efficient way to combine both hot water for space heating and domestic use, as well as air conditioning

**| PREMIUM ´CLASS A’ EFFICIENCY
The full range is available with rating over the Class A.
AWR-HT/CA-E and AWR-HT/LNCA-E ensures premium efficiencies and quietness, making this range the best solution for both residential and light commercial markets.
---|---
|
OPERATION DOWN TO -20°C
AWR-HT is the perfect solution in terms of extended operation even in extreme weather conditions. Without using any other heating device, this heat pump operates also in harsh climate areas with outdoor temperatures down to -20°C.
|
MODULAR CONFIGURATION
For medium- and high- capacity installations, system capacity can be extended to up to 1000 kW using a modular configuration. This feature allows to manage different thermal loads according to the real demand, treating heating requirements for domestic use differently from heating requirements for space heating, or cooling.
|
HOT WATER UP TO 65°C
All units produce hot water up to 65°C for space heating and domestic purposes. Thanks to this solution the space heating can be easily  provided by using radiators, without any major changes on the already existing distribution system available on site.
|
RELIABILITY ABOVE ALL
AWR-HT offers maximum operating reliability, thanks to their two main features:
▶ Two independent circuits for all sizes;
▶ An advanced system to prevent formation of ice on the coil, ensuring shorter and more efficient defrost cycles.
|
RENEWABLE ENERGY FOR COMMERCIAL INSTALLATIONS**
AW-HT is the ideal solution in replacing old boilers systems where there is the need to retain the existing water distribution plant based on radiators.
This situation is typical in public spaces such as schools, government offices, as well as blocks of buildings for residential use, where it is common practice to have a centralized heating and cooling system.

TECHNOLOGICAL CHOICES

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Fig1

W3000SE CONTROL and USER-FRIENDLY USER INTERFACE
Fully in-house software developed by Mitsubishi Electric Hydronics & IT Cooling Systems.

  • 19 supported languages.
  • Optional serial cards with the most common protocols are available: Mod Bus, BACnet MS/TP RS485, BACnet Over IP, Echelon Lon works.
  • “QUICK MIND” logic: a self-adapting algorithm that activates or deactivates the compressors only when a change in the system load moves the flow temperature out of the setpoint neutral zone.
  • Diagnostics: “BLACK BOX” function for saving more than 100 machine variables for a rapid troubleshooting.

Advanced technologies smartly applied to achieve top-level performance levels.

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Fig2

Compact Keyboard

The compact keyboard comes as standard in all units.

  • Large LCD display and functional keys.
  • Quick and easy parameter consultation and adjustment by means of a multi-level menu with settable display language.

| AWR-HT 0122-0302 34-91,7 kW
High efficiency reversible heat pump, air source for outdoor installation, high water temperature
---|---
AWR-HT / CA-E| 0122| 0152| 0202| 0262| 0302
---|---|---|---|---|---
Power supply
COOLING ONLY (GROSS| VALUE)| V/ph/Hz| 400/3+N/50| 400/3+N/50| 400/3+N/50| 400/3+N/50| 400/3+N/50
Cooling capacity| (1)| kW| 34,10| 43,80| 60,30| 76,40| 91,70
Total power input| (1)| kW| 11,60| 14,70| 20,40| 25,80| 31,30
EER| (1)| kW/kW| 2,940| 2,980| 2,956| 2,961| 2,930
ESEER| (1)| kW/kW| 3,400| 3,340| 3,400| 3,380| 3,350

COOLING ONLY (EN14511 VALUE)

Cooling capacity (1)(2) kW 34,00 43,70 60,20 76,20 91,40
EER (1)(2) kW/kW 2,910 2,950 2,940 2,930 2,890
ESEER (1)(2) kW/kW 3,340 3,260 3,330 3,300 3,270
Cooling energy class B B B B B

HEATING ONLY (GROSS VALUE)
Total heating capacity| (3)| kW| 38,00| 51,30| 68,80| 84,90| 102,0
Total power input| (3)| kW| 10,70| 14,40| 19,40| 23,60| 27,70
COP| (3)| kW/kW| 3,551| 3,562| 3,546| 3,597| 3,682
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 38,10| 51,40| 69,00| 85,20| 102,3
COP| (3)(2)| kW/kW| 3,530| 3,540| 3,520| 3,560| 3,650
Cooling energy class| | | A| A| A| A| A

ENERGY EFFICIENCY

Prated,c (11) kW
SEER (11)(12)
Performance hs (11)(13) %

SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
Design| (4)| kW| 28,4| 33,8| 47,5| 58,5| 70,6
SCOP| (4)(14)| | 3,24| 3,16| 3,22| 3,26| 3,35
Performance has| (4)(15)| %| 127| 124| 126| 127| 131
Seasonal efficiency class| (16)| | A+| A+| A+| A+| –
Design| (5)| kW| 30,5| 36,8| 50,7| 63,3| 74,7
SCOP| (5)(14)| | 3,00| 2,98| 3,01| 3,05| 3,12
Performance has| (5)(15)| %| 117| 116| 117| 119| 122
Seasonal efficiency class| (17)| | A+| A+| A+| A+| –
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow| (1)| l/s| 1,631| 2,095| 2,884| 3,654| 4,385
Pressure drop| (1)| kPa| 8,10| 9,21| 11,0| 14,5| 18,2
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 1,834| 2,476| 3,321| 4,098| 4,924
Pressure drop| (3)| kPa| 10,2| 12,9| 14,6| 18,3| 22,9
REFRIGERANT CIRCUIT
Compressors Nr.| N°| 2| 2| 2| 2| 2
No. Circuits| N°| 2| 2| 2| 2| 2
Refrigerant charge| kg| 13,0| 22,0| 27,6| 35,0| 42,0
NOISE LEVEL
Sound power level in cooling| (6)(7)| dB(A)| 84| 86| 87| 87| 87
Sound power level in heating| (6)(8)| dB(A)| 84| 86| 87| 87| 87
Sound Pressure| (9)| dB(A)| 67| 69| 70| 69| 69
SIZE AND WEIGHT
A| (10)| mm| 1695| 2195| 2745| 2745| 2745
B| (10)| mm| 1120| 1120| 1120| 1120| 1120
H| (10)| mm| 1465| 1465| 1465| 1665| 1665
Operating weight| (10)| kg| 510| 750| 870| 940| 1030

Notes:

  1. Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C.
  2. Values in compliance with EN14511
  3. Plant (side) heat exchanger water (in/out) 40°C/45°C; Source (side) heat exchanger air (in) 7°C – 87% R.H.
  4. Parameter calculated for LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
  5. Parameter calculated for MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
  6. Sound power on the basis of measurements made in compliance with ISO 9614.
  7. Sound power level in cooling, outdoors.
  8. Sound power level in heating, outdoors.
  9. Average sound pressure level at 1m distance, unit in a free field on a reflective surface; nonbinding value calculated from the sound power level.
  10. Unit in standard configuration/execution, without optional accessories.
  11. Parameter calculated according to [REGULATION (EU) N. 2016/2281]
  12. Seasonal energy efficiency ratio
  13. Seasonal space cooling energy efficiency
  14. Seasonal coefficient of performance
  15. Seasonal space heating energy efficiency
  16. Energy efficiency class referred to LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]
  17. Energy efficiency class referred to MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]

The units highlighted in this publication contain HFC R407C [GWP100 1774] fluorinated greenhouse gases.
Certified data in EUROVENT

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
icon12www.eurovent- certification.com

AWR-HT / LN-CA-E 0122 0152 0202 0262 0302
Power supply V/ph/Hz 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50

400/3+N/50
COOLING ONLY (GROSS VALUE)
Cooling capacity| (1)| kW| 34,00| 44,46| 60,20| 76,20| 90,40
Total power input| (1)| kW| 11,60| 14,90| 20,50| 26,10| 32,90
EER| (1)| kW/kW| 2,931| 2,987| 2,937| 2,920| 2,748
Cooling capacity| (1)(2)| kW| 33,90| 44,30| 60,10| 76,00| 90,10
---|---|---|---|---|---|---|---
EER| (1)(2)| kW/kW| 2,900| 2,940| 2,910| 2,890| 2,720
ESEER| (1)(2)| kW/kW| 3,330| 3,220| 3,290| 3,280| 3,100
Cooling energy class| B| B| B| C| C
HEATING ONLY (GROSS VALUE)
Total heating capacity| (3)| kW| 38,40| 50,43| 69,40| 85,80| 100,3
Total power input| (3)| kW| 10,70| 14,30| 19,40| 23,70| 27,60
COP| (3)| kW/kW| 3,589| 3,524| 3,577| 3,620| 3,634
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 38,50| 50,60| 69,60| 86,10| 100,6
COP| (3)(2)| kW/kW| 3,560| 3,490| 3,550| 3,590| 3,600
Cooling energy class| | | A| A| A| A| A

ENERGY EFFICIENCY

SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration

Prated,c (11) kW
SEER (11)(12)
Performance hs (11)(13) %

SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)

PDesign (4)            kW 26,8 34,5 47,8 59,3 70,3
SCOP (4)(14) 3,26 3,14 3,24 3,29 3,35
Performance hs (4)(15) % 127 123 127 128 131
Seasonal efficiency class (16) A+ A+ A+ A+
PDesign (5) kW 28,8 37,1 50,9 63,3 75,2
SCOP (5)(14) 3,00 2,97 3,02 3,05 3,11
Performance hs (5)(15) % 117 116 118 119 121
Seasonal efficiency class (17) A+ A+ A+ A+

EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow| (1)| l/s| 1,626| 2,126| 2,879| 3,644| 4,323
Pressure drop| (1)| kPa| 8,05| 17,7| 11,0| 14,5| 17,7
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 1,854| 2,434| 3,350| 4,142| 4,842
Pressure drop| (3)| kPa| 10,5| 23,2| 14,8| 18,7| 22,2
REFRIGERANT CIRCUIT
Compressors nr.| N°| 2| 2| 2| 2| 2
No. Circuits| N°| 2| 2| 2| 2| 2
Refrigerant charge| kg| 16,0| 25,3| 35,3| 44,1| 52,0
NOISE LEVEL
Sound power level in cooling| (6)(7)| 80| 82| 83| 83| | 84
Sound power level in heating| (6)(8)| 82| 82| 84| 85| | 86
Sound Pressure| (9)| dB(A)| 48| 50| 51| 51| 52
SIZE AND WEIGHT
A| (10)| mm| 1695| 2195| 2745| 2745| 2745
B| (10)| mm| 1120| 1120| 1120| 1120| 1120
H| (10)| mm| 1465| 1465| 1465| 1665| 1665
Operating weight| (10)| kg| 550| 780| 940| 1010| 1060

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Diogram

| AWR-HT 0404-0604 116-181 kW
High efficiency reversible heat pump, air source for outdoor
---|---
AWR-HT / CA-E| 0404| 0524| 0604
---|---|---|---
Power supply| VALUE)| V/ph/Hz| 400/3/50| 400/3/50| 400/3/50
COOLING ONLY (GROSS
Cooling capacity| (1)| kW| 119,7| 146,5| 181,2
Total power input| (1)| kW| 43,80| 53,30| 65,80
EER| (1)| kW/kW| 2,733| 2,749| 2,754
ESEER| (1)| kW/kW| 3,340| 3,420| 3,310
COOLING ONLY (EN14511 VALUE)
Cooling capacity| (1)(2)| kW| 119,4| 146,1| 180,7
EER| (1)(2)| kW/kW| 2,710| 2,720| 2,730
ESEER| (1)(2)| kW/kW| 3,250| 3,330| 3,230
Cooling energy class| | | C| C| C
HEATING ONLY (GROSS VALUE)
Total heating capacity| (3)| kW| 134,9| 171,0| 204,8
Total power input| (3)| kW| 39,60| 48,10| 58,90
COP| (3)| kW/kW| 3,407| 3,555| 3,477
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 135,4| 171,6| 205,5
COP| (3)(2)| kW/kW| 3,380| 3,520| 3,450
Cooling energy class| A| A| A
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c| (11)| kW| –                                    –| –|
SEER| (11)(12)| | –                                    –| –|
Performance hs| (11)(13)| %| –                                    –| –|
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)| |
PDesign| (4)| kW| 92,6| 117| 139
SCOP| (4)(14)| | 3,23| 3,40| 3,29
Performance hs| (4)(15)| %| 126| 133| 129
Seasonal efficiency class| (16)| –| –| –| –
PDesign| (5)| kW| 98,9| 126| 148
SCOP| (5)(14)| | 3,02| 3,19| 3,08
Performance hs| (5)(15)| %| 118| 125| 120
Seasonal efficiency class| (17)| | –| –| –
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION

Water flow| (1)| l/s| 5,724| 7,006| 8,665
Pressure drop| (1)| kPa| 19,6| 20,6| 24,0
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 6,512| 8,254| 9,886
Pressure drop| (3)| kPa| 25,4| 28,6| 31,3
REFRIGERANT CIRCUIT
Compressors nr.| N°| 4| 4| 4
No. Circuits| N°| 2| 2| 2
Refrigerant charge| kg| 66,0| 108| 108
NOISE LEVEL
Sound power level in cooling| (6)(7)| dB(A)| 92| 93| 94
Sound power level in heating| (6)(8)| dB(A)| 92| 93| 94
Sound Pressure| (9)| dB(A)| 73| 73| 74
SIZE AND WEIGHT
A| (10)| mm| 3110| 4110| 4110
B| (10)| mm| 2220| 2220| 2220
H| (10)| mm| 2150| 2150| 2150
Operating weight| (10)| kg| 1950| 2400| 2530

Notes:

  1. Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C.
  2. Values in compliance with EN14511
  3. Plant (side) heat exchanger water (in/out) 40°C/45°C; Source (side) heat exchanger air (in) 7°C – 87% R.H.
  4. Parameter calculated for LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
  5. Parameter calculated for MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
  6. Sound power on the basis of measurements made in compliance with ISO 9614.
  7. Sound power level in cooling, outdoors.
  8. Sound power level in heating, outdoors.
  9. Average sound pressure level at 1m distance, unit in a free field on a reflective surface; nonbinding value calculated from the sound power level.
  10. Unit in standard configuration/execution, without optional accessories.
  11. Parameter calculated according to [REGULATION (EU) N. 2016/2281]
  12. Seasonal energy efficiency ratio
  13. Seasonal space cooling energy efficiency
  14. Seasonal coefficient of performance
  15. Seasonal space heating energy efficiency
  16. Energy efficiency class referred to LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]
  17. Energy efficiency class referred to MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]

The units highlighted in this publication contain HFC R407C [GWP100 1774] fluorinated greenhouse gases.
Certified data in EUROVENT

AWR-HT / LN-CA-E **** 0404 0524 0604
Power supply V/ph/Hz 400/3/50 400/3/50 400/3/50

COOLING ONLY (GROSS VALUE)
Cooling capacity| (1)| kW| 116,3| 144,7| 175,8
Total power input| (1)| kW| 42,00| 52,20| 63,20
EER| (1)| kW/kW| 2,769| 2,772| 2,782
ESEER| (1)| kW/kW| 3,390| 3,470| 3,370
COOLING ONLY (EN14511 VALUE)
Cooling capacity| (1)(2)| kW| 116,0| 144,3| 175,3
EER| (1)(2)| kW/kW| 2,740| 2,740| 2,750
ESEER| (1)(2)| kW/kW| 3,310| 3,370| 3,280
Cooling energy class| | | C| C| C
HEATING ONLY (GROSS| VALUE)| | | |
Total heating capacity| (3)| kW| 134,9| 171,0| 204,8
Total power input| (3)| kW| 39,60| 48,10| 58,90
COP| (3)| kW/kW| 3,407| 3,555| 3,477
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 135,4| 171,6| 205,5
COP| (3)(2)| kW/kW| 3,380| 3,520| 3,450
Cooling energy class| A| A| A
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c| (11)| kW| –                                     – –
SEER| (11)(12)| | –                                     – –
Performance hs| (11)(13)| %| –                                     – –
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
PDesign| (4)| kW| 92,6| 117| 139
SCOP| (4)(14)| | 3,23| 3,40| 3,29
Performance hs| (4)(15)| %| 126| 133| 129
Seasonal efficiency class| (16)| | –| –| –
PDesign| (5)| kW| 98,9| 126| 148
SCOP| (5)(14)| | 3,02| 3,19| 3,08
Performance hs| (5)(15)| %| 118| 125| 120
Seasonal efficiency class| (17)| | –| –| –
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION

Water flow| (1)| l/s| 5,562| 6,920| 8,407
Pressure drop| (1)| kPa| 18,5| 20,1| 22,6
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 6,512| 8,254| 9,886
Pressure drop| (3)| kPa| 25,4| 28,6| 31,3
REFRIGERANT CIRCUIT|
Compressors nr.| | N°| 4| 4| 4
No. Circuits| | N°| 2| 2| 2
Refrigerant charge| | kg| 70,0| 110| 110
NOISE LEVEL
Sound power level in cooling| (6)(7)| dB(A)| 86| 86| 87
Sound power level in heating| (6)(8)| dB(A)| 88| 88| 89
Sound Pressure| (9)| dB(A)| 67| 66| 67
SIZE AND WEIGHT
A| (10)| mm| 3110| 4110| 4110
B| (10)| mm| 2220| 2220| 2220
H| (10)| mm| 2150| 2150| 2150
Operating weight| (10)| kg| 1960| 2410| 2540

“ BY FAR THE BEST PROOF IS EXPERIENCE ”
Sir Francis Bacon British philosopher (1561 – 1626)

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Fig3

IKOS OLIVIA HOTEL
2015 Geraniin – Chalcidice – Greece
Application: Hotel and resorts
Plant type: Hydronic System
Cooling capacity: 1718 kW
Heating capacity: 2682 kW
Installed machines:
9x AW-HT LN/CAE 0302,
2x NECS-N/CA,
1x NX-N T/LN CA,
1x FOCS2-W/CAE/H

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Fig4

Project
This 5-star resort rises on white sands and refreshing waters of the Aegean. Ikos Olivia boasts spacious rooms, suites and bungalows with flowing green gardens, several swimming pools and a Spa.
Challenge
Ensuring maximum comfort for all guests and making their holidays unforgettable both inside their rooms as well as in common areas like swimming pools and the spa, was a key challenge. For owners, energy efficiency and reliability were also fundamental, in order to reduce running and maintenance costs and to contribute to an outstanding business performance of the hotel.
Solution
To perfectly satisfy the hot water request for swimming pools and for domestic hot water, the heating system is based on 9 air source heat pumps AW HT by Climaveneta. These units in fact can supply hot water up to 65°C.
Climaveneta branded heat pumps are ready-to-be-installed units. Neither probes nor connection pipes to wells are needed, thus making the installation activities onsite quick and easy.
Every project is characterized by different needs and system specifications for various climates. All these projects share high energy efficiency, maximum integration, and total reliability resulting from the Climaveneta brand experience.
Villaggio Valentino
2018 Castellaneta Marina – Italy Hotel and resorts
Plant type: Hydronic System
Cooling capacity: 393 kW
Heating capacity: 444 kW
Installed machines: 2x AWR-HT/D/CA-E 0202, 3x AWR-HT/D/CA-E 0302

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Fig5

Samhi Hotels Bangalore 2013 Bangalore – India
Hotel and resorts
Plant type: Hydronic System
Cooling capacity: 87.3 kW
Heating capacity: 116.7 kW
Installed machines: 1x AWR-HT/CA-E 0302

MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps -
Fig6

Vertical Wind Tunnel 2017 Milan – Italy Sport structures
Plant type: Hydronic System
Cooling capacity: 90 kW
Heating capacity: 120 kW
Installed machines: 1x AWR-HT LN CA E 0302, 1x AW HT 0061

for a greener tomorrow
Eco Changes is the Mitsubishi Electric Group’s environmental statement, and expresses the Group’s stance on environmental management. Through a wide range of businesses, we are helping contribute to the realization of a sustainable society.

MITSUBISHI ELECTRIC HYDRONICS & IT COOLING SYSTEMS S.p.A.
Head Office: Via Cadet Cephalonia 1 – 36061 Bassano del Grappa (VI) – Italy
Tel (+39) 0424 509 500 –
Fax (+39) 0424 509 509
www.climaveneta.com
www.melcohit.com

www.fsc.org

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Mitsubishi Electric User Manuals

Related Manuals