MITSUBISHI ELECTRIC AWR-HT Air Source Reversible Heat Pumps Installation Guide
- June 13, 2024
- Mitsubishi Electric
Table of Contents
HYDRONICS & IT COOLING SYSTEMS S.p.A.
AWR-HT AIR SOURCE REVERSIBLE
HEAT PUMPS FOR OUTDOOR
INSTALLATION
AWR-HT Air Source Reversible Heat Pumps
Air source reversible heat pump with scroll compressors, from 34 to 181 kW
Committed to achieve premium sustainability and efficiency targets, AWR-HT is
the new compact heat pump able to produce high temperature water for domestic
use, but also chilled water for air conditioning in Summer.
With this solution the space heating can be easily provided by using
radiators, without any major changes on the already existing distribution
system.
AWR-HT is a ready-to-use heat pump. Neither probes nor connections pipes to
wells are needed, making this heat pump an ideal solution for both new and
replacement constructions.
THE PERFECT HEAT PUMP FOR EVERY NEED
| The unit works as a heat pump by exploiting the heat of the air-source air
via the finned coil heat exchanger and then heats the water
delivered to the distribution system via a plate heat exchanger.
The unit can supply water up to 65°C, ideal for space heating and residential
applications, operating over a wide outdoor air temperature range, ideal for
space heating and residential applications.
---|---
| The unit operates as a simple chiller and transfers the excess heat from the
inside environment (heat of condensation) to the air via a finned coil heat
exchanger.
COMFORT APPLICATIONS
- Commercial premises
- Office buildings
- Hotels and resorts
- Healthcare facilities
- Retail and department stores
- Sports and leisure installations
ACOUSTIC VERSION
| Premium efficiency version| Class A enhanced
---|---|---
| Premium efficiency version| Class A enhanced, low-noise
HEAT RECOVERY CONFIGURATIONS
| Standard unit| Unit for the production of chided water.| Baseline
---|---|---|---
| Partial heat recovery| A super heater on the compressor discharge line
recovers approximately 20% of the unit’s capacity.| 60°C
AWR-HT, the easiest and most efficient way to combine both hot water for space heating and domestic use, as well as air conditioning
**| PREMIUM ´CLASS A’ EFFICIENCY
The full range is available with rating over the Class A.
AWR-HT/CA-E and AWR-HT/LNCA-E ensures premium efficiencies and quietness,
making this range the best solution for both residential and light commercial
markets.
---|---
| OPERATION DOWN TO -20°C
AWR-HT is the perfect solution in terms of extended operation even in extreme
weather conditions. Without using any other heating device, this heat pump
operates also in harsh climate areas with outdoor temperatures down to -20°C.
| MODULAR CONFIGURATION
For medium- and high- capacity installations, system capacity can be extended
to up to 1000 kW using a modular configuration. This feature allows to manage
different thermal loads according to the real demand, treating heating
requirements for domestic use differently from heating requirements for space
heating, or cooling.
| HOT WATER UP TO 65°C
All units produce hot water up to 65°C for space heating and domestic
purposes. Thanks to this solution the space heating can be easily provided by
using radiators, without any major changes on the already existing
distribution system available on site.
| RELIABILITY ABOVE ALL
AWR-HT offers maximum operating reliability, thanks to their two main
features:
▶ Two independent circuits for all sizes;
▶ An advanced system to prevent formation of ice on the coil, ensuring shorter
and more efficient defrost cycles.
| RENEWABLE ENERGY FOR COMMERCIAL INSTALLATIONS**
AW-HT is the ideal solution in replacing old boilers systems where there is
the need to retain the existing water distribution plant based on radiators.
This situation is typical in public spaces such as schools, government
offices, as well as blocks of buildings for residential use, where it is
common practice to have a centralized heating and cooling system.
TECHNOLOGICAL CHOICES
W3000SE CONTROL and USER-FRIENDLY USER INTERFACE
Fully in-house software developed by Mitsubishi Electric Hydronics & IT
Cooling Systems.
- 19 supported languages.
- Optional serial cards with the most common protocols are available: Mod Bus, BACnet MS/TP RS485, BACnet Over IP, Echelon Lon works.
- “QUICK MIND” logic: a self-adapting algorithm that activates or deactivates the compressors only when a change in the system load moves the flow temperature out of the setpoint neutral zone.
- Diagnostics: “BLACK BOX” function for saving more than 100 machine variables for a rapid troubleshooting.
Advanced technologies smartly applied to achieve top-level performance levels.
Compact Keyboard
The compact keyboard comes as standard in all units.
- Large LCD display and functional keys.
- Quick and easy parameter consultation and adjustment by means of a multi-level menu with settable display language.
| AWR-HT 0122-0302 34-91,7 kW
High efficiency reversible heat pump, air source for outdoor installation,
high water temperature
---|---
AWR-HT / CA-E| 0122| 0152| 0202| 0262| 0302
---|---|---|---|---|---
Power supply
COOLING ONLY (GROSS| VALUE)| V/ph/Hz| 400/3+N/50| 400/3+N/50|
400/3+N/50| 400/3+N/50| 400/3+N/50
Cooling capacity| (1)| kW| 34,10| 43,80| 60,30| 76,40| 91,70
Total power input| (1)| kW| 11,60| 14,70| 20,40| 25,80| 31,30
EER| (1)| kW/kW| 2,940| 2,980| 2,956| 2,961| 2,930
ESEER| (1)| kW/kW| 3,400| 3,340| 3,400| 3,380| 3,350
COOLING ONLY (EN14511 VALUE)
Cooling capacity | (1)(2) | kW | 34,00 | 43,70 | 60,20 | 76,20 | 91,40 |
---|---|---|---|---|---|---|---|
EER | (1)(2) | kW/kW | 2,910 | 2,950 | 2,940 | 2,930 | 2,890 |
ESEER | (1)(2) | kW/kW | 3,340 | 3,260 | 3,330 | 3,300 | 3,270 |
Cooling energy class | B | B | B | B | B |
HEATING ONLY (GROSS VALUE)
Total heating capacity| (3)| kW| 38,00| 51,30| 68,80| 84,90| 102,0
Total power input| (3)| kW| 10,70| 14,40| 19,40| 23,60| 27,70
COP| (3)| kW/kW| 3,551| 3,562| 3,546| 3,597| 3,682
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 38,10| 51,40| 69,00| 85,20| 102,3
COP| (3)(2)| kW/kW| 3,530| 3,540| 3,520| 3,560| 3,650
Cooling energy class| | | A| A| A| A| A
ENERGY EFFICIENCY
Prated,c | (11) | kW | – | – | – | – | – |
---|---|---|---|---|---|---|---|
SEER | (11)(12) | – | – | – | – | – | |
Performance hs | (11)(13) | % | – | – | – | – | – |
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
Design| (4)| kW| 28,4| 33,8| 47,5| 58,5| 70,6
SCOP| (4)(14)| | 3,24| 3,16| 3,22| 3,26| 3,35
Performance has| (4)(15)| %| 127| 124| 126| 127| 131
Seasonal efficiency class| (16)| | A+| A+| A+| A+| –
Design| (5)| kW| 30,5| 36,8| 50,7| 63,3| 74,7
SCOP| (5)(14)| | 3,00| 2,98| 3,01| 3,05| 3,12
Performance has| (5)(15)| %| 117| 116| 117| 119| 122
Seasonal efficiency class| (17)| | A+| A+| A+| A+| –
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow| (1)| l/s| 1,631| 2,095| 2,884| 3,654| 4,385
Pressure drop| (1)| kPa| 8,10| 9,21| 11,0| 14,5| 18,2
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 1,834| 2,476| 3,321| 4,098| 4,924
Pressure drop| (3)| kPa| 10,2| 12,9| 14,6| 18,3| 22,9
REFRIGERANT CIRCUIT
Compressors Nr.| N°| 2| 2| 2| 2| 2
No. Circuits| N°| 2| 2| 2| 2| 2
Refrigerant charge| kg| 13,0| 22,0| 27,6| 35,0| 42,0
NOISE LEVEL
Sound power level in cooling| (6)(7)| dB(A)| 84| 86| 87| 87| 87
Sound power level in heating| (6)(8)| dB(A)| 84| 86| 87| 87| 87
Sound Pressure| (9)| dB(A)| 67| 69| 70| 69| 69
SIZE AND WEIGHT
A| (10)| mm| 1695| 2195| 2745| 2745| 2745
B| (10)| mm| 1120| 1120| 1120| 1120| 1120
H| (10)| mm| 1465| 1465| 1465| 1665| 1665
Operating weight| (10)| kg| 510| 750| 870| 940| 1030
Notes:
- Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C.
- Values in compliance with EN14511
- Plant (side) heat exchanger water (in/out) 40°C/45°C; Source (side) heat exchanger air (in) 7°C – 87% R.H.
- Parameter calculated for LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
- Parameter calculated for MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
- Sound power on the basis of measurements made in compliance with ISO 9614.
- Sound power level in cooling, outdoors.
- Sound power level in heating, outdoors.
- Average sound pressure level at 1m distance, unit in a free field on a reflective surface; nonbinding value calculated from the sound power level.
- Unit in standard configuration/execution, without optional accessories.
- Parameter calculated according to [REGULATION (EU) N. 2016/2281]
- Seasonal energy efficiency ratio
- Seasonal space cooling energy efficiency
- Seasonal coefficient of performance
- Seasonal space heating energy efficiency
- Energy efficiency class referred to LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]
- Energy efficiency class referred to MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]
The units highlighted in this publication contain HFC R407C [GWP100 1774]
fluorinated greenhouse gases.
Certified data in EUROVENT
www.eurovent- certification.com
AWR-HT / LN-CA-E | 0122 | 0152 | 0202 | 0262 | 0302 | |
---|---|---|---|---|---|---|
Power supply | V/ph/Hz | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 | 400/3+N/50 |
400/3+N/50
COOLING ONLY (GROSS VALUE)
Cooling capacity| (1)| kW| 34,00| 44,46| 60,20| 76,20| 90,40
Total power input| (1)| kW| 11,60| 14,90| 20,50| 26,10| 32,90
EER| (1)| kW/kW| 2,931| 2,987| 2,937| 2,920| 2,748
Cooling capacity| (1)(2)| kW| 33,90| 44,30| 60,10| 76,00| 90,10
---|---|---|---|---|---|---|---
EER| (1)(2)| kW/kW| 2,900| 2,940| 2,910| 2,890| 2,720
ESEER| (1)(2)| kW/kW| 3,330| 3,220| 3,290| 3,280| 3,100
Cooling energy class| B| B| B| C| C
HEATING ONLY (GROSS VALUE)
Total heating capacity| (3)| kW| 38,40| 50,43| 69,40| 85,80| 100,3
Total power input| (3)| kW| 10,70| 14,30| 19,40| 23,70| 27,60
COP| (3)| kW/kW| 3,589| 3,524| 3,577| 3,620| 3,634
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 38,50| 50,60| 69,60| 86,10| 100,6
COP| (3)(2)| kW/kW| 3,560| 3,490| 3,550| 3,590| 3,600
Cooling energy class| | | A| A| A| A| A
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c | (11) | kW | – | – | – | – |
---|---|---|---|---|---|---|
SEER | (11)(12) | – | – | – | – | – |
Performance hs | (11)(13) | % | – | – | – | – |
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
PDesign | (4) kW | 26,8 | 34,5 | 47,8 | 59,3 | 70,3 | |
---|---|---|---|---|---|---|---|
SCOP | (4)(14) | 3,26 | 3,14 | 3,24 | 3,29 | 3,35 | |
Performance hs | (4)(15) | % | 127 | 123 | 127 | 128 | 131 |
Seasonal efficiency class | (16) | A+ | A+ | A+ | A+ | – | |
PDesign | (5) | kW | 28,8 | 37,1 | 50,9 | 63,3 | 75,2 |
SCOP | (5)(14) | 3,00 | 2,97 | 3,02 | 3,05 | 3,11 | |
Performance hs | (5)(15) | % | 117 | 116 | 118 | 119 | 121 |
Seasonal efficiency class | (17) | A+ | A+ | A+ | A+ | – |
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow| (1)| l/s| 1,626| 2,126| 2,879| 3,644| 4,323
Pressure drop| (1)| kPa| 8,05| 17,7| 11,0| 14,5| 17,7
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 1,854| 2,434| 3,350| 4,142| 4,842
Pressure drop| (3)| kPa| 10,5| 23,2| 14,8| 18,7| 22,2
REFRIGERANT CIRCUIT
Compressors nr.| N°| 2| 2| 2| 2| 2
No. Circuits| N°| 2| 2| 2| 2| 2
Refrigerant charge| kg| 16,0| 25,3| 35,3| 44,1| 52,0
NOISE LEVEL
Sound power level in cooling| (6)(7)| 80| 82| 83| 83| | 84
Sound power level in heating| (6)(8)| 82| 82| 84| 85| | 86
Sound Pressure| (9)| dB(A)| 48| 50| 51| 51| 52
SIZE AND WEIGHT
A| (10)| mm| 1695| 2195| 2745| 2745| 2745
B| (10)| mm| 1120| 1120| 1120| 1120| 1120
H| (10)| mm| 1465| 1465| 1465| 1665| 1665
Operating weight| (10)| kg| 550| 780| 940| 1010| 1060
| AWR-HT 0404-0604 116-181 kW
High efficiency reversible heat pump, air source for outdoor
---|---
AWR-HT / CA-E| 0404| 0524| 0604
---|---|---|---
Power supply| VALUE)| V/ph/Hz| 400/3/50| 400/3/50| 400/3/50
COOLING ONLY (GROSS
Cooling capacity| (1)| kW| 119,7| 146,5| 181,2
Total power input| (1)| kW| 43,80| 53,30| 65,80
EER| (1)| kW/kW| 2,733| 2,749| 2,754
ESEER| (1)| kW/kW| 3,340| 3,420| 3,310
COOLING ONLY (EN14511 VALUE)
Cooling capacity| (1)(2)| kW| 119,4| 146,1| 180,7
EER| (1)(2)| kW/kW| 2,710| 2,720| 2,730
ESEER| (1)(2)| kW/kW| 3,250| 3,330| 3,230
Cooling energy class| | | C| C| C
HEATING ONLY (GROSS VALUE)
Total heating capacity| (3)| kW| 134,9| 171,0| 204,8
Total power input| (3)| kW| 39,60| 48,10| 58,90
COP| (3)| kW/kW| 3,407| 3,555| 3,477
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 135,4| 171,6| 205,5
COP| (3)(2)| kW/kW| 3,380| 3,520| 3,450
Cooling energy class| A| A| A
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c| (11)| kW| – –| –|
SEER| (11)(12)| | – –| –|
Performance hs| (11)(13)| %| – –| –|
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)| |
PDesign| (4)| kW| 92,6| 117| 139
SCOP| (4)(14)| | 3,23| 3,40| 3,29
Performance hs| (4)(15)| %| 126| 133| 129
Seasonal efficiency class| (16)| –| –| –| –
PDesign| (5)| kW| 98,9| 126| 148
SCOP| (5)(14)| | 3,02| 3,19| 3,08
Performance hs| (5)(15)| %| 118| 125| 120
Seasonal efficiency class| (17)| | –| –| –
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow| (1)| l/s| 5,724| 7,006| 8,665
Pressure drop| (1)| kPa| 19,6| 20,6| 24,0
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 6,512| 8,254| 9,886
Pressure drop| (3)| kPa| 25,4| 28,6| 31,3
REFRIGERANT CIRCUIT
Compressors nr.| N°| 4| 4| 4
No. Circuits| N°| 2| 2| 2
Refrigerant charge| kg| 66,0| 108| 108
NOISE LEVEL
Sound power level in cooling| (6)(7)| dB(A)| 92| 93| 94
Sound power level in heating| (6)(8)| dB(A)| 92| 93| 94
Sound Pressure| (9)| dB(A)| 73| 73| 74
SIZE AND WEIGHT
A| (10)| mm| 3110| 4110| 4110
B| (10)| mm| 2220| 2220| 2220
H| (10)| mm| 2150| 2150| 2150
Operating weight| (10)| kg| 1950| 2400| 2530
Notes:
- Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C.
- Values in compliance with EN14511
- Plant (side) heat exchanger water (in/out) 40°C/45°C; Source (side) heat exchanger air (in) 7°C – 87% R.H.
- Parameter calculated for LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
- Parameter calculated for MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 813/2013]
- Sound power on the basis of measurements made in compliance with ISO 9614.
- Sound power level in cooling, outdoors.
- Sound power level in heating, outdoors.
- Average sound pressure level at 1m distance, unit in a free field on a reflective surface; nonbinding value calculated from the sound power level.
- Unit in standard configuration/execution, without optional accessories.
- Parameter calculated according to [REGULATION (EU) N. 2016/2281]
- Seasonal energy efficiency ratio
- Seasonal space cooling energy efficiency
- Seasonal coefficient of performance
- Seasonal space heating energy efficiency
- Energy efficiency class referred to LOW-TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]
- Energy efficiency class referred to MEDIUM TEMPERATURE application in AVERAGE climate conditions according to [REGULATION (EU) N. 811/2013]
The units highlighted in this publication contain HFC R407C [GWP100 1774]
fluorinated greenhouse gases.
Certified data in EUROVENT
AWR-HT / LN-CA-E | **** | 0404 | 0524 | 0604 |
---|---|---|---|---|
Power supply | V/ph/Hz | 400/3/50 | 400/3/50 | 400/3/50 |
COOLING ONLY (GROSS VALUE)
Cooling capacity| (1)| kW| 116,3| 144,7| 175,8
Total power input| (1)| kW| 42,00| 52,20| 63,20
EER| (1)| kW/kW| 2,769| 2,772| 2,782
ESEER| (1)| kW/kW| 3,390| 3,470| 3,370
COOLING ONLY (EN14511 VALUE)
Cooling capacity| (1)(2)| kW| 116,0| 144,3| 175,3
EER| (1)(2)| kW/kW| 2,740| 2,740| 2,750
ESEER| (1)(2)| kW/kW| 3,310| 3,370| 3,280
Cooling energy class| | | C| C| C
HEATING ONLY (GROSS| VALUE)| | | |
Total heating capacity| (3)| kW| 134,9| 171,0| 204,8
Total power input| (3)| kW| 39,60| 48,10| 58,90
COP| (3)| kW/kW| 3,407| 3,555| 3,477
HEATING ONLY (EN14511 VALUE)
Total heating capacity| (3)(2)| kW| 135,4| 171,6| 205,5
COP| (3)(2)| kW/kW| 3,380| 3,520| 3,450
Cooling energy class| A| A| A
ENERGY EFFICIENCY
SEASONAL EFFICIENCY IN COOLING (Reg. EU 2016/2281)
Ambient refrigeration
Prated,c| (11)| kW| – –
–
SEER| (11)(12)| | – –
–
Performance hs| (11)(13)| %| – –
–
SEASONAL EFFICIENCY IN HEATING (Reg. EU 813/2013)
PDesign| (4)| kW| 92,6| 117| 139
SCOP| (4)(14)| | 3,23| 3,40| 3,29
Performance hs| (4)(15)| %| 126| 133| 129
Seasonal efficiency class| (16)| | –| –| –
PDesign| (5)| kW| 98,9| 126| 148
SCOP| (5)(14)| | 3,02| 3,19| 3,08
Performance hs| (5)(15)| %| 118| 125| 120
Seasonal efficiency class| (17)| | –| –| –
EXCHANGERS
HEAT EXCHANGER USER SIDE IN REFRIGERATION
Water flow| (1)| l/s| 5,562| 6,920| 8,407
Pressure drop| (1)| kPa| 18,5| 20,1| 22,6
HEAT EXCHANGER USER SIDE IN HEATING
Water flow| (3)| l/s| 6,512| 8,254| 9,886
Pressure drop| (3)| kPa| 25,4| 28,6| 31,3
REFRIGERANT CIRCUIT|
Compressors nr.| | N°| 4| 4| 4
No. Circuits| | N°| 2| 2| 2
Refrigerant charge| | kg| 70,0| 110| 110
NOISE LEVEL
Sound power level in cooling| (6)(7)| dB(A)| 86| 86| 87
Sound power level in heating| (6)(8)| dB(A)| 88| 88| 89
Sound Pressure| (9)| dB(A)| 67| 66| 67
SIZE AND WEIGHT
A| (10)| mm| 3110| 4110| 4110
B| (10)| mm| 2220| 2220| 2220
H| (10)| mm| 2150| 2150| 2150
Operating weight| (10)| kg| 1960| 2410| 2540
“ BY FAR THE BEST PROOF IS EXPERIENCE ”
Sir Francis Bacon British philosopher (1561 – 1626)
IKOS OLIVIA HOTEL
2015 Geraniin – Chalcidice – Greece
Application: Hotel and resorts
Plant type: Hydronic System
Cooling capacity: 1718 kW
Heating capacity: 2682 kW
Installed machines:
9x AW-HT LN/CAE 0302,
2x NECS-N/CA,
1x NX-N T/LN CA,
1x FOCS2-W/CAE/H
Project
This 5-star resort rises on white sands and refreshing waters of the Aegean.
Ikos Olivia boasts spacious rooms, suites and bungalows with flowing green
gardens, several swimming pools and a Spa.
Challenge
Ensuring maximum comfort for all guests and making their holidays
unforgettable both inside their rooms as well as in common areas like swimming
pools and the spa, was a key challenge. For owners, energy efficiency and
reliability were also fundamental, in order to reduce running and maintenance
costs and to contribute to an outstanding business performance of the hotel.
Solution
To perfectly satisfy the hot water request for swimming pools and for domestic
hot water, the heating system is based on 9 air source heat pumps AW HT by
Climaveneta. These units in fact can supply hot water up to 65°C.
Climaveneta branded heat pumps are ready-to-be-installed units. Neither probes
nor connection pipes to wells are needed, thus making the installation
activities onsite quick and easy.
Every project is characterized by different needs and system specifications
for various climates. All these projects share high energy efficiency, maximum
integration, and total reliability resulting from the Climaveneta brand
experience.
Villaggio Valentino
2018 Castellaneta Marina – Italy Hotel and resorts
Plant type: Hydronic System
Cooling capacity: 393 kW
Heating capacity: 444 kW
Installed machines: 2x AWR-HT/D/CA-E 0202, 3x AWR-HT/D/CA-E 0302
Samhi Hotels Bangalore 2013 Bangalore – India
Hotel and resorts
Plant type: Hydronic System
Cooling capacity: 87.3 kW
Heating capacity: 116.7 kW
Installed machines: 1x AWR-HT/CA-E 0302
Vertical Wind Tunnel 2017 Milan – Italy Sport structures
Plant type: Hydronic System
Cooling capacity: 90 kW
Heating capacity: 120 kW
Installed machines: 1x AWR-HT LN CA E 0302, 1x AW HT 0061
for a greener tomorrow
Eco Changes is the Mitsubishi Electric Group’s environmental statement, and
expresses the Group’s stance on environmental management. Through a wide range
of businesses, we are helping contribute to the realization of a sustainable
society.
MITSUBISHI ELECTRIC HYDRONICS & IT COOLING SYSTEMS S.p.A.
Head Office: Via Cadet Cephalonia 1 – 36061 Bassano del Grappa (VI) – Italy
Tel (+39) 0424 509 500 –
Fax (+39) 0424 509 509
www.climaveneta.com
www.melcohit.com