IMPORTANT: Read carefully before installing fixture.
Retain for future reference.
WARNING
Risk of Electrical Shock! Disconnect power at fuse or circuit breaker before installing or servicing.
WARNING
Risk of Fire! For Non-IC fixtures do not install insulation within 3 inches (76 mm) of any part of the luminaire fixture or in a way that may entrap heat.
WARNING
Installation and servicing to be performed only by qualified personnel. If not qualified, consult an electrician.
WARNING
Do not energize the LED Engine until the protective cover has been removed with the optic and lower trim properly installed. Do not touch the surface of the LED as it may damage the light engine.
Note:   This fixture should be supported by main runners or other structure that is capable of supporting fixture weight of 35 Ibs.
SAFETY: When using electrical equipment, basic safety precautions should always be followed, including the following:

  1. This unit is for recessed mounting only. Do not use in hazardous locations nor near gas or electric heaters.
  2. Do not use this equipment for other than the intended use.
  3. Install only in accordance with National Electrical Code and local regulatory agencies’ requirements.

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED -
Fig

| Aperture| Ceiling Cutout| Fixture Height| Lumens| Ceiling Type
---|---|---|---|---|---
LDA4| 4-7/16″| 5-1/8″| 9″| 900-1800| IC or Non-IC
2800| Non-IC Marked Spacing
Center to Center of Adjacent Luminaires: 36″
Center of Luminaire to Side of Building Member:
18″ Minimum Overhead Clearance: 1/2″ Above Fixture
LDA6| 5-11/16″| 6-3/8″| 1000-2000| IC or Non-IC
3000-6500| Non-IC Marked Spacing Center to Center of Adjacent
Luminaires: 36″
Center of Luminaire to Side of Building Member: 18″ Minimum Overhead Clearance: 1/2″ Above Fixture

INSTALLATION

Rough-In Section

  1. Fixture Attachment Method: Install fixture into ceiling cavity using 1/2˝ electrical conduit. Use 3/4˝ channel, 1-1/2˝ channel, 1/8˝ x 1/2˝ bar stock, or T-bar fasteners as mounting rails (furnished by others) by inserting them through hanger brackets at both sides.
  2. Adjust hanger adjustment screws so bottom of plaster ring is flush with finished ceiling line. Hanger bracket is reversible for total adjustment of 5˝ (Figure 2).
  3. Remove one of the junction box covers. Connect supply lead wires to lead wires of driver as per Wiring Diagram and in accordance with your local electrical code(s) or N.E.C.

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED - Fig
1 Rotation and Tilt Adjustment

  1. Loosen Angle Adjustment Thumbnuts (2) through Plaster Ground opening but do not remove (Figure 3).

  2. Pull Angle adjustment plunger to change tilt and release for rough adjustment in 10 degree increments. Angle alignment marks provided for reference (Figure 3).
    Note:
    For Lensed Wall Wash trims adjust angle to 30 degrees.

  3. Twist angle adjustment plunger counterclockwise while pulled out to lock in place. For full adjustment between 0 degrees and max tilt.

  4. Tighten Angle Adjustment Thumbnuts (2) to lock in angle.

  5. Reach through Plaster Ground opening, loosen Rotation Thumb Screw, rotate to desired direction and re tighten thumb screw to lock in place (Figure 4).

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED - Fig
2Portfolio IB520144ML
LDA4 LDA6 Commercial Recessed Adjustable LED - Fig 3

Description Catalog Number For Use With
OPTIC, PORTFOLIO LED ADJ 20DEG SPOT HL LARH20SP LDA6A-45, -55, -65
OPTIC, PORTFOLIO LED ADJ 30DEG NRW FLD HL LARH30NF LDA6A-45, -55, -65
OPTIC, PORTFOLIO LED ADJ 40DEG FLOOD HL LARH40FL LDA6A-45, -55, -65
OPTIC, PORTFOLIO LED ADJ, 15DEG SPOT LAR15SP LDA4A-09, -13, -18, -28
OPTIC, PORTFOLIO LED ADJ, 25DEG NRW FLD LAR25NF LDA4A-09, -13, -18, -28
OPTIC, PORTFOLIO LED ADJ, 35DEG FLOOD LAR35FL LDA4A-09, -13, -18, -28;

LDA6A-10, -15, -20, -30
OPTIC, PORTFOLIO LED ADJ 15DEG SPOT LL| LARL15SP| LDA6A-10, -15, -20, -30
OPTIC, PORTFOLIO LED ADJ 20DEG NR FLD LL| LARL20NF| LDA6A-10, -15, -20, -30

Optic Installation

  1. Remove Optic from protective packaging and remove rubber Media Holder (Optional) ring to install any optional Media (Figure 5). To re-attach Media Holder to Reflector start with Alignment Arrow at Alignment Notch and work around flange. For 1 piece of Media (optional) place the Reflector in the upper position (Figure 6 & 7) and for 2 pieces of Media (optional) place the Reflector in the lower position (Figure 6 & 7).
  2. When using directional media such as the Linear Spread Lens (optional) align the lens grooves with Alignment Arrow on Media Holder (Figure 8).
  3. Remove protective LED Cover (Figure 9) from Housing by rotating counter clockwise.
  4. Insert Optic Assembly into housing Flange first while holding the metal Reflector and not the rubber Media Holder. Place the Flange on the white Reflector Mounting Clip and press firmly then rotate clockwise until the 3 latches snap into place (Figure 10). Ensure Alignment Arrows on Media Holder and Reflector Mounting Clip line up for optional directional media (Figure 11).

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED - Fig
4Portfolio IB520144ML
LDA4 LDA6 Commercial Recessed Adjustable LED - Fig 5Portfolio IB520144ML LDA4 LDA6 Commercial Recessed
Adjustable LED - Fig 6![Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED

  • Fig 7](https://manuals.plus/wp-content/uploads/2023/08/Portfolio-IB520144ML- LDA4-LDA6-Commercial-Recessed-Adjustable-LED-Fig-7.png) Trim Installation

    1. Remove Trim from protective packaging and place Trim Ring (optional) over reflector before installation.
    2. Install Trim Assembly by inserting Torsion Springs into Spring Receivers inside housing (Figure 12).
    3. For angle cut trims, place tall side of reflector next to Rotation Adjustment Thumb Screw.

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED - Fig
8

Cleaning

To Clean Trims:

  1. Gently wipe with soft, clean, dry lint free cloth to remove dust.
  2. Wipe with mild detergent solution on a soft, clean cloth to remove fingerprints and stains.
  3. Rinse with clean water and dry with soft, clean, dry lint free cloth.

Electrical Connection

CAUTION
Make certain no bare wires are exposed outside of wire nut connectors.

  1. Provide electrical service according to the “National Electrical Code” or your local electrical code to the junction box (located on the plaster frame). Supply wire insulation must be rated for at least 90°C. The junction box is rated for a maximum of 4 No. 12 AWG Branch Circuit conductors that must also be suitable for at least 90°C.
  2. Remove junction box cover (Figure 13).
  3. Remove appropriate round pry out and connect conduit to junction box with proper connector (not included).
  4. Connect supply lead wires to junction box lead wires (line, neutral and ground) in the fixture using properly sized wire nuts. Be careful not to leave any bare conductors outside of the wire nut connectors.
  5. Connect white wire to neutral, black wire to supply line, and ground (from electrical service) on the supply side to the bare copper wire in the junction box. See wiring diagrams for low voltage wire connections. Place all excess wiring and connections into the junction box and replace the cover.

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED - Fig
9

Driver Replacement

CAUTION
To avoid possible electrical shock, be sure that the power is turned off before installing or servicing this fixture The driver should be replaced by a qualified electrician.
The driver may be replaced either from below or above the ceiling.

  1. If below the ceiling remove trim assembly from housing then loosen Thumb Screw, rotate Access Plate clockwise slightly and pull in to remove (Figure 14).
  2. Press Junction Box Latch to remove Driver Assembly (Figure 15).
  3. Disconnect wiring to Driver Assembly by removing wire nuts.
  4. Discard old Driver Assembly.
  5. Connect new driver leads with wire nuts.
  6. Reattach new Driver Assembly and latch securely.

Portfolio IB520144ML LDA4 LDA6 Commercial Recessed Adjustable LED - Fig
10Portfolio IB520144ML
LDA4 LDA6 Commercial Recessed Adjustable LED - Fig 11 Constructions built before Jan 2022 may have gray wire for 0-10 dimming control present. In these cases, the installer will label the gray building wire as a 0-10 dimming wire and connect to our product’s pink 0-10V dimming control wire. Reference NFPA70 (2020 NEC), section 410.69.
Dimming
The Portfolio LDA4
D010TE/LDA6D010TE Series can be dimmed with many standard electronic low voltage dimmers and 0-10V DC dimming controls. The Portfolio LDA4DL3/LDA6DL3 Series can be dimmed with Lutron 3-wire fluorescent and EcoSystem® digital controls. The Portfolio LDA4DLT/LDA6DLT Series can be dimmed with Lutron 2-wire forward phase controls. The Portfolio LDA4D010TR/LDA6D010TR Series can be dimmed with many standard 120V incandescent dimmers, electronic low voltage dimmers and 0-10V DC dimming controls. The Portfolio LDA4D5LT/LDA6D5LT Series can be dimmed with Fifth Light and DALI compatible controls. The Portfolio LDA4DMX/LDA6DMX Series can be dimmed with DMX compatible controls. The Portfolio LDA4DE010/LDA6DE010 and LDA6D010 Series can be dimmed with 0-10V DC dimming controls but are NOT to be dimmed using line voltage dimmers. To be assured of the latest information regarding luminaire and dimmer compatibility, please reference the Portfolio LED website: www.portfolio-lighting.com.

Warranties and Limitation of Liability

Please refer to www.cooperlighting.com/legal for our terms and conditions.
FCC Statement
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications.
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense.

  • Reorient or relocate the receiving antenna.

  • Increase the separation between the equipment and receiver.

  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.

  • Consult the dealer or an experienced radio/TV technician for help.

  • This device complies with Part 15 of the FCC Rules.
    Operation is subject to the following two conditions:
    (1) this device may not cause harmful interference, and
    (2) this device must accept any interference received, including interference that may cause undesired operation.

  • This device complies with ISED ICES Standard Canada ICES-005 (A) / NMB-005 (A) or ICES-005 (B) / NMB-005 (B) depending on driver selected.

Any changes or modifications to this unit not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.

Cooper Lighting Solutions 1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
Canada Sales
5925 McLaughlin Road Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2021 Cooper Lighting Solutions All Rights Reserved
Printed in USA
Imprimé aux États-Unis Impreso en los EE. UU.
Publication No. IB520144ML
October 26, 2021
Cooper Lighting Solutions is a registered trademark.