Portfolio Lighting LDSQA4 Adjustable LED Instruction Manual

June 13, 2024
Portfolio Lighting

Portfolio Lighting LDSQA4 Adjustable LED

Portfolio Lighting LDSQA4 Adjustable LED

SAFETY WARNING SYMBOLS

IMPORTANT: Read carefully before installing fixture.
Retain for future reference.

WARNING
Risk of Electrical Shock! Disconnect power at fuse or circuit breaker before installing or servicing.

WARNING
Risk of Fire! For Non-IC fixtures do not install insulation within 3 inches (76 mm) of any part of the luminaire fixture or in a way that may entrap heat.

WARNING
Installation and servicing to be performed only by qualified personnel. If not qualified, consult an electrician.

WARNING
Do not energize the LED Engine until the protective cover has been removed with the optic and lower trim properly installed. Do not touch the surface of the LED as it may damage the light engine.

Note: This fixture should be supported by main runners or other structure that is capable of supporting fixture weight of 35 Ibs.

SAFETY: When using electrical equipment, basic safety precautions should always be followed, including the following:

  1. This unit is for recessed mounting only. Do not use in hazardous locations nor near gas or electric heaters.
  2. Do not use this equipment for other than the intended use.
  3. Install only in accordance with National Electrical Code and local regulatory agencies’ requirements.

Safety

| Aperture| Ceiling Cutout| Fixture Height| Lumens| Ceiling Type
---|---|---|---|---|---
LDSQA4| 5-1/4″ x 5-1/4″| 5-1/8″ x 5-1/8″| 9″| 900-1800| IC or Non-IC
2800| Non-IC

INSTALLATION

Rough-In Section
  1. Fixture Attachment Method: Install fixture into ceiling cavity using 1/2˝ electrical conduit. Use 3/4˝ channel, 1-1/2˝ channel, 1/8˝ x 1/2˝ bar stock, or T-bar fasteners as mounting rails (furnished by others) by inserting them through hanger brackets at both sides.
  2. Adjust hanger adjustment screws so bottom of collar is flush with finished ceiling line. Hanger bracket is reversible for total adjustment of 5˝ (Figure 2).
  3. Remove one of the junction box covers. Connect supply lead wires to lead wires of driver as per Wiring Diagram and in accordance with your local electrical code(s) or N.E.C.
    Rough-In Section
Rotation and Tilt Adjustment
  1. Loosen Angle Adjustment Thumbnuts (2) through collar opening but do not remove (Figure 3).

  2. Pull Angle adjustment plunger to change tilt and release for rough adjustment in 10 degree increments. Angle alignment marks provided for reference (Figure 3).
    Rotation and Tilt Adjustment

  3. Twist angle adjustment plunger counterclockwise while  pulled out to lock in place. For full adjustment between0 degrees and max tilt.

  4. Tighten Angle Adjustment Thumbnuts (2) to lock in angle.

  5. If adjustment of the rotational alignment of the collar is desired, loosen the collar locking thumb nut. Rotate the collar to the desired position and then tighten the collar locking thumb nut (Figure 4)

  6. Reach through collar opening, loosen Rotation Thumb Screw, rotate to desired direction and re tighten thumb screw to lock in place (Figure 4).
    Rotation and Tilt Adjustment

Optic Installation
  1. Remove Optic from protective packaging and remove rubber Media Holder (Optional) ring to install any optional Media (Figure 5).
    Optic Installation

  2. To re-attach Media Holder to Reflector start with Alignment Arrow at Alignment Notch and work around flange. For 1 piece of Media (optional) place the Reflector in the upper position (Figure 6 & 7) and for 2 pieces of Media (optional) place the Reflector in the lower position (Figure 6 & 7).
    Optic Installation

  3. When using directional media such as the Linear Spread Lens (optional) align the lens grooves with Alignment Arrow on Media Holder (Figure 8).
    Optic Installation

  4. Remove protective LED Cover (Figure 9) from Housing by rotating counter clockwise.
    Optic Installation

  5. Insert Optic Assembly into housing Flange first while holding the metal Reflector and not the rubber Media Holder. Place the Flange on the white Reflector Mounting Clip and press firmly then rotate clockwise until the 3 latches snap into place (Figure 10).
    Optic Installation

  6. Ensure Alignment Arrows on Media Holder and Reflector Mounting Clip line up for optional directional media (Figure 11).
    Optic Installation

Trim Installation

  1. Remove Trim from protective packaging and place Trim Square (optional) over reflector before installation.

  2. Install Trim Assembly by inserting Mousetrap Springs into Square Aperture inside collar (Figure 12).
    Trim Installation

  3. For angle cut trims, place tall side of reflector on the same side as the Rotation Adjustment Thumb Screw.

Cleaning

To Clean Trims:

  1. Gently wipe with soft, clean, dry lint free cloth to remove dust.
  2. Wipe with mild detergent solution on a soft, clean cloth to remove fingerprints and stains.
  3. Rinse with clean water and dry with soft, clean, dry lint free cloth.
Electrical Connection

CAUTION

Make certain no bare wires are exposed outside of wire nut connectors.

  1. Provide electrical service according to the “National Electrical Code” or your local electrical code to the junction box (located on the plaster frame). Supply wire insulation must be rated for at least 90°C. The junction box is rated for a maximum of 4 No. 12 AWG Branch Circuit conductors that must also be suitable for at least 90°C.

  2. Remove junction box cover (Figure 13).
    Electrical Connection

  3. Remove appropriate round pry out and connect conduit to junction box with proper connector (not included).

  4. Connect supply lead wires to junction box lead wires (line, neutral and ground) in the fixture using properly sized wire nuts. Be careful not to leave any bare conductors outside of the wire nut connectors.

  5. . Connect white wire to neutral, black wire to supply line, and ground (from electrical service) on the supply side to the bare copper wire in the junction box. See wiring diagrams for low voltage wire connections. Place all excess wiring and connections into the junction box and replace the cove

Driver Replacement

CAUTION

To avoid possible electrical shock, be sure that the power is turned off before installing or servicing this fixture
The driver should be replaced by a qualified electrician.
The driver may be replaced either from below or above the ceiling.

  1. If below the ceiling remove trim assembly from housing then loosen Thumb Screw, rotate Access Plate clockwise slightly and pull in to remove (Figure 14).
    Driver Replacement

  2. Push Junction Box Latch outward to remove Driver Assembly (Figure 15).
    Driver Replacement

  3. Disconnect wiring to Driver Assembly by removing wire nuts.

  4. Discard old Driver Assembly.

  5. Connect new driver leads with wire nuts.

  6. Reattach new Driver Assembly and latch securely.

Wiring Diagrams
  1. For D010TE
    Wiring Diagrams

  2. For D010TR
    Wiring Diagrams

  3. For D5L
    Wiring Diagrams

  4. For DE010

  5. For DL3
    Wiring Diagrams

  6. For DLT
    Wiring Diagrams

  7. For DMX
    Wiring Diagrams

Dimming

The Portfolio LDSQA4D010TE Series can be dimmed with many standard electronic low voltage dimmers and 0-10V DC dimming controls. The Portfolio LDSQA4DL3 Series canbe dimmed with Lutron 3-wire fluorescent and EcoSystem®  digital controls. The Portfolio LDSQA4DLT Series can be dimmed with Lutron 2-wire forward phase controls. The Portfolio LDSQA4D010TR Series can be dimmed with many standard 120V incandescent dimmers, electronic low voltage dimmers and 0-10V DC dimming controls. The Portfolio LDSQA4D5LT Series can be dimmed with Fifth Light and DALI compatible controls. The Portfolio LDSQA4DMX Series can be dimmed with DMX compatible controls. The Portfolio LDSQA4*DE010 Series can be dimmed with 0-10V DC dimming controls but are NOT to be dimmed using line voltage dimmers. To be assured of the latest information regarding luminaire and dimmer compatibility, please reference the Portfolio LED website: www .portfolio-lighting.com.

Warranties and Limitation of Liability

Cooper Lighting Solutions provides a 5-year limited warranty on this LED lighting product. Refer to the complete warranty terms & conditions of sale at www.cooperlighting.com.

CUSTOMER SERVICE

Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
© 2020 Cooper Lighting Solutions
All Rights Reserved
Printed in USA
Imprimé aux États-Unis
Impreso en los EE. UU.
Publication No. IL520003EN November 3, 2015

Logo

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals