Kilsen CR255 Electronic Delay Control Unit Installation Guide
- June 12, 2024
- Kilsen
Table of Contents
CR255 Electronic Delay Control Unit Installation
Sheet
CR255 Electronic Delay Control Unit
Installation Sheet
Description
The CR255 Electronic Delay Control Unit is designed for use with double-leaf
fire doors.
Figures
Figure 1: Wiring
- Fire panel
- 24 VDC supply line
- Normally closed relay inpu(4) Immediate release electromagnet
- Delayed release electromagnet
- CR255 module
Installation
Caution: This product must be installed and maintained by qualified
personnel adhering to EN 54-14 and all local or national installation
requirements and any other applicable regulations.
Install the unit as close to the fire doors as possible, at a maximum distance
of 200 m from the power supply.
Wiring
Connect the CR255 as shown in Figure 1.
Maintenance
Basic maintenance consists of a yearly inspection. Do not modify internal wiring or circuitry.
Specifications
Operating voltage | 20 to 27 VDC |
---|---|
Maximum current | 0.5 A |
Delay time | 5 seconds |
Wire size (cross-sectional area) | 1.5 mm2 |
Maximum wire length | 200 m |
Operating environment Operating temperature Storage temperature Relative
humidity| —10 to +60°C —20 to +70°C 0 to 95% noncondensing
Dimensions (W x H x D)| 40 x 35 x 12 mm
Weight| 24 g
Regulatory information
This section provides a summary on the declared performance according to the
Construction Products Regulation
(EU) 305/2011 and Delegated Regulations (EU) 157/2014 and (EU) 574/2014.
For detailed information, see the product Declaration of Performance
(available at firesecurityproducts.com).
EU compliance | **** |
---|---|
Certification body | 1134 |
Manufacturer | Carrier Safety System (Hebei) Co. Ltd., 80 Changjiang East Road, |
QETDZ, Qinhuangdao 066004, Hebei, China.
Authorized EU manufacturing representative: Carrier Fire & Security B.V.,
Kelvinstraat 7, 6003 DH Weed, Netherlands.
Year of first CE marking| 12
Declaration of Performance number| 360-5151-0199
EN 54| EN 54-18:2005/AC:2007
Product identification| CR255
Intended use| See the product Declaration of Performance
Declared performance/s| See the product Declaration of Performance
****| 2012/19/EU (WEEE Directive): Products marked with this symbol cannot be
disposed of as unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon the purchase of
equivalent new equipment, or dispose of it at designated collection points.
For more information see: recyclethis.info.
Contact information
For contact information, visit
firesecurityproducts.com.
Product warnings and disclaimers
THESE PRODUCTS ARE INTENDED FOR SALE TO AND INSTALLATION BY QUALIFIED
PROFESSIONALS.
CARRIER FIRE & SECURITY B.V. CANNOT PROVIDE ANY ASSURANCE THAT ANY PERSO OR
ENTITY BUYING ITS PRODUCTS, INCLUDING ANY “AUTHORIZED DEALER” OR “AUTHORIZED
RESELLER”, IS ROPERLY TRAINED OR EXPERIENCED TO CORRECTLY INSTALL FIRE AND
SECURITY RELATED PRODUCTS.
For more information on warranty disclaimers and product safety information,
please check
https://firesecurityproducts.com/policy/product-warning/ or scan the QR
code:
https://www.utcfssecurityproducts.eu/productwarning/ P/N 10-4109-501-3CR2-07 • ISS 21NOV22
Documents / Resources
|
Kilsen CR255 Electronic Delay Control
Unit
[pdf] Installation Guide
CR255 Electronic Delay Control Unit, CR255, Electronic Delay Control Unit,
Delay Control Unit, Control Unit, Unit
---|---
References
- Home - Fire Security Products
- HOME
- HOME
- Home - Fire Security Products
- Product warnings and disclaimers - Fire Security Products
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>