Kilsen KAL455 Manual Call Point Installation Guide

June 10, 2024
Kilsen

KAL455 Manual Call Point
Installation Guide

KAL455 Manual Call Point

Kilsen KAL455 Manual Call Point fig 1 Kilsen
KAL455 Manual Call Point fig 2

Installation Sheet

Description

This document includes installation information for UTC Fire &Security KAL455 manual call points. These manual call pointsare designed for use in UTC Fire & Security Kilsen analogueaddressable fire alarm systems and include models for indoorand outdoor use.

Installation

Caution:

This product must be installed by qualified personneladhering to the CEN/TS 54-14 standard and any otherapplicable local authority laws.

Electrical connections

Connect to the KAL455 connection block (Figure 2) as follows:

  1. Line in (positive)

  2. Line out (positive)

  3. Line in (negative)

  4. Line out (negative)

Addressing

Use the DIP switch (Figure 1) to allocate a device addressfrom 128 to 252 (see page 9).

Maintenance

Basic maintenance consists of a yearly inspection. Do notmodify internal wiring or circuitry.

Specifications

Voltage 22 to 35 VDC

Current
Standby Alarm| max. 250 tIA
max. 2.5 mA
Cable size
Minimum Maximum| 0.8 mm2
2.5 mm2
IP rating
KAL455, KAL455-18 KAL455E, KAL455E-18| IP24D IP67
Operating environment Operating temperature
Storage temperature Relative humidity| -10°C to +70°C -20°C to +70°C 10% to 95% noncondensing
Dimensions (W x H x D)
KAL455, KAL455-18 KAL455E, KAL455E-18| 89 x 93 x 27.5 mm [1] 97.5 x 93 x 27.5 mm [1]
Weight| 187 g

Weight 187 g [1] Excluding surface mount.

Regulatory information

Manufacturer| KAC Alarm Company Ltd. KAC House. Thornhill Road, North Moons Moat. Redditch. Worcestershire, 898 9ND, England Authorized EU manufacturing representative: UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert. Netherlands
---|---
Year of manufacture| The first two digits of the DATE MFG number (located on the product identification label) are the year of manufacture.
Certification| ****
CPD certificates
KAL455. KAL455-18
KAL455E. KAL455E-18| 0832-CPD-0750
0832-CPD-0752
EN 54| EN 54-11 Type A
|  2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment. or dispose of it at designated collection points. For more information see: www.recyclethis.info.

Contact information

For contact information, see www.utcfssecurityproducts.eu.

Kilsen KAL455 Manual Call Point fig 3

P/N 20-8030-501-1100-09
ISS 03NOV21
D1113-4