Kilsen PG700N Device Programmer Unit User Guide

June 3, 2024
Kilsen

Kilsen PG700N Device Programmer Unit

Description

  • The PG700N Device Programmer Unit has the following capabilities:
  • To assign or modify the address for the KL700A series addressable detectors
  • To calibrate the replacement optical chamber for the KL731A Addressable Optical Smoke Detectors
  • To calibrate the KL731 and KL731B conventional optical detectors

The range of addresses is from 1 through 125. Models are shown in Table 1 below.

Table 1: Compatible devices

Model Description
KL731A Addressable Optical Smoke Detector
KL731AB Addressable Optical Smoke Detector (Black)
KL735A Addressable Dual (Optical/Heat) Detector
KL731 Conventional Optical Detector
KL731B Conventional Optical Detector (Black)

Operation

Button functionality of the device is described in Table 2.

Table 2: Button functionalityKilsen-PG700N-Device-Programmer-Unit-
FIG-2

There are six program mode options from P1 to P6, including a setup option, descibed in Table 3.

Table 3: Program modes

Program Function
P1 Auto address and calibrate. Automatically assigns the allocated address to

the mounted detector (refer to the screen text for P1 in Table 4). When a detector is removed, the unit automatically changes to the next address. This program also calibrates.
P2| Assign a new address and calibrate. Enter the new address and calibrate the detector.

To operate the unit:

  1. Press the power on button for three seconds.
  2. Attach the detector to the unit head and turn it clockwise until the detector clicks into place.
  3.  Select the required function from the program mode options shown in Table 3.

The unit displays the detector address, calibration, or diagnostic state in the screen text, as described in Table 4.

The device descriptions are:

  • OD Optical Detector
  • HD Heat Detector
  • ID Ionisation Detector
  • OH Optical Heat (Multi-Sensor) Detector

Table 4: Program mode screensKilsen-PG700N-Device-Programmer-Unit-
FIG-3

Calibration error codes, meanings, and possible solutions are shown in Table 5.

Table 5: Calibration error codes

Code Cause and solution
ERROR-1 The optical chamber could not be calibrated. If the error persists,

replace the chamber. If the detector still does not calibrate, replace the detector.

Batteries

The PG700N uses two 9 V PP3 batteries. To check the battery voltage select the Setup program mode (the battery voltage indicator option). Batteries must be replaced when their voltage level drops below 12V. The screen displays [Low Battery] when the batteries need to be replaced.

Regulatory information

Certification Manufacturer

UTC Fire & Security South Africa (Pty) Ltd. 555 Voortrekker Road, Maitland, Cape Town 7405, PO Box 181 Maitland, South Africa Authorized EU manufacturing representative: UTC Fire & Security B.V. Kelvinstraat 7, 6003 DH Weert, Netherlands 2002/96/EC (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For proper recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points. For more information see: www.recyclethis.info.
2006/66/EC (battery directive): This product contains a battery that cannot be disposed of as unsorted municipal waste in the European Union. See the product documentation for specific battery information. The battery is marked with this symbol, which may include lettering to indicate cadmium (Cd), lead (Pb), or mercury (Hg). For proper recycling, return the battery to your supplier or to a designated collection point. For more information see: www.recyclethis.info.

Contact information
For contact information see our Web site: www.utcfireandsecurity.com

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals