Danfoss VZH088-117-170 Compressor Instructions

June 12, 2024
Danfoss

Danfoss VZH088-117-170 Compressor

Danfoss VZH088-117-170 Compressor

Product versions

Product versions

Product description

A: Model number
B: Serial number
C: Refrigerant
D: Supply voltage to frequency converter
E: Housing service pressure
F: Factory charged lubricant
G: Compressor frequency Max Rated Current (VZH088/117/170CGN)
Compressor frequency Max Rated Current (VZH088/117/170*M)
Compressor frequency & Max Must Trip Current (VZH088/117/170
N*)
Compressor frequency & Max Operating Current (VZH088/117/170**M)

Product description

Operating maps

VZH088/117/170 A & B Operating map – R410A 

Operating maps

The compressor must only be used for its designed purpose(s) and within its scope of application (refer to «operating limits»). Consult Application guidelines and datasheet available from http://cc.danfoss.com

Under all circumstances, the EN378 (or other applicable local safety regulation) requirements must be fulfilled.

The compressor is delivered under nitrogen gas pressure (between 0.3 and 0.7 bar) and hence cannot be connected as is; refer to the «assembly» section for further details.

The compressor must be handled with caution in the vertical position (maximum offset from the vertical : 15°)

Oil injection control assembly

Put the clip-on coil (1) with the gasket (2) over the valve body (3) on the compressor

Oil injection control assembly 

Attach the connector (4) to the coil using the delivered accessories (5) and (6).

Oil injection control assembly 

Wire the connector as indicated and plug it to the CDS relay 1 location.

Oil injection control assembly 

Oil injection control dismantling

Remove the clip-on coil by using a screwdriver.

Oil injection control dismantling 

Oil level sensor assembly

Install the screw-in optical part on oil level switch port. (Factory preset for manifold version VZH compressor.)

Oil level sensor assembly 

Install the electrical part on optical part. Make sure the cable outlet downside vertically.

Oil level sensor assembly 

VZH088/117/ 170 C Operating Map – R410A/R452B/R454B

VZH088/117/ 170 C Operating Map - R410A/R452B/R454B

For VZH088/117 with R410A/R452B/R454B and VZH170 with R410A, the solid line envelope is valid for a suction superheat within 5K at nominal voltage. Higher suction superheat may lead to discharge temperatures above 135°;
For superheat between 5K and 11K, this top left envelope might be reduced by condensing temperature of 1°C or 2°C in order to keep discharge T° below 135°C.
For superheat above 11K, the envelop will further be reduced based on 135°C discharge temperature restriction.

For VZH170 with R452B/R454B, The solid line envelope is valid for a suction superheat within 5K at nominal voltage. Higher suction superheat may lead to discharge temperatures above 150°;
For superheat between 5K and 11K, this top left envelope might be reduced by condensing temperature of 1°C or 2°C in order to keep discharge T° below 150°C.
For superheat above 11K, the envelop will further be reduced based on 150°C discharge temperature restriction.

Basic connections

  • Depending on the frequency converter version, the physical position of individual connectors may differ from below diagram.
  • Always make sure that the compressor terminals T1, T2, T3 are connected to the frequency converter terminals 96, 97, 98 respectively.
  • The compressor motor cable must be shielded and the armoured part must be connected to ground on both cable ends; at the side of the compressor and at the side of the frequency converter.
  • Use an EMC cable gland for cable installation and perfect grounding; The metallic terminal box of the compressor has a paint-free surface around the connection hole for better conductivity.
  • A low pressure safety switch is mandatory to avoid compressor vacuum operation.
  • At start-up, verify that the compressor rotates in the right direction and pumps.
    Basic connections
POS Description Open loop Process loop
91, 92, 93: 3 Phase mains input X X
95: Earth X X
39, 42 Analogue output
50: Analogue output
53: PLC+ (0 to 10 V) X
54: Sensor – X
55: PLC- X
12: HP/LP switch X X
12: External On/Off (NO) X X
13: Factory bridged to 37 X X
13: Sensor + X
18: External On/Off (NO) X X
19: Digital input
27: HP/LP switch (NC) / safety devices X X
29: Digital input/output
32, 33 Digital input
20: Digital input Common
37: Factory bridged to 13 X X
98: To compressor terminal T3 X X
97: To compressor terminal T2 X X
96: To compressor terminal T1 X X
99: To compressor earth connection X X
02, 01: Relay 1 to oil solenoid valve X X
06, 05, 04: Relay 2
69, 68: RS485 Bus
61: RS485 Bus Common

-: Optional connection X: Mandatory connection

The CDS303 frequency converter is factory preset with parameters for the open loop control principle. The process loop control principle can be selected by changing parameters in the «Quick menu».

Open loop: 0 – 10 V control, Frequency converter in slave mode
Process loop: 4 – 20 mA control, Frequency converter under own PID controller

Check carefully for compatibility between compressor model and variable speed drive.
Basic connections refer to application guideline or contact with Danfoss regional technical support.

Compressor model Refrigerant Drive power Drive model
VZH088-G R410A 15kW CDS303
VZH117-G R410A 18.5kW CDS303
VZH170-G R410A 22kW CDS303
VZH088-J R410A/R452B/R454B 15kW CDS303
VZH117-J R410A/R452B/R454B 18.5kW CDS303
VZH170-J R410A/R452B/R454B 22kW CDS303
VZH088-H R410A/R452B/R454B 18.5kW CDS303
VZH117-H R410A/R452B/R454B 30kW CDS303
VZH170-H R410A/R452B/R454B 30kW CDS303
VZH088-G R410A/R452B/R454B 18.5kW CDS803
VZH117-G R410A/R452B/R454B 22kW CDS803
VZH170-G R410A/R452B/R454B 30kW CDS803

Electrical connections / Wiring for Oil level sensor

See at the correct diagram corresponding to different power supply models for proper wiring

Electrical connections / Wiring for Oil level sensor
Electrical connections / Wiring for Oil level sensor

  1. Power supply (L or 24V)
  2. Output NO CONTACT
  3. Power supply (N or 0V)
  4. Output COMMON
    Electrical connections / Wiring for Oil level sensor

Introduction

These instructions pertain to the VZH Variable Speed scroll compressors used for A/C systems. They provide necessary information regarding safety and proper usage of this product.

Handling and storage

  • Handle the compressor with care. Use the dedicated handles in the packaging. Use the compressor lifting lug and use appropriate and safe lifting equipment.
  • Store and transport the compressor in an upright position.
  • Store the compressor between -35 °C(-31 °F) and 70 °C(158 °F) when charged with nitrogen.
  • Don’t expose the compressor and the packaging to rain or corrosive atmosphere.

Safety measures before assembly

Never use the compressor in a flammable atmosphere.

  • The compressor ambient temperature may not exceed Ts max value for LP side indicated on compressor nameplate during off-cycle.
  • Mount the compressor on a horizontal flat surface with less than 3° slope.
  • The compressor can only be supplied by a frequency converter. Make sure that the frequency converter is the dedicated one for the compressor (power size and voltage: input & output). Parameter 1.13 of the frequency converter lists the possible combinations of compressors, frequency converters and refrigerants.
  • When installing a VZH, use equipment specifically reserved for HFC refrigerants which was never used for CFC refrigerants.
  • Use clean and dehydrated refrigeration-grade copper tubes and silver alloy brazing material.
  • Use clean and dehydrated system components.
  • The piping connected to the compressor must be flexible in 3 dimensions to dampen vibrations.
  • Make sure the installation is equipped with high pressure safety components (e.g. pressure switch, pressure relief valve) to prevent against the bursting of pressure-containing components.

Assembly

  • Slowly release the nitrogen holding charge through the schrader port.
  • Connect the compressor to the system as soon as possible to avoid oil contamination from ambient moisture.
  • Avoid material entering into the system while cutting tubes. Never drill holes where burrs cannot be removed.
  • Braze with great care using state-of-the-art technique and vent piping with nitrogen gas flow.
  • Connect the required safety and control devices. When the schrader port is used for this, remove the internal valve.

Leak detection

Never pressurize the circuit with oxygen or dry air. This could cause fire or explosion.

  • Do not use dye for leak detection.
  • Perform a leak detection test on the complete system.
  • The test pressure must not exceed 1.1 x PS value for LP side and PS value for HP side indicated on compressor nameplate.
  • When a leak is discovered, repair the leak and repeat the leak detection.

Vacuum dehydration

  • Never use the compressor to evacuate the system.
  • Connect a vacuum pump to both the LP & HP sides.
  • Evacuate the system to a pressure of 500 µm Hg (0.67 mbar) absolute.
  • Do not use a megohmmeter nor apply power to the compressor while it is under vacuum as this may cause internal damage.

Electrical connections

  • Switch off and isolate the main power supply. See previous page for wiring details.
  • The compressor is protected against excess current by the frequency converter. Follow local regulations regarding power line protection. The compressor must be connected to ground.
  • All electrical components must be selected as per local standards and compressor requirements.
  • Please refer to drawings for typical wiring connections and examine the specific wiring diagram located in the frequency converter package. For further details, refer to the application guidelines.
  • Follow very closely the installation instruction for the frequency converter:
    • Mounting: The base frame of the frequency converter must be very well fixed to the support to ensure a very good continuity between the ground potential of all electrical panels and electrical boxes of the system.
    • Wiring: All control wires have to be of a screened design. The cable for electrical motor supply has to be of a shielded design as well. Correct earthing of the shield cover has to be done using the method shown on drawings, every time this one has to be earthed on each end of the cables. Distinct cable trays must be used for control and motor supply.
  • The frequency converter ensures direct motor protection and the factory set parameters are such to protect the motor over all current malfunctions. An external overload is not necessary.
  • Set the frequency converter parameters in accordance with Danfoss recommendations for the CDS frequency converter and VZH variable speed compressor.

Filling the system

  • Keep the compressor switched off.
  • Fill the refrigerant in liquid phase into the outlet side of the condenser or liquid receiver. The charge must be as close as possible to the nominal system charge to avoid low pressure operation and excessive superheat.
    Compressor| Refrigerant charge limit (kg)
    ---|---
    VZH088| 6.0
    VZH117| 8.0
    VZH170| 13

Never let the pressure on LP side exceed the pressure on HP side with more than 5 bar. Such pressure difference could cause internal compressor damage.

  • Keep the refrigerant charge below the indicated charge limits if possible. Above this limit protect the compressor against risk of flooded start (see Application Guidelines section “manage off cycle migration”).

Verification before commissioning

Use safety devices such as safety pressure switch and mechanical relief valve in compliance with both generally and locally applicable regulations and safety standards. Ensure that they are operational and properly set.

Check that the settings of high-pressure switches and relief valves don’t exceed the maximum service pressure of any system component.

  • A low-pressure switch is mandatory to avoid vacuum operation. Minimum setting 1.5 bar (g).
  • Verify that all electrical connections are properly fastened and in compliance with local regulations.
  • The crankcase heater function is factory preset to «disabled». It must not be used for VZH170 but could be used for VZH088/117. In default case, an external crankcase heater is required.
  • After commissioning it is strongly recommended to keep the frequency converter always energized.

Start-up

  • All service valves must be in the open position.
  • Balance the HP/LP pressure.
  • Energize the compressor. It must start promptly.
  • If the compressor doesn’t start, verify that the compressor is hooked up to the frequency converter; check the power lead connections. If these verifications reveal no abnormality, check the motor windings with an ohmmeter.
  • Check the frequency converter control panel: If any alarm is displayed check the wiring and in  particular the polarity of the control cables. If an alarm is shown, refer to the frequency converter application manual. Verify in particular the combination of compressor, frequency converter and refrigerant.
  • Check current draw and voltage levels on the mains. The values for the compressor electrical motor can be directly displayed on the frequency converter control panel.
  • The optimum compressor suction superheat is around 6K. The maximum allowed superheat is 30K.

Check with running compressor

  • Check current draw and voltage.
  • Check suction superheat to reduce risk of slugging.
  • Observe the oil level at start and during operation to confirm that the oil level remains visible.Excess foaming in oil sight glass indicates refrigerant on the sump.
  • Monitor the oil sight glass for 1 hour after system equilibrium to ensure proper oil return to the compressor. This oil check has to be done over the speed range to guarantee:
    • a good oil return at low speed with minimum gas velocity.
    • a good oil management at high speed with maximum oil carry over.
  • Respect the operating limits.
  • Check all tubes for abnormal vibration. Movements in excess of 1.5 mm require corrective measures such as tube brackets.
  • When needed, additional refrigerant in the liquid phase may be added in the low-pressure side as far as possible from the compressor. The compressor must be operating during this process.
  • Do not overcharge the system.
  • Never release refrigerant to the atmosphere.
  • Before leaving the installation site, carry out a general installation inspection regarding cleanliness, noise and leak detection.
  • Record type and amount of refrigerant charge as well as operating conditions as a reference for future inspections.
  • Compressor failure to build up pressure: Check all bypass valves in the system to ensure that none of these has been opened. Also check that all solenoid valves are in their proper position.
  • Abnormal running noise: Ensure the absence of any liquid flood-back to the compressor by means of measuring the return gas superheat and compressor sump temperature. The sump should be at least 8K for VZH088/117 and 6K for VZH170 above the saturated suction temperature under steady-state operating conditions.
  • The high-pressure switch trips out: Check condenser operations (condenser cleanliness, fan operation, water flow and water pressure valve, water filter, etc.). If all these are OK, the problem may be due to either refrigerant overcharging or the presence of a non-condensable (e.g. air, moisture) in the circuit
  • The low-pressure switch trips out: Check evaporator operations (coil cleanliness, fan operations, water flow, water filter, etc.), liquid refrigerant flow and pressure drops (solenoid valve, filter dryer, expansion valve, etc.), refrigerant charge.
  • Low refrigerant charge: The correct refrigerant charge is given by the liquid sight glass indication, the condenser delta T in relation to the refrigerant pressure tables (pressure-temperature), the superheat and the sub-cooling, etc. (if additional charge is deemed necessary, refer to section 8).
  • Compressor short cycling: The number of cycles shall never exceed 12 starts per hour.

Maintenance

Internal pressure and surface temperature are dangerous and may cause permanent injury. Maintenance operators and installers require appropriate skills and tools. Tubing and compressor upper shell temperature may exceed 100 °C (212 °F) and can cause severe burns.
Ensure that periodic service inspections to ensure system reliability and as required by local regulations are performed.

To prevent system related compressor problems, following periodic maintenance is recommended:

  • Verify that safety devices are operational and properly set.
  • Ensure that the system is leak tight.
  • Check the compressor current draw.
  • Confirm that the system is operating in a way consistent with previous maintenance records and ambient conditions.
  • Check that all electrical connections are still adequately fastened.
  • Keep the compressor clean and verify the absence of rust and oxidation on the compressor shell, tubes and electrical connections.
  • Check the internal temperature of the frequency converter on its display and the cooling air flow.
  • Faults are logged in the frequency converter memory and can be displayed. This can help to evaluate and improve parameters of the frequency converter or of the system itself.

Warranty

Always transmit the model number and serial number with any claim filed regarding this product.

Use the fault memory of the frequency converter to recover the fault descriptions before initializing the system and even before shutting off the power.

The product warranty may be void in following cases:

  • Absence of nameplate.
  • External modifications; in particular, drilling, welding, broken feet and shock marks.
  • Compressor opened or returned unsealed.
  • Rust, water or leak detection dye inside the compressor.
  • Use of a refrigerant or lubricant not approved by Danfoss.
  • Any deviation from recommended instructions pertaining to installation, application or maintenance.
  • Use in mobile applications.
  • Use in explosive atmospheric environment.
  • No model number or serial number transmitted with the warranty claim.

Disposal

Danfoss recommends that compressors, frequency converters and compressor oil should be recycled by a suitable company.

DanfossA/S
Climate Solutions • danfoss.com • +45 7488 2222

Any information, including, but not limited to information on selection of product, its application or use, product design, weight, dimensions, capacity or any other technical data in product manuals, catalogues descriptions, advertisements, etc. and whether made available in writing, orally, electronically, online or via download, shall be considered informative, and is only binding if and to the extent, explicit reference is made in a quotation or order confirmation. Danfoss cannot accept any responsibility for possible errors in catalogues, brochures, videos and other material. Danfoss reserves the right to alter its products without notice. This also applies to products ordered but not delivered provided that such alterations can be made without changes to form, fit or function of the product.