MEAN WELL H150W Ultra-High Peak Power Supply Instruction Manual
- June 12, 2024
- MEAN WELL
Table of Contents
MEAN WELL H150W Ultra-High Peak Power Supply Instruction Manual
Features
-
Universal AC input / Full range
-
Withstand 300VAC surge input for 5 seconds
-
300% peak power capability
-
Built-in constant current limiting circuit
-
Fanless design, Cooling by free air convection
-
Protections: Short circuit / Overload / Over voltage /
Over temperature -
Built-in remote sense function
-
Withstand 5G vibration
-
Prating altitude up to 5000 meters(Note.5)
-
Output votage adjustable +15%(Avg.)
-
1U low profile 38mm
-
5 years warranty
Applications
- Industrial automation machinery
- Industrial control system
- Mechanical and electrical equipment
- Diagnostic or biological facilities
- Test or measurement systems
- Telecommunication equipment
GTIN CODE
MW Search: https:/www.meanwell.com/serviceGTIN.aspx
Description
HRP-150N3 series is a 150W single output AC/DC ultra-high peak power supply. This series operates at 85~264VAC input voltage and offers the models with the DC output mostly demanded from the industry. Each model is cooled by free air convection, working for the temperature up to 70°C without cover. Moreover, HRP-150N3 can provide 300% short-duration peak power for motor applications and electromagnetically loads requiring much higher power during start-up.
Model Encoding
SPECIFICATION
MODEL| HRP-150N3-12| HRP-150N3-24| HRP-150N3-36| HRP-
150N3-48
---|---|---|---|---
OUTPUT| DC VOLTAGE| 12V| 24V| 36V| 48V
RATED CURRENT| 13A| 6.5A| 4.3A| 3.3A
CURRENT RANGE| 0 ~ 13A| 0 ~ 6.5A| 0 ~ 4.3A| 0 ~ 3.3A
RATED POWER| 156W| 156W| 154.8W| 158.4W
RIPPLE & NOISE (max.) Note.2| 120mVp-p| 150mVp-p| 200mVp-p| 240mVp-p
VOLTAGE ADJ. RANGE| 10.2 ~ 13.8V| 21.6 ~ 28.8V| 28.8 ~ 39.6V| 40.8 ~
55.2V
VOLTAGE TOLERANCE Note.3| ±1.5%| ±1.5%| ±1.5%| ±1.5%
LINE REGULATION| ±0.3%| ±0.2%| ±0.2%| ±0.2%
LOAD REGULATION| ±0.5%| ±0.5%| ±0.5%| ±0.5%
SETUP, RISE TIME| 3000ms, 50ms/230VAC 3000ms, 50ms/115VAC at full
load
HOLD UP TIME (Typ.)| 16ms/230VAC 16ms/115VAC at full load
INPUT| VOLTAGE RANGE Note.4| 85 ~ 264VAC 120 ~ 370VDC
FREQUENCY RANGE| 47 ~ 63Hz
POWER FACTOR (Typ.)| PF>0.95/230VAC PF>0.98/115VAC at full load
EFFICIENCY (Typ.)| 88%| 88%| 89%| 89%
AC CURRENT (Typ.)| 1.7A/115VAC 0.9A/230VAC
INRUSH CURRENT (Typ.)| 35A/115VAC 70A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION| OVERLOAD| Output power >105% rated for more than 5
seconds then shut down o/p voltage, re-power on to recover
Constant current limiting for output power >330% rated for more than 5 seconds
and then shut down o/p voltage, re-power on to recover
OVER VOLTAGE| 14.4 ~ 16.8V| 30 ~ 34.8V| 41.4 ~ 48.6V| 57.6 ~ 67.2V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, recovers automatically after
temperature goes down
ENVIRONMENT| WORKING TEMP.| -40 ~ +70℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 90% RH non-condensing
STORAGE TEMP., HUMIDITY| -50 ~ +85℃, 10 ~ 95% RH non-condensing
TEMP. COEFFICIENT| ±0.04%/℃ (0 ~ 50℃)
VIBRATION| 10 ~ 500Hz, 5G 10min./1cycle, 60min. each along X, Y, Z axes
OPERATING ALTITUDE Note.5| 5000 meters
SAFETY & **EMC (Note 6)| SAFETY STANDARDS| UL62368-1, TUV BS
EN/EN62368-1, EAC TP TC 004, AS/NZS 62368.1 approved
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION| Parameter| Standard| Test Level / Note
Conducted| BS EN/EN55032| Class B
Radiated| BS EN/EN55032| Class B
Harmonic current| BS EN/EN61000-3-2| Class A
Voltage Flicker| BS EN/EN61000-3-3| —–
EMC IMMUNITY| BS EN/EN55035 , BS EN/EN61000-6-2(BS EN/EN50082-2)
Parameter| Standard| Test Level / Note
ESD| BS EN/EN61000-4-2| Level 3, 8KV air; Level 2, 4KV contact
RF field| BS EN/EN61000-4-3| Level 3, 10V/m
EFT/ Burst| BS EN/EN61000-4-4| Level 3, 2KV
Surge| BS EN/EN61000-4-5| Level 4, 4KV/Line-FG; 2KV/Line-Line
Conducted| BS EN/EN61000-4-6| Level 3, 10V
Magnetic Field| BS EN/EN61000-4-8| Level 4, 30A/m
** Voltage Dips and Interruptions| ** BS EN/EN61000-4-11| 95% dip 0.5
periods, 30% dip 25 periods,95% interruptions 250 periods
OTHERS| MTBF| 1706.0K hrs min. Telcordia TR/SR-332 (Bellcore) ;
222.8K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 1599738mm (LWH)
PACKING| 0.54Kg; 24pcs/12.96Kg/0.9CUFT
NOTE*| 1. All parameters NOT specially mentioned are measured at 230VAC
input, rated load and 25℃ of ambient temperature.2. Ripple & noise are
measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated
with a 0.1uf & 47uf parallel capacitor.3. Tolerance : includes set up
tolerance, line regulation and load regulation.4. Derating may be needed under
low input voltages. Please check the derating curve for more details.5. The
ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m
with fan models for operating altitude higher than 2000m(6500ft).6. The power
supply is considered a component which will be installed into a final
equipment. All the EMC tests are been executed by mounting the unit on a
360mm360mm metal plate with 1mm of thickness. The final equipment must be re-
confirmed that it still meets EMC directives. For guidance on how to perform
these EMC tests, please refer to “EMl testing of component power supplies.”
(as available on http://www.meanwell.com)※ Product Liability Disclaimer:For
detailed information, please refer to
https://www.meanwell.com/serviceDisclaimer.aspx
Block Diagram
Derating Curve
AMBIENT TEMPERATURE (C)
Output Derating VS Input Voltage
INPUT VOLTAGE (V) 60Hz
Function Manual
Peak Power
PoX t+ Py x (T-)
T ated
Duty = x100% = 35%
t =5sec
Pav: Average output power (W)
Pg : Peak output power (W)
Pasc: Non-peak output power (W)
Praea: Rated output power(W)
t: Peak power width(sec)
T: Period(sec)
Peak output power (W)
For example (12V model):
Vin =200V Duty_max =5% P.= P, = 156W P,.= 450W t<5sec T2 552 > 100sec TP, – tP, P..< — < 140W
Remote Sense
The remote sensing compensates voltage drop onthe load wiring up to 0.5V.
NC | NC | +S |
---|---|---|
NC | NC | -S |
Mechanical Specification
Terminal Pin No. Assignment:
Pin No. | Assignment | Pin No. | Assignment |
---|---|---|---|
1 | AC/L | 4,5 | DC OUTPUT -V |
2 | AC/N | 6,7 | DC OUTPUT +V |
3 | FG |
Connector Pin No. Assignment (CN100) : HRS DF11-6DP-2DSA
Pin No. | Assignment | Mating Housing | Terminal |
---|---|---|---|
1 | -S | HRS DF11-6DSor equivalent | HRS DF11-**SCor equivalent |
2 | +S | ||
3~6 | NC |
Installation Manual
Please refer to: http://www.meanwell.com/manual.htm|
File Name: HRP-150N3-SPEC 2022-03-03
Symbols
Documents / Resources
| MEAN
WELL H150W Ultra-High Peak Power
Supply
[pdf] Instruction Manual
H150W Ultra-High Peak Power Supply, H150W, Ultra-High Peak Power Supply, High
Peak Power Supply, Peak Power Supply, Power Supply, Supply
---|---
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>