ecotap Duo Charger User Manual
- June 12, 2024
- ecotap
Table of Contents
- ecotap Duo Charger
- Product Information
- INTRODUCTION
- GENERAL
- DEVICE DESCRIPTION
- SAFETY
- MANDATORY CHECKS BEFORE INITIAL USE
- USER / INSTALLATION MANUAL
- MAINTENANCE
- TRANSPORTATION AND STORAGE
- IN CASE OF MALFUNCTIONS
- OPERATION AND CONTROL OF CHARGING COLUMN
- TECHNICAL SPECIFICATIONS
- EC DECLARATION OF CONFORMITY
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
ecotap Duo Charger
Product Information
Introduction
The Duo charging station is designed for public areas and can be installed
in various environments such as paved areas, open soil/sand, or asphalt
surfaces. It is not suitable for grounds that can flood, loading quays, or
slopes with an angle of more than 4%.
General
Warranty
No information provided in the user manual.
Symbols used in this manual and on the charging system
- Pay attention! Indicates important instructions.
- Electrical hazard: For maintenance, disconnect the installation from its power supply and test it to make sure there is no voltage left before engaging in any maintenance activities.
- Wear special gloves: Indicates the need to wear special gloves.
- Disconnect the electrical installation from its power supply: Indicates the need to disconnect the electrical installation from its power supply.
Device Description
Use
The Duo charging station is designed for use in public areas.
Accessories
The following accessories are not provided: tools, foundation.
Safety Features
- 2 half euro profile cylinders
- Extra caps behind front cap
- 12 Volt control voltage
- Components comply with IP2 at least
- Strain reliefs
- 4 mm steel casing
- IP54 (lowest waterproof class for Mennekes outlets)
Safety
Read the safety regulations carefully before installing and using the
charging station. Ensure there is no danger of tripping over objects or paving
while digging the hole for the foundation. Wear suitable gloves for any
special actions during installation and connection process.
Mandatory Checks Before Initial Use
The following checks are mandatory before the charging station is used. Do
not use the charging station if any of the checks indicate insufficient power
supply or stability.
- Check the insulation resistance of the various conductors in accordance with NEN1010 provision 61.3.3.
- Perform all activities in accordance with NEN 3140.
- Check if the wires have been connected to the terminals in the right order.
- Check if the conductors on the terminals have been screwed on properly (4 to 5 NM).
- Check if the grounding connector has been connected to the coded terminal.
Maintenance
No information provided in the user manual.
Transportation and Storage
No information provided in the user manual.
In Case of Malfunctions
No information provided in the user manual.
Operation and Control of Charging Station
No information provided in the user manual.
Technical Specifications
No information provided in the user manual.
Contact Details Supplier
No information provided in the user manual.
EG Conformity Statement
No information provided in the user manual.
INTRODUCTION
Thank you for choosing for an Ecotap® charging station. This manual is
regarding the charge point DUO.
This manual contains important information for properly and safely installing
and using the charging station.
This charging station is designed for vehicles that are equipped with a mode 3
charging system that complies with IEC 61815-1 (version 2.0) and a plug system
that complies with VDE-AR-E 2623-2-2. Together with the vehicle and system,
the charging station will select the best option for charging the vehicle
quickly and safely.
The entire charging station complies with the 2014/35/EU directive dealing
with the harmonisation of regulations regarding electric materials within
certain voltage limits (a recast of all previously published versions).
This manual explains how to safely install and use the charging station. This
manual was drawn up in such a way as to ensure the charging station’s maximum
functioning and lifespan.
This manual was drawn up with great care. However, should anything remain
unclear after reading it, please contact your supplier before you install the
charging station.
We cannot guarantee that this charging station will function properly unless
it is installed by an authorised or certified installer / mechanic.
Read this manual carefully before you install or use the charging station.
Save this manual and store it near the station so that the instructions and
safety regulations will always be readily available.
© Copyright
No part of this publication may be copied, reproduced or saved in a retrieval
system without Ecotap® B.V.’s prior written consent.
This is an English translation of the original Dutch manual.
GENERAL
Warranty
The Ecotap® B.V. General terms and conditions for delivery apply here.
Ecotap® B.V. cannot be held accountable for any injury or damage to goods
should the charging station be altered, damaged, refitted or expanded upon
with other components, or not used in accordance with the instructions and
conditions set out here.
Symbols used in this manual and on the charging system
Symbol | Meaning |
---|---|
**** | Pay attention! Important instruction |
**** | Electrical hazard |
For maintenance: first disconnect the installation from its power supply |
and test it to make sure there is no voltage left, before engaging in any
maintenance activities
| Wear special gloves.
| Disconnect the electrical installation from its power supply
| Reading this manual is mandatory
---|---
DEVICE DESCRIPTION
Use
This charging station is especially designed for public areas.
The station can be installed in various environments: in paved areas, in open
soil/sand, or in asphalt surfaces.
The following environments, however, are not suitable:
- All grounds that can flood
- Loading quays
- Slope at an angle of more than 4%
Accessories
The following accessories will not be provided: tools, foundation.
Safety provisions
- 2 half euro profile cylinders
- Extra caps behind front cap
- 12 Volt control voltage
- Components comply with IP2 at least
- Strain reliefs
- 4 mm steel casing
- IP54 (lowest waterproof class for Mennekes outlets).
SAFETY
Read the following safety regulations carefully before you install and use the charging station.
Safety regulations
Before you install the charging station, you must make sure the location is
safe for all bystanders. NEVER allow children onto this worksite. Never allow
ANYONE who has nothing to do with the work onto the worksite.
- Never be distracted while you are performing the work.
- Make sure you maintain a healthy posture at all times while doing the work.
- Do not leave any tools or charging station components unattended.
- Make sure any tools you are using are clean and dry.
- Make sure that the charging station, tools and components will stay dry when it is raining.
Make sure that there is no danger of anyone tripping over objects or paving while you are digging the hole for the foundation.
****Make sure to wear good, suitable gloves for any special actions throughout the entire installation and connection process.
****Always check any measuring instruments you will be using to disconnect the installation from its power supply before you use them, checking them several times to make sure they are working properly.
MANDATORY CHECKS BEFORE INITIAL USE
**| The following checks are mandatory before the charging station goes
live. NEVER use the charging station if one or more of the checks indicate
that the power supply or stability of the charging station does not suffice.
Check the insulation resistance of the various conductors in accordance with
NEN1010 provision 61.3.3.
---|---
**| Always perform the checks below before voltage is applied to the DUO
charging station.
- All of the activities listed below must be performed in accordance with NEN 3140.
- Check whether the wires have been connected to the terminals in the right order.
- Check whether the conductors on the terminals have been screwed on properly (4 to 5 NM).
- Check whether the grounding connector has been connected to the coded terminal and whether it has been connected to the grounding electrode or the supplied grounding device. The entire grounding system must comply with the NEN1010/EU/35.
- Check whether the charging station is stable.
- Check whether the seals on the charging station’s caps have been installed properly during installation (IP54).
- Check whether any actions still need to be performed, so that they may be performed safely.
- Make sure there are no obstacles surrounding the worksite.
- Before any voltage is applied to the charging station, make sure to contact Ecotap® B.V. by calling 0031 (0) 411-210210 so that we can activate that particular station’s software; we will need the station’s unique code to do so.
USER / INSTALLATION MANUAL
Mounting the casing on the foundation
- The foundation must be installed in a hole of 50×50 cm in size and 80 cm deep.
- The bottom of the hole must be stable and flattened out properly. Place the foundation in the hole and check whether it level using a spirit level. You can correct any small deviations while you are closing the hole.
- Place the charging station on the foundation without its 2 bent steel cap sections and mount it using the bolts and nuts supplied (the nuts go on the top).
- Leave the transparent lids on the front of the charging station in place for now. Make sure the station faces the right way (i.e. the connecting side is at the front).
- Close the hole using around 20 cm of soil/sand.
- Install the cap in the back using the nuts that have been supplied.
- Keep in mind that there is sufficient space for the operation of the charging station. For this we advise to keep at least 1 meter of free space around the charging station.
Opening and closing the charging station
Always deenergise the charging column and read the operating instructions
before handling maintenance or malfunctions.
At the base of the charging station, at the front in the cover, there is a lock that locks the entire DUO charging column.
- Remove the cover plate with socket 2.5.
- Open the charging point with the key provided.
- Insert your key into the right lock.
- Turn the key all the way to the right.
- Turn the two locks with cylinder all the way to the left.
After unlocking the lock, the front cover (with lock) can be disconnected from the charging point.
- Grasp the front cover at the sides.
- Slide the front cover upwards (± 10cm) and move the top of the front cover away from the charging point. (see T1.4)
After removing the front cover, the rear cover can be disconnected.
- At the bottom of the charging point at the front, loosen the two nuts.
- Move the rear cover off the charging point at the bottom.(see T1.5)
Installing the protective casing
The protective casing pipe (80cm) is supplied along with the foundation.
Once the casing has been mounted on the foundation, the clear plastic
protective lid on the bottom of the charging station can be removed.
Install the casing bottom side-down and fix it in place using the support
clamp. (diagram 1.1)
Feeding the cable and installing it with strain relief
Feed the power cable through the protective casing pipe.
Avoid making it too long. Fit the cable clamp around the cable and fix it in
place (3 Nm max). (diagram 1.1)
Connecting the power cable to the terminals
Connect the phase conductors to the terminals marked L1 / L2 / L3 (4-5 Nm)
Connect the neutral conductor to the neutral terminal (blue)(4-5 Nm). Connect
the grounding conductor to the coded ground terminal (green)
Connecting the grounding electrode/grounding conductor
Connect the connection cable’s grounding conductor to the specified grounding
point (the ground terminal). If a grounding electrode has been installed,
connect that to the ground terminal as well, as shown in diagram 1.1. Perform
the entire grounding process in accordance with the guidelines currently in
force, namely NEN1010/EU/35
Replace cylinder lock
Always deenergize the charging column and read the operating instructions
before handling maintenance or malfunctions.
- Use socket 2.5 to remove the cover plate which keeps the lock free of sand and dirt.
- Insert the key into the right lock and turn the key clockwise.
- Turn the two locks with casing counterclockwise 90˚.
- Lift the cover (front with lock) up and off the column.
Half euro lock cylinder replacement
- Unscrew the Allen bolt with socket 3mm.
- Slide the entire lock cylinder (with the locks) out of the cover.
- Work the cylinder lock, making sure the cam matches Figure 6 (T 1.9)
- Unscrew the Allen bolt (with Allen spanner 2.5mm).
- Lock can be replaced.
- Screw everything in reverse order.
MAINTENANCE
Always disconnect the charging station from its power supply completely and
read the manual before performing any maintenance or fixing any malfunctions.
Repairs or replacements of components may only be done if using products that
are approved by the supplier. When in doubt, please contact Ecotap® first.
Repairs and replacements must always be performed by an authorised person /
specialist. The maintenance must always comply with and be performed in
compliance with NEN3140 and NEN50110 low voltage European standards.
Check the charging station for any leaks.
Test the heating element and the thermostat together to make sure they are
working correctly. The thermostat must be set to five degrees or to frost
protection mode. Check the connections on the power supply cable and ensure a
fixed connection of between 4 and 5 Nm.
Treat any minor damage to the charging station with corrosion-resistant paint
in the right shades (Ecotap® green ral.6018 & white ral.9016).
Treat the cylinder locks with graphite powder or a suitable oil product if
they require any maintenance.
TRANSPORTATION AND STORAGE
Transport the charging station (the core housing all of the technology) upright and prevent the coating from being damaged; any such damage might result in corrosion. Provided that they are properly protected to prevent them being damaged, the caps can be transported in a variety of positions. The charging station should be stored in a dry, damp-free area.
IN CASE OF MALFUNCTIONS
In case the DUO charging station is not functioning (properly), please contact
the Ecotap® 24/7 helpdesk immediately
(phone number: 0031 (0) 411-745020) or a licensed mechanic in possession of
measuring and testing equipment with auto simulation.
WARNING!
All work performed on and modifications made to the charging station must
comply with NEN1010 at the very least.
OPERATION AND CONTROL OF CHARGING COLUMN
The charging column can be operated with a charging card.
To charge with registration, you still need to register it.
Once registration is complete, the charging column can be used with any
Electric Transport Charging Card (EV Charging Card) or other suitable cards,
mobile and key holders. When unused, the charging column will give an
illuminated green signal with some regularity.
Operation: Starting or stopping charging is done by holding the charging card
in front of the scan point, you hear 1 sound signal and the lamp starts
flashing green. First, the plug is locked in the Mennekes charging socket.
Then the charging column communicates with the vehicle and the BackOffice
system. Once all safety and payment requirements have been checked, the
maximum permissible charging current is transmitted. The charging procedure is
now automatically switched on and the lamp lights blue. When stopping the
charging process, hold the pass in front of the scan point again. You will
hear 2 beeps and the lamp will flash green and go out as soon as the plug is
unlocked. You can now safely remove the plug.
TECHNICAL SPECIFICATIONS
General characteristics|
---|---
Reference number| 60111810 / 60321110 / 60161610 / 60321610 / 60081812/
60081112 / 60081612 / 60081813 / 60081114 / 60081
614/60102215/60102205/60080199 / 60080198
Reference number (Eichrecht)| 60451810 / 60451110 / 60451610
Dimension H x W x D (mm)| 1400 x 220 x 240
Casing material| Steel 2,2 mm
Standard colour| Body: Ral 6018 / Cover: Ral 9016 for 60451810 / 60081812 /
60081813 / 60102215 / 60102205 / 60080199 / 60080198
Body: Ral 7011 / Cover: Ral 9016 for 60111810 / 60321110 /
60451110 / 60081112 / 60081114
Body: Ral 9016 / Cover: Ral 9016 for 60161610 / 60321610
/ 60451610 / 60081612 / 60081614
Steel treatment| Anti-corrosion (KTL) and powder coating
Weight (kg)| 45 kg for 60451810 / 60451110 / 60451610 / 60081812 / 60081112 /
60081612 / 60081813 / 60081114 / 60081614
49 kg for 60111810 / 60321110 / 60161610 / 60321610 / 60102215 / 60102205 /
60080199 / 60080198
Number of charging points| 2
Socket| Type 2
Cable| Type 2
Electrical characteristics|
Power output per socket| 0 to 22 kW for 60321110 / 60321610 / 60451810 /
60451110 / 60451610 / 60081812 / 60081112 / 60081612 / 60081813 / 60081114 /
60081614 / 60102215 / 60102205 0 to 11 kW for 60111810 / 60161610 / 60080199 /
60080198
Operating voltage (Ue) / Current rates (In A, In C)| Single-phase cabling,
phase + N 230V~ from 0 to 32A (determined at 20°C)
Three-phase cabling, 3 phases + N 400V~ from 0 to 32A (determined at 20°C)
Impulse voltage (Uimp)| 4kV
Insulation voltage (Ui)| 230V single-phase 500V three-phase
Frequency (fn)| 50Hz/60Hz
Rated voltage| 1 phase + N: 230V – 3 phases + N: 400V
Voltage tolerance (V) regardless of vehicle requirements| 195V – 265V
Integrated protection system on charging station| Fuse type gG 63A
Integrated protection system per charge point| MCB 40A curve C
RCD 40A 30mA Type B
Conditional short-circuit| 6000A IEC/EN 60898-1
10kA IEC/EN 60947-2
Allowable thermal stress in Short Circuit| 16 000 A²s
Connection to the mains| Phase/Neutral, rigid cable, 2.5 to 35 mm², screw
terminals H07 V R/U Earth, rigid cable, 2.5 to 35mm², screw terminals H07 V
R/U
Type of load| Mode 3 charging terminal equipped with a locking system for Mode
3
Vehicle connection Mode 3 connector socket (60451810 / 60451110 / 60451610 /
60081812 /
60081112 / 60081612 / 60081813 / 60081114 / 60081614)| Type 2 3P+N (single-
phase compatible) with pilots compliant with IEC 62191-1 and IEC 62196-2.
Use only a manufacturer-approved plug with silver-plated contacts.
Use of extension and adapter prohibited. .
Vehicle connection Mode 3 attache cable connector (60111810 / 60321110 /
60161610 / 60321610 / 60102215 / 60102205 / 60080199 / 60080198)| Type 2 3P+N
(single-phase compatible) with pilots compliant with IEC 62191-1 and IEC
62196-2.
Use of extension and adapter prohibited. 60080199 / 60080198: 4m curl 3x16A
60111810 / 60161610: 4m straight 3x16A
60321110 / 60321610 / 60102215 / 60102205: 8m
straight 3x32A
AC meters| MID certified, Class B according to EN 50470-1, -3
Back office protocol| OCPP 1.6 Json
Positioning| GPS
Connectivity Ethernet| RJ45 connector for 60451810 / 60451110 / 60451610
/ 60081813 / 60081114 / 60081614 / 60102215 / 60080199
Environment|
Operating temperature| -25°C / +50°C
Storage temperature| -25°C / + 80°C
Relative humidity| 0 to 90% without condensation
Protection rating| IP 54 (IEC 60529), IK 10 (EN 62262) Plugged in or not
Noise level| < 40 dBA at 1m
Product| IEC 61851-1, IEC TS 61439-7 (AEVCS)
Installation| Interior or exterior, limited access zone, intended for use by
ordinary persons (DBO), assembly in cabinet (wall mounted), Pollution Degree
3, TNS, TT,compatible earthing system.
In the event of an IT earthing system, this can be changed locally by adding
an isolation transformer.
Electrical safety| Class 1 IEC 61140
Electromagnetic compatibility|
European standards| Low Voltage Directive 2014 / 35EU / EMC Directive: 2014 /
30 / EU|
Radio technology type| GSM 2G/3G/4G, GPRS, RFID|
Suitable charging cards| Mifare, Ntag and iCODE SLI cards (more
info)|
| | |
EC DECLARATION OF CONFORMITY
EC Declaration of Conformity for machines
(Directive 2014/35/EU, Annex II page 96/369)
Ecotap® B.V. Industrieweg 4 5281RW Boxtel, The Netherlands, hereby declares
that the charging stations stated below comply with the Machinery Directive
and other regulations and standards mentioned.
Name: Ecotap® Charging station DUO, Type: SLA_K2, Designed in: 2018
EC directives applied:
- Machinery Directive 2014/35/EU
- EMC Directive 2014/30/EU
Standards used as reference:
- EN/IEC 60950-22:2017
- EN/IEC61851-1:2017
- EN/IEC61851-22:2002
- EN/IEC 62196-2:2017
- EN/IEC 61000-6-2:2016
- EN/IEC 61000-6-3/2007 + A1:2011
- EN/IEC 60335-1/2012 + A13:2017
- EN/IEC 60364-4-41:2017
- NEN/EN/IEC 60529
- IEC 62262
- NEN/EN/IEC 61439-1
- IEC/TS 61439-7
Boxtel, June 2018
Ir. P.F.A. van der Putten (Technical Director)
Ecotap B.V.
Kruisbroeksestraat 23 5281 RV Boxtel
The Netherlands
+31(0) 411 210 210 info@ecotap.nl
www.ecotap.nl