RC132V G4 LED36S/840 PSU W60L60 OC ELB3| 3600| 4000| 29| 595×595×11| 3.90
RC132V G4 LED36/840 PSU W60L60 OC TP(a)ELB3| 3600| 4000| 29| 595×595×11| 3.90
RC132V G4 LED34S/830 PSD W60L60 OC ELB3| 3400| 3000| 29| 595×595×11| 3.90
RC132V G4 LED36S/840 PSD W60L60 OC ELB3W4W2| 3600| 4000| 29| 595×595×11| 3.90
RC132V G4 LED43S/840 PSD W60L60 OCELB3W4/W2| 4300| 4000| 34| 595×595×11| 3.90
RC132V G4 LED36S/840 W60L60 OC IA1 ELB3 W4| 3600| 4000| 29| 595×595×11| 3.90
RC132V G4 LED43S/840 W60L60 OC IA1 ELB3| 4300| 4000| 34| 595×595×11| 3.90
RC132V G4 LED36/840 W60L60 OC TP(a)IA1 ELB3| 3600| 4000| 29| 595×595×11| 3.90
RC133V G4 LED36S/840 PSD W62L62 OC ELB3| 3600| 4000| 29| 622×622×11| 4.10
RC133V G4 LED34S/830 PSD W62L62 OC ELB3| 3400| 3000| 29| 622×622×11| 4.10
RC132V G4 LED36S/840 PSU W30L120 OC ELB3| 3600| 4000| 29| 1195×295×11| 4.00
RC132V G4 LED36S/840 PSD W30L120 OC ELB3| 3600| 4000| 29| 1195×295×11| 4.00
RC132V G4 LED36S/840 W30L120 OC IA1 ELB3| 3600| 4000| 29| 1195×295×11| 4.00
RC132V G4 LED36S/840 PSU W60L60 NOC ELB3| 3600| 4000| 29| 595×595×11| 3.90
RC132V G4 LED43S/840 PSD W60L60 NOC ELB3| 4300| 4000| 34| 595×595×11| 3.90
RC132V G4 LED36S/840 W60L60 NOC IA1 ELB3| 3600| 4000| 29| 595×595×11| 3.90
RC132V G4 LED43S/840 W60L60 NOC IA1 ELB3| 4300| 4000| 34| 595×595×11| 3.90
RC132V G4 LED36S/840 PSU W30L120 NOC ELB3| 4300| 4000| 34| 595×595×11| 3.90
RC132V G4 LED36S/840 W30L120 NOC IA1 ELB3| 3600| 4000| 29| 1195×295×11| 4.00

DIMENSIONS

PHILIPS-RC132V-RC-LED-Panels-FIG-2

INSTALLATION INSTRUCTIONS

PHILIPS-RC132V-RC-LED-Panels-FIG-3

Versions with Wieland connector (W4, W4/W2) ELB3 versions

PHILIPS-RC132V-RC-LED-Panels-FIG-4

If the external flexible cable or cord of this luminaire is damaged, it shall be replaced by a special cord or cord exclusively ! available from the manufacturer or his service agent

ELB3 versions

PHILIPS-RC132V-RC-LED-Panels-FIG-5

Emergency Luminaires
In case a self-contained emergency driver has been added, this is how to set the timers (IEC62034 (§6.3.2)):

  • DALI version : Check IEC 62386 part 202.
  • PRO version : The first test is randomized. Then a fixed schedule is maintained, there is no need to set the timers or take special precautions when powering
  • BASIC version : No timers available, only manual testing through the test button.

PHILIPS-RC132V-RC-LED-Panels-FIG-6

Lifetime

The batteries have a life time expectancy of 4 years when maintained properly. Replace after that time!

Automatic emergency time selection
After installation and power up the driver will detect the battery and start the automatic detection process.

  • During automatic detection, the indicator LED will light up with short green flashes.
  • Between minimum 6 and maximum 30 seconds the TrustSight driver will set the battery type (number of cells) and will set the emergency output power accordingly.

After that, the system is defined and fully operational. The battery type definition has influence on the performance during the self-test and on the battery charge method. When the automatic battery detection process is disrupted, e.g. by switching off the permanent mains, the detection process is stopped and the TrustSight emergency driver will go into emergency mode with the lowest output power. At a next power up, the automatic detection process will start again.

Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to EN50172 clause 7.2.3 and 7.2.4. Switch on in the emergency mode each month by simulation of a failure of the supply to the normal lighting for a period sufficient to ensure that each lamp is illuminated. Twice per year, each luminaire shall be tested for its full rated duration (at least 3hrs). For more information please consult the TrustSight Gen 3 Design in guide. The latest version is available online

PHILIPS-RC132V-RC-LED-Panels-FIG-7PHILIPS-
RC132V-RC-LED-Panels-FIG-8

  • The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
  • The light source of this luminaire is not replaceable; when the light source reached its end of life the whole luminaire shall be replaced
  • During installation or maintaining the luminaire please use gloves to avoid spots on the cover.
  • To remove dirt and spots use the following
    • Dust: use micro fiber cloths only.
    • Fingerprints, etc.: use a cleaner for synthetic materials with antistatic properties.
  • Luminaires not suitable for covering with thermally insulating material.
  • For controllable luminaires ,the classification of insulation between LV supply and control conductors shall be basic insulation at least.
  • Luminaire must not be used or stored in corrosive environment where hazardous materials such as Sulphur,Chlorine, Phthalates, etc, are present.

To get an overview of all spare parts for a luminaire, please refer to detailed instructions in the service manual available via the Signify Service tag apps (Android and iOS).

age, installation, use, operation and maintenance of the products needs to be performed exactly according the instructions in this manual and other uctions as may be provided by us to guarantee safe use of the product over its entire lifetime. Falure to adhere to these instructions wil invalidate your lement to warranty. Bolts with indication of torque strength on the drawing need to be tightened using a calibrated torque wrench. Pre-assembled bolts dto be retightened again to the required torque specification to assure maximum strength over Mealtime.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals