Berker 80040001 Bus Application Unit Flush Mounted System Instruction Manual

June 12, 2024
Berker

Berker 80040001 Bus Application Unit Flush Mounted System

Berker-80040001-Bus-Application-Unit-Flush-Mounted-System-product-
image

Product Information

The product is a bus application unit that is flush-mounted and can be used with the system-/easylink. It is designed for installation by qualified electricians and complies with relevant
accident prevention regulations. The device is part of the KNX system and requires specialized knowledge obtained from KNX training courses for comprehension. It can be programmed and configured using KNX-certified software or devices specifically developed for simple setting and start-up. The device has various features including an illuminated programming button, mounting device for fastening clamps, dust protection cover for the user interface, screw holes for dismantling protection, plug-in interface for a temperature sensor, and a KNX bus connection terminal.

Product Usage Instructions:

  1. Ensure that the device is installed and assembled by a qualified electrician.
  2. Always follow the relevant accident prevention regulations during installation and assembly.
  3. Comply with applicable regulations and standards for SELV electrical circuits when installing and laying cables.
  4. Protect the device from pollution during renovation work, such as paint, wallpaper paste, and dust.
  5. Retain these instructions as they are an integral component of the product.
  6. For correct use, attach application modules (e.g., push-button, thermostat) to the KNX system.
  7. Install the device into a wall box according to DIN 49073.
  8. To connect the device, follow these steps:
    • Connect the bus line via the KNX bus terminal (red +).
    • If necessary, connect an external temperature sensor via the connecting terminal.
  9. For flush-mounted installation in a wall box, use the fixing claws provided. For installation in a hollow wall wall-box, use screws for fixing.
  10. Mount the device into the wall box in the correct position.
  11. If no application module is mounted, close the dust protection cover for the user interface.

Safety instructions

  • Electrical equipment may only be installed and assembled by qualified electricians. Always follow the relevant accident prevention regulations.
  • Failure to comply with these installation instructions may result in damage to the device, fi re or other hazards.
  • When installing and laying cables, always comply with the applicable regulations and standards for SELV electrical circuits.
  • During renovation work, protect the device from pollution by paint, wallpaper paste, dust etc. The device can be damaged.
  • These instructions are an integral component of the product and must be retained by the end user.

Design and layout of the device

  • Figure 1: Front view
  • Figure 2: Rear view
  1. Illuminated programming button
  2. Mounting device for fastening clamps
  3. Dust protection cover for user interface (suitable for labelling fi eld sticker)
  4. User interface
  5. Screw holes for dismantling protection
  6. Plug-in interface for temperature sensor
  7. KNX bus connection terminal
  8. Attachment claws

Function

System information
This device is a product of KNX system and corresponds to the KNX guidelines. Detailed specialised knowledge obtained from KNX training courses
is required for comprehension. The planning, installation and commissioning are carried out with the help of KNX-certified software.

system link start-up
The function of the device is software-dependent. The software is to be taken from the product database. You can fi nd the latest version of the product database, technical descriptions as well as conversion and additional support programmes on our website.

easy link start-up
The function of the device is configuration-dependent. The configuration can also be done using devices developed specially for simple setting and start- up.
This type of configuration is only possible with devices of the easy link system. easy link stands for easy, visually supported start-up. Preconfigured standard functions are assigned to the in/outputs by means of a service module.

Correct use

  • Attaching application modules, e.g. push-button, thermostat, to the KNX system
  • Installation into wall box according to DIN 49073

Product characteristics

  • Start-up and programming in S-mode and E-mode
  • Localisation function by integrated buzzer (siren)
  • Connection for external temperature sensor
  • Integrated dust protection cover for protection of the user interface

Information for electricians Installation and electrical connection

DANGER!

  • Touching live parts in the installation environment can result in an electric shock!
  • An electric shock can be lethal!
  • Disconnect the connecting cables before working on the device and cover all live parts in the area!

Connecting and installing the device

  • Connect bus line via KNX bus terminal (7): red +, black –.
  • Connect external temperature sensor via connecting terminal (6) if necessary.
  • For mounting in a flush-mounted wall box use fixing claws (8) or in a hollow wall wall-box use screws for fixing.
  • Mount the device into the wall box in the correct position.
  • If no application module is mounted, close dust protection cover for user interface.

Start-up

system link – Loading the physical address and application software

  • The device is mounted and connected to the KNX bus. Application module is not mounted. The programming button and LED are accessible.
  • The physical address is only ever assigned for one device. Only one device can ever be in programming mode.
    • Switch on bus voltage.
    • Press programming button (1). The button lights up.
  • If the button does not light up, no bus voltage is present.
    • Load the physical address into the device.
    • The programming LED goes out.
    • Load application software into the device.
    • Note the physical address on the bus application unit (3) and on the associated application module.
  • The application software of the application module can be fully loaded into the bus application unit. The bus application unit automatically detects the application module after mounting.

easy link
Information on the system configuration can be taken from the extensive description of the service module easy link.

Appendix Technical data

  • KNX Medium TP 1
  • Start-up mode system link, easy link
  • Rated voltage KNX DC 21 … 32 V SELV
  • Connection mode KNX bus connecting terminal
  • Power consumption KNX max. 150 mW (with application module)
  • User interface output power max. 100 mW
  • Dimensions (W x H x D) 71 x 71 x 32 mm
  • Clamping range of attachment claws 52 … 70 mm
  • Degree of protection IP20
  • Protection class III
  • Operating temperature -5 … +45 °C
  • Storage/transport temperature -20 … +70 °C

Troubleshooting

Bus operation is not possible

  • Cause: Bus voltage is not present.
    • Check bus connection terminals for correct polarity.
    • Check bus voltage by briefly pressing the pro-gramming button (1), red LED lights up if bus voltage is present.

Warranty

  • We reserve the right to make technical and formal changes to the product in the interest of technical progress.
  • Our products are under guarantee within the scope of the statutory provisions.
  • If you have a warranty claim, please contact the point of sale or ship the device postage free with a description of the fault to the appropriate regional representative.

Berker GmbH & Co. KG, Zum Gunterstal, 66440 Blieskastel, Germany T + 49 6842 945 0 F + 49 6842 945 4625 info@berker.de berker.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals