BEGA 24173 Ceiling and Wall Luminaire Instruction Manual
- June 13, 2024
- BEGA
Table of Contents
24173 Ceiling and Wall Luminaire
Instruction Manual
Technical amendments reserved
Ceiling and wall luminaire
24173 Ceiling and Wall Luminaire
Instructions for use
Application
Unshielded ceiling and wall luminaire with high protection class.
A luminaire made of aluminium alloy and crystal glass.
Product description
Luminaire made of aluminium alloy, aluminium and stainless steel BEGA Unidure
® coating technology
Crystal glass, white inside 2 mounting holes ø 4.5 mm Distance apart 236 mm 2
screw cable glands with strain relief for through-wiring power connecting
cable ø 7–12 mm 1 screw cable gland closed at the factory with a dummy plug
Connection terminal 2.5@ Earth conductor connection LED power supply unit
220-240 V x 0/50-60 Hz DC 176-280 V BEGA Thermal Switch ® Temporary thermal
shutdown to protect temperature-sensitive components
Safety class I
Ballproof – The testing of ball impact safety
was carried out exclusively with handballs in accordance with DIN 18032-3:
2018-11.
Protection class IP 65
Dust-tight and protection against water jets
Impact strength IK10
Protection against mechanical impacts < 20 joule
– Safety mark
– Conformity mark
Weight: 2.6 kg
This product contains light sources of energy efficiency class(es) C, D
Safety
The installation and operation of this luminaire are subject to national
safety regulations.
Installation and commissioning may only be carried out by a qualified
electrician.
The manufacturer accepts no liability for damage caused by improper use or
installation.
If subsequent modifications are made to the luminaire, the person responsible
for these modifications shall be considered the manufacturer.
Overvoltage protection
The electronic components installed in the luminaire are protected against
overvoltage in accordance with DIN EN 61547.
To achieve an additional protection against e. g. transients, etc. we
recommend separate overvoltage protection components. You can find them on our
website at www.bega.com.
Lamp
Module connected wattage | 12.9 W |
---|---|
Luminaire connected wattage | 15 W |
Rated temperature | ta = 25 °C |
Ambient temperature | ta max = 30 °C |
24 173 K3
Module designation | LED-0985/830 |
---|---|
Colour temperature | 3000 K |
Colour rendering index | CRI > 80 |
Module luminous flux | 2155 lm |
Luminaire luminous flux | 1158 lm |
Luminaire luminous efficiency | 77,2 lm / W |
24 173 K4
Module designation | LED-0985/840 |
---|---|
Colour temperature | 4000 K |
Colour rendering index | CRI > 80 |
Module luminous flux | 2265 lm |
Luminaire luminous flux | 1217 lm |
Luminaire luminous efficiency | 81,1 lm / W |
Installation
LED are high-quality electronic components!
Please avoid touching the light output opening of the LED directly during
installation or relamping.
Undo hexagon socket head screw (wrench size 3 mm) through the opening in the
luminaire housing up to the stop and lift luminaire top.
Disconnect the earth conductor connection from the plug connection.
Disconnect plug-connection of the LED connecting cable.
Lead the mains supply cable through the screw cable gland into the luminaire
back housing.
The installed black gasket insert is intended for cables ø < 10 mm.
For cables ø 10-12 mm the enclosed grey gasket insert must be used.
In case of through-wiring replace the factory installed dummy plug with the
enclosed corresponding gasket insert.
At the same time, use the enclosed synthetic cone-thrust collar between gasket
insert and thrust screw (wrench size 22 mm) (see sketch).
Fix luminaire base with enclosed or any other suitable fixing material onto
the mounting surface.
Tighten screw cable gland.
Make the earth conductor connection and the electrical connection.\
In order to guarantee the maximum service life of the electrical components,
the enclosed desiccant pouch must be placed in the luminaire.
Remove the desiccant pouch from the foil packaging and place it in the
position marked by the red information label immediately before finally
closing the luminaire.
Connect the LED connection cable by means of a plug connector.
Make earth conductor connection between luminaire top and luminaire base.
Push plug into coupler as far as it will go.
In order to ensure the tightness of the luminaire, the grub screw for fixing
the luminaire upper part must not lie in the marked area.
Make sure that gasket is positioned correctly.
Tighten grub screw firmly.
Cleaning · Maintenance
Clean luminaire regularly with solvent-free cleansers from dirt and deposits.
Do not use high pressure cleaners.
Replacing the LED module
The designation of the LED module is noted on a label in the luminaire.
The light colour and light output of BEGA replacement modules correspond to
those of the modules originally fitted.
The module can be replaced by qualified persons using standard tools.
Disconnect the system and open the luminaire.
Please follow the installation instructions for the LED module.
Inspect and, if necessary, replace the luminaire gaskets.
Defective glass must be replaced.
Close the luminaire.
Spares
Spare glass | 11 003 518 |
---|---|
LED power supply unit | DEV-0150/350 |
LED module 3000 K | LED-0985/830 |
LED module 4000 K | LED-0985/840 |
Gasket glass | 83 001 907 |
Gasket housing | 83 002 167 B1 |
BEGA Gantenbrink-Leuchten KG ·
Postfach 31 60
· 58689 Menden ·
info@bega.com ·
www.bega.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>