EATON CA650055EN 600 A 35 kV Class T-OP II Deadbreak Connector Instruction Manual
- June 4, 2024
- EATON
Table of Contents
Catalog Data CA650055EN
Effective July 2022
Supersedes May 2020
COOPER POWER SERIES
General
Eaton’s Cooper PowerE series 600 A 35 kV Class T-OPE II deadbreak connector is used to terminate the high-voltage underground cable to transformers, switches, switchgear, and other apparatus. It is fully shielded and submersible and meets the requirements of IEEET Std 386E-2016— ”Separable Insulated Connector Systems.” The 200 A three-phase rated interface provides a means for obtaining a live test, visible ground, and visible break using a clampstick. It also provides a convenient location for an Eaton’s Cooper Power series metal oxide varistor elbow (M.O.V.E.) arrester, grounding elbow, or a 200 A tap line. Eaton’s Cooper Power series offers an optional capacitive test point similar to its 200 A elbow connectors. This allows use of test point faulted circuit indicators. T-OP II connectors are designed for use on solid dielectric cable (XLPE or EPR) with extruded semi-conducting shields. Installation on the jacketed cable may require additional sealing material. Adapters are available for terminating tape shield and drain wire UniShieldT jacketed cable.
900 A rating
The T-OP II connector system is rated for 900 A continuous when installed on a
copper bushing.
200 kV BIL rating
The T-OP II connector is available with an optional 200 kV BIL rating,
allowing you to match the BIL rating of the system and the equipment to which
it will be connected.
Installation
The T-body is assembled onto a prepared cable with a threaded coppertop
compression connector or shear bolt. The loadbreakreducing tap plug (LRTP) is
threaded into the connector by using a 5/16 inch T-wrench. The short end of a
special copper alloy stud, provided with the kit, is threaded into a de-
energized 600 A bushing.
The assembled housing is then connected to the apparatus bushing using an
O&T/torque tool. The T-OP II connector’s unique captured rotating nut feature
provides ease of removal of the T-OP II system from the apparatus bushing.
(See Table 6 for information on tools.) Refer to Installation Instruction
Sheet MN650051EN for details.
Production tests
Tests are conducted in accordance with IEEE Std 386-2016:
- ac 60 Hz 1-minute withstand
- 50 kV/70 kV
- Minimum partial discharge extinction voltage
- 26 kV
Tests are conducted in accordance with Eaton requirements:
- Physical inspection
- Periodic dissection
- Periodic fluoroscopic analysis
Table 1. Voltage ratings and characteristics
Description | kV |
---|---|
Standard voltage class | 35 |
Maximum rating phase-to-phase (loadbreak-reducing tap plug only) | 36.6 |
Maximum rating phase-to-ground | 21.1 |
ac 60 Hz 1-minute withstand
150 kV BIL Class T-OP II
200 kV BIL Class T-OP II| 50
70
dc 15-minute withstand| 103
BIL and full wave crest| 150/200
Minimum partial discharge extinction voltage| 26
Note: N Voltage ratings and characteristics meet or exceed IEEE Std 386-2016.
Table 2. Current ratings and characteristics
Description | Amperes |
---|
600 A Interface
Continuous| 600/900 A rms
24-hour overload| 1000 A rms
Short time| 40,000 A rms symmetrical for 0.20 s 27,000 A rms symmetrical for 4
s
200 A Interface 1
Continuous| 200 A rms
Switching 2| 10 operations at 200 A rms at 21.1 kV
Fault closure| 10,000 A rms symmetrical at 36.6 kV for 0.17 s
Short time| 10,000 A rms symmetrical for 0.17 s 3500 A rms symmetrical for 3 s
1 System design and protection must recognize the ratings of 200 A interface.
2 Switching rating limited to single-phase 21.1 kV.
Note: Current ratings and characteristics meet or exceed IEEE Std
386-2016.
600 A 35 kV Class T-OP II deadbreak connector
Features and benefits
Figure 1. T-OP II cutaway design features
Note: Dimensions are in inches (mm) and are for reference only.
Optional features
Protective cap
200 A insulated protective cap fits over loadbreak-reducing tap plug for dead
front shielding.
Capacitive test point
Capacitive test point on molded T-body, with snap-on cap, provides a place to
mount Eaton’s Cooper Power series STVT, STLO, and STHI faulted circuit
indicators.
Copper alloy stud
The Copper alloy stud with its extended length allows for threading into the
connector prior to mating the bushing and terminator interfaces. Blunt start
threads on the stud help eliminate crossthreading. Stud threads into an
industry-standard 600 A bushing.
T-wrench
The T-wrench is used to install the loadbreak-reducing tap plug into the
compression connector and T-body.
Torque tool
The torque tool is required to check the torque of a 35 kV Class T-OP II
deadbreak connector or bushing adapter when it is installed on a 600 A bushing
interface. It is precision calibrated and hotstick operable.
Combination operating and test/torque tool
The combination operating and test/torque tool is used with a hot stick to
test for circuit de-energization and to install and remove a 35 kV Class LRTP
equipped connector from an apparatus tap. The standard tool is equipped with a
molded EPDM rubber cap and torque limiter to allow proper tool seating and
gripping of the T-OP II connector. It also ensures that the connector has been
properly torqued into the mating bushing.
5/16-inch hex shaft
5/16-inch hex shaft with 3/8-inch socket drive tool.
Ordering information
Each BOL-T connector kit contains:
- Molded rubber T-body
- Insulating plug
- Cap
- Compression or shear bolt connector
- Cable adapter
- Silicone lubricant
- Installation instruction sheet
A 35 kV T-OP II connector is available with or without a protective cap and with or without the test point. Use the following procedure to develop the correct part number for the desired T-OP II connector kit, based on cable size, conductor size, and desired options.
T-OP II connector kit—catalog numbering system
Build the 8- to 10-digit catalog number for a T-OP II kit by following the
steps given below. The first 3 digits are “TP6”, so only digits 4 through 8
need to be selected. Digits 9 and 10 are optional.
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 10 |
---|---|---|---|---|---|---|---|---|---|
T | P | 6 |
Catalog number digits:
1 and 2 — “TP” = T-OP II connector system
3 — “6” = 600 A system
Step 1. Select digits 4 and 5 150 kV BIL or 200 kV BIL version
“35” = 35 kV class bushing interface, 150 kV BIL
“38” = 35 kV class bushing interface, 200 kV BIL
Step 2. Select digit 6 cable adapter range code
Determine the cable’s diameter over the electrical insulation as shown in
Figure 3 (including tolerances).
Then identify a cable range from Table 3 that covers the minimum and maximum
insulation diameters. Select the correct cable range code from Table 3.
Table 3. Cable diameter range
Inches | mm | Cable range code |
---|---|---|
0.875–0.985 | 22.2–25.0 | D |
0.930–1.040 | 23.6–26.4 | E |
0.980–1.115 | 24.9–28.3 | F |
1.040 –1.175 | 26.4–29.8 | G |
1.095 –1.240 | 2 7.8 – 31.5 | H |
1.160 –1.305 | 29.5–33.1 | J |
1.220 –1.375 | 31.0–34.9 | K |
1.285 –1.395 | 32.5–35.4 | L |
1.355 –1.520 | 34.4–38.6 | M |
1.485 –1.595 | 3 7.7– 4 0.5 | N |
1.530 –1.640 | 38.9 – 41.7 | P |
1.575 –1.685 | 40.0–42.8 | Q |
1.665 –1.785 | 42.3–45.3 | R |
1.755 –1.875 | 4 4.6 – 47.9 | S |
1.845 –1.965 | 46.9–50.0 | T |
1.960 –2.210 | 49.8–56.1 | U |
Step 3. Select digits 7 and 8 conductor code
Identify the conductor size and type in Table 4 (compression) or Table 5
(shear bolt) and select the conductor code from the appropriate column.
Table 4. Compression connector
AWG or kcmil| mm
2| AWG or kcmil| mm
2| Conductor code
---|---|---|---|---
No connector| | | 0
2| 35| 1| —| 11
1| —| Jan-00| 50| 12
Jan-00| 50| Feb-00| 70| 13
Feb-00| 70| Mar-00| —| 14
Mar-00| —| Apr-00| 95| 15
Apr-00| 95| 250| 120| 16
250| 120| 300| —| 17
300| —| 350| —| 18
350| —| 400| 185| 19
400| 185| 450| —| 20
450| —| 500| 240| 21
500| 240| 600| 300| 22
600| 300| 700| —| 23
650| —| 750| —| 24
750| —| 900| —| 25
900| —| 1000| 500| 26
1000| 500| —| —| 27
1250| 630| 1250| —| 28
Table 5. Shear bolt connector
Cable conductor size
Compact| Compressed| Concentric| mm²
standard **sizes| Conduct code| Catalog number
---|---|---|---|---|---
1/0| 1/0| 1/0| 50| S1| CDT630SB150T
2/0| 2/0| 2/0| 70| |
3/0| 3/0| 3/0| —| |
4/0| 4/0| 4/0| 95| |
250| 250| 250| 120| |
350| —| —| 150| |
—| 350| 350| 185| S3| CDT630SB300T
500| 500| 500| 240| |
600| 600| 600| 300| |
700| —| —| —| |
—| 700| 700| —| S4| CDT630SB400T
750| 750| 750| —| |
800| 800| —| 400| |
900| —| —| —| |
—| —| 800| —| S6| CDT1250SB630T
—| 900| 900| —| |
1000| 1000| 1000| 500| |
—| 1100| 1100| —| |
—| 1200| 1200| —| |
—| 1250| 1250| 630| |
—| 1300| 1300| —| S8| CDT1250SB800T**
—| 1400| 1400| —| |
—| 1500| 1500| 800| |
Figure 3. Typical construction of medium-voltage underground cable
Step 4. Select digit 9 and 10 (optional)
“TC” = T-OP II connector kit with a capacitive test point and protective cap
“C” = T-OP II connector kit with a protective cap (no capacitive test point)
Blank = T-OP II connector kit without capacitive test point or protective cap
Example
Select a 200 kV BIL T-OP II connector kit without a capacitive test point,
with a protective cap for a 4/0 compressed cable with a nominal insulation
diameter of 1.26 inches.
Step 1. Select digits 4 and 5
Kit requires 200 kV BIL bushing interface.
Select “TP638”
Step 2. Select digit 6
Nominal diameter over the insulation is 1.26 ± 0.030 inches minimum diameter =
1.26 – 0.030 = 1.23 inches maximum diameter = 1.26 + 0.030 = 1.29 inches From
Table 3, identify the cable range 1.23 – 1.29 inches and select the “J” or “K”
cable range code.
Step 3. Select digits 7 and 8
The conductor size is a 4/0 compressed. From Table 4, under the column
“Concentric or compressed,” identify 4/0 and select the “16” conductor code.
Step 4. Select digit 9
The kit should have a protective cap. Select a “C” for digit 9.
Order catalog number: TP638J16C.
Accessories
To order replacement compression connectors, shear bolts, and cable adapters
for a T-OP II connector system, see Catalog Data CA650006EN, “Deadbreak
Accessories, Tools,
and Replacement Parts.”
Table 6. Replacement parts and tools
Description | Catalog number 150 kV BIL | 200 kV BIL |
---|---|---|
T-body without test point | DT635 | DT638 |
T-body with test point | DT635T | DT638T |
Loadbreak-reducing tap plug (LRTP) | LRTP635 | LRTP638 |
Operating and test/torque tool with cap | OTTQ635 | OTTQ635 |
Installation torque tool | TQHD635 | TQHD635 |
5/16-inch T-wrench | TWRENCH | TWRENCH |
Copper alloy stud for use with T-OP II | STUD-T | STUD-T |
200 A, 35 kV class insulated protective cap | LPC235 | LPC238 |
5/16-inch threaded coppertop connector | CC6C1T | CC6Ca1T |
Cable adapters | CA6352 | CA6382 |
5/16-inch hex shaft with 3/8-inch drive socket | HD635 | HD635 |
Operating and test tool with cap | OT635 | OT635 |
1 Use Table 4 and/or Table 5 for conductor code.
2 Use Table 3 to select cable range code.
Catalog Data CA650055EN
Effective July 2022
600 A 35 kV Class T-OP II
deadbreak connector
Eaton
1000 Eaton Boulevard
Cleveland, OH 44122
United States
Eaton.com
Eaton’s Power Systems Division
2300 Badger Drive
Waukesha, WI 53188
United States
Eaton.com/cooperpowerseries
© 2022 Eaton
All Rights Reserved
Printed in USA
Publication No. CA650055EN / Z26565
July 2022
Eaton is a registered trademark.
All other trademarks are property of their respective owners.
EATON www.eaton.com
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>