EMERSON CC200 Controller Hardware and Wiring User Guide
- June 7, 2024
- Emerson
Table of Contents
EMERSON CC200 Controller Hardware and Wiring
Functions of the CC200
- Low, medium, and dual temperature case types supported.
- Stepper Valve Driver Onboard.
- EEPR control based on pressure or temperature.
- New patent pending floating evaporator SST setpoint management automatically adjusts evaporator SST to the optimum setpoint for discharge air.
- Case Display with touchscreen.
- Form C relays allow direct control of case loads and simplified wiring.
- Simplified wiring and connections reduce labor and setup time.
- Bluetooth® connectivity for easy controller status and service.
CC200 Main Controller Specifications
N a m e| D e s c r i p t
i o n
---|---
Power Requirement| 24VDC 71(Earth) – 72(+) – 73(-)
Mounting| DIN Rail
Dimensions| 7 3/16″x 4 5/16″x 3″ (W x H x D)
__
__
__
Serial Port
| Master/slave, 1/8 load, up to 115.2K Baud, isolated; generic 150-ohm
termination with switch. 3-Terminal connector with onboard 100-ohm between
RS485 “C” Terminal and RS485 isolated ground to allow direct earth ground
connection. The RS485 Port B Gnd is isolated from RS485 Port A Gnd and all
other circuit and earth grounds.
ETH1 ETH2| BACnet TCP/IP repeater (Ethernet 10/100) BACnet TCP/IP repeater
(Ethernet 10/100)
Operating Temperature| 14°F to 122°F (-10°C to 50°C)
Relative Humidity| 20-85% RH; non-condensing
Power Supply Wiring and Specifications
Power Supply Specifications
Primary Power| 120VAC
Secondary Power| 24VDC
CC200 Power Requirement| 24VDC 60W
Required Power Supply| CC200 Power Supply
24VDC 60W Emerson P/N 810-3182
Power Supply Terminals| 2 (-V) & 3 (+V)
CC200 Power Terminals| 72(+) –73(-) — 71(Earth)
Wire Spec| 16AWG
24VDC Max Wire Length| 20”
Mounting| DIN Rail Mounted
Power Supply Dimensions| 2.06” x 3.54” x 2.14” (W x H x D)
Step 1: Mount Power Supply and CC200 Main Controller to DIN Rail.
Step 2: Wire Secondary power from Power Supply to CC200 Main Controller.
a. Reference specification and drawing for Terminals.
b. This is Polarity Sensitive.
Step 3: Wire Primary power to Power Supply.
a. Reference the specification and drawing for Terminals.
CC200 Main Controller Output Wiring
Note : Fan motors over 5 amps must use the alternate wiring method with a pilot device between CC200 and the motor
Step 1: Verify power is OFF on the CC200 Main Controller.
Step 2: Refer to the specification drawing below for the correct
termination terminals and how to wire:
For Fan Motors Over 5A
CC200 Main Controller Output Specifications
R e l a y S p e c i f i c a t i o n s
__
CC200 L a b e l
| __
A M P / V A C
| L O A D S C O N TRO L L E D| __
TE R M I N A L S
__
__
__
__
Fan/CT
| Form C Relay with built in CT:
N O : Resistive 5A, 240Vac or less;
5FLA, 30LRA, 240Vac
or less;
Pilot Duty B300 N C : Resistive 5A , 240Vac or less;
5FLA, 30LRA, 240Vac
or less;
Pilot Duty C300
| __
__
__
__
Evap Fans
| __
__
__
__
4(C) – 5(NO) – 6 (NC)
Defrost| Form C Relay
N O : Resistive 12A, 240Vac or less;
10FLA, 60LRA, 240Vac
or less;
Pilot Duty B300 N C : Resistive 12A, 240Vac or less;
5FLA, 30LRA, 240Vac
or less;
Pilot Duty C300
| Defrost Heaters| 7(C) – 8(NO) – 9(NC)
Light| Case Lights| 10(C) – 11(NO) – 12(NC)
Refrig| LLSV| 13(C) – 14(NO) – 15(NC)
__
__
AUX Relay
| Alarm Out, Door Alarm, Satellite for E2E control, backup for other RO| __
__
16(C) – 17(NO) – 18(NC)
__
__
AO1 (AO)
| __
__
4-20mA or 0-10VDC
| Satellite for E2E control, f u t u r e L i g h t D i mm i n g , f u t u r e A n t i – sweat| __
__
39(+) – 40(-)
AO2 (AO)| 4-20mA or 0-10VDC| F u t u r e L i g h t D i mm i n g| 41(+) – 42(-)
CC200 Main Controller Input Specifications
I n p u t S p e c i f i c a t i o n s
CC200 L a b e l| D e s c r i
p t i o n| TE R M I N A L
S & C O L O R
DAT| Discharge Air| 46 – 47 G r e e n
TERM| Defrost Termination| 48 – 49 Or a n g
e
RAT| Return Air| 50 – 51 P u r p l e
COIL OUT| Coil Out| 52 – 53
__
PRESSURE
| 100lb Pressure Transducer
P o l a r i t y se n sit i v e
| 43(0v) – 44(Sig) –
45(+5V)
Black – White – Red
Def CT Amps| Defrost Amps (electric defrost only)| 54(+) – 55(-)
A u x I n p u t s A I & D
I
AI1 AI2| Configurable functions: External fan CT, Coil Inlet Temp, Product
Temp, Circuit Suction Temp| 56(+) – 57(-)
58(+) – 59(-)
DI1 DI2 DI3 DI4| Door switch, service switch, dual temp switch, defrost term switch, leak shutdown, satellite 1 for E2E, satellite 2 for E2E| 31(DI1) – 32(C)
33(DI2) – 34(C)
35(DI3) – 36(C)
37(DI4) – 38(C)
W i r e S p e c i f i c a t i o n s f o r e x t e n din g I n pu t a n d V a l v e s
__
Analog Temp Sensors or Digital Inputs
| General Cable 92454A #22/2 Shielded
E m e r so n P / N 135 – 0600
I f m a n u f a c t u r e r h ar n e ss must be extended, join wires with heat shrink and solder.
__
Pressure Transducer
| Belden 28326AS #18/4 Shielded
E m e r so n P / N 135 – 2832
I f m a n u f a c t u r e r h ar n e ss must be extended, join wires with heat shrink and solder.
CC200 Input Wiring
Step 1: Make sure the power is OFF to the CC200 Main Controller.
Step 2: Determine what sensors will be needed and wire per the
specification above.
a. If sensor need to be extended Emerson only supports heat shrink and solder.
Step 3: Determine how many coils are on the cases.
a. For multi-coil cases the CC200 supports one sensor per coil for discharge
air, return air, defrost termination and coil outlet. Pressure transducers for
multi-coil cases may be installed one per coil or one for the entire case
(parameter selectable).
b. For multi-coil cases the sensors on coil #1 will terminate on the CC200
Main Controller. Second and third sensor coils will require an Expansion
Module per coil and each coil’s sensor will terminate on the each of the
Expansion Modules.
CC200 Stepper Valve Wiring and Specifications
S t e p p e r V a l v e ( S p o r l a n C D S O n l y )
Stepper Valve
|
Bipolar
| W2
76(White) – 77(Black)
W1
78(Red) – 79(Green)
Stepper Valve – Expansion Module
|
Bipolar
| W2
33 (White) – 34 (Black)
W1
35 (Red) – 36 (Green)
Step 1: Make sure the power is OFF to the CC200 Main Controller.
Step 2: The CC200 Case control system (Main Controller + Expansion
Modules) supports Electronic Expansion Valve (EEV) control using either Pulse
Width Modulation (PWM) valves OR Stepper valves but NOT both.
The first case in a CC200 lineup (“a” Case) has support for control of
Electronic Evaporator Pressure Regulation (EEPR) stepper valve.
-
PWM EEV 1 or Stepper EEV 1 is always located on CC200 Main Controller
-
PWM EEV 2 or Stepper EEV 2 is always located on Expansion Module 1
-
PWM EEV 3 or Stepper EEV 3 is always located on Expansion Module 2
EEPR Location -
When PWM EEV is used, EEPR is always located on CC200 Main
Controller Stepper terminals -
When Stepper EEV is used, EEPR is located on the last Expansion
Module Stepper terminals
a. The wiring specification above is only for the Sporlan CDS and SER valves.
b. If other manufacturer valves are used, refer to the manufacturer’s
specification and contact Emerson for instructions on how to terminate.
Step 3: Refer to the drawing and specification for termination of the valve:
CC200 Expansion Module Wiring and Specifications
CC200L a b e l| D e s c r i
p t i o n| TE R M I N A L
S & C O L O R
---|---|---
DAT| Discharge Air| 16 – 17 G r e e n
TERM| Defrost Termination| 18 – 19 Or a n g
e
RAT| Return Air| 20 – 21 P u r p l e
COIL OUT| Coil Out| 22 –23
PRESSURE
| 100lb Pressure Transducer P o l ar i t y se n sit i v e| 12(0v) – 13(Sig) – 14(+5V)
Black – White – Red
W i r e S p e c s f o r E
x t e n d i n g I n pu t s
a n d V a l v e s
Analog Temp Sensors or Digital Inputs| Heat Shrink and Solder
General Cable 92454A #22/2 Shielded.
E m e r so n P / N 135 – 0 600
Pressure Transducer
| Heat Shrink and Solder Belden 28326AS #18/4 Shielded.
E m e r so n P / N 135 – 2 832
Stepper Valve
| Heat Shrink and Solder
Use the manufacturer harness with a max length not to exceed 30ft (9 meters).
Belden 28326AS #18/4
E m e r so n P / N 135 – 2 832
Step 1 : Determine if you need an Expansion Module.
a. You will add an Expansion for a second or third coil. Each coil will have
temp sensors and a transducer and will be wired to the respective Expansion
Module.
Step 2: Addressing the Expansion Module
a. Set the address of each Expansion Module using the ON/OFF dip switch bank
on the top left corner of the hardware (refer to figure below).
b. Expansion Module one must be set to address 1, Expansion Module two to
address 2, Expansion Module three to address 3.
Step 3: Install the Expansion Module.
a. Make sure power is OFF to the CC200 Main Controller. Power will be restored
in a later step.
b. Install Expansion Module 1 on the DIN rail adjacent to the CC200’s right
side. The CC200 Expansion port terminal V+ should be aligned with Expansion
Module 1 Expansion port terminal V+. Slide the Expansion Module into the CC200
Expansion port so both device’s Expansion port connectors fasten together.
c. If Expansion Modules 2 and 3 are present, connect to Expansion Module 1’s
Expansion port using in the same manner described in the above step. No wiring
is needed between the CC200 Main Controller and CC200 Expansion
Module. Power and communication are sourced from the CC200 Expansion port and
passed through each Expansion Module Expansion port.
Step 4: Terminate sensors on the Expansion Module and refer to the
drawing and specifications above for terminal numbers and how to terminate.
Once all sensor terminations are complete and the Expansion Module Expansion
port is securely plugged into the CC200 Expansion port, restore the 24VDC
supply power to the CC200 Main Controller. Once connected, the Expansion
Module PWR ON LED will illuminate green indicating supply power is
present.
CC200 Case Display
CC 20 0 D i s p l a y S p e c i f i c a t i o n s
Power Requirement| Powered from the CC200 Case Controller
Required Wire| Belden #8771 3C22AWG or Belden #8772 3C22AWG
Mounting| Use the white sliding clips that are provided with the CC200 Display
Operating Temp| UL: 32°F to 131°F / UL: 0°C to 55°C
Relative Humidity| 20 to 85 RH% (non-condensing humidity)
Protection| Body: IP20; Front: IP66
P o i n t s| C C200 Te r m i
n a l s t o C C200 D i s pl
a y Te r m i n a l s
–| 27(-) to 5(-)
+| 28(+) to 4(+)
VNR| 29(VNR) to 3(VNR)
Step 1: Make sure power to the CC200 Main Controller is turned OFF.
Step 2: Make termination from the CC200 Main Controller to the CC200
Display.
a. It is critical that these terminations are made correctly as this can
result in damage to both devices if not terminated correctly.
b. Clip and insulate shield at both ends of the Belden connection cable. Keep
cable length at less than 50 ft (15 meters).
Step 3: Power ON the CC200 Main Controller.
Part Numbers for Ordering
*** E m e r s o n P a r t N
u m b e r| D e s c r i p
t i o n**
---|---
810-3180| CC200 Main Controller
810-3181| CC200 Expansion Module
810-3182| CC200 Power Supply 24VDC 60W
E m e r so n P / N 8 10 – 3182
810-3183| CC200 Case Display
501-1122| Discharge Air Temperature Sensor
501-1127| Defrost Termination Temperature Sensor
501-1128| Return Air Temperature Sensor
501-1125 (blue)
501-1126 (red)
| Coil Out Temperature Sensor
800-2100| 100lb Pressure Transducer
*For optimal performance of the CC200, Emerson parts are required.
Cold Chain Connect is the CC200 mobile application for setting parameters, graphing inputs and outputs, setting service overrides, and viewing alarms. Cold Chain Connect provides a window into CC200 operation and diagnostics directly at the location of the refrigerated fixture or walk-in box. Download Cold Chain Connect from the App Store at Apple: https://www.apple.com/ios /app-store
This document may be photocopied for personal use. Visit our website at
http://www.climate.emerson.com for the latest technical documentation and
updates.
Join Emerson Technical Support on Facebook
http://on.fb.me/WUQRnt
For Technical Support call 479-845-3430
or email
ColdChain.TechnicalServices@Emerson.com
The contents of this publication are presented for informational purposes only
and they are not to be construed as warranties or guarantees, express or
implied, regarding the products or services described herein or their use or
applicability. Emerson Retail Solutions, Inc. and/or its affiliates
(collectively “Emerson”), reserves the right to modify the designs or
specifications of such products at any time without notice. Emerson does not
assume responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use and maintenance of
any product remains solely with the purchaser and end-user. Emerson is a
trademark of Emerson Electric Co. ©2020 Emerson Retail Solutions, Inc. All
rights reserved.
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>