CyberPower CP1000AVRL Intelligent LCD UPS
Product Information: CP1000AVRL UPS
The CP1000AVRL is a UPS (Uninterruptible Power Supply) system designed by
CyberPower Systems. It provides reliable power protection, operation, and
performance for your electronic devices. The UPS features automatic voltage
regulation (AVR) to stabilize inconsistent utility power voltage and ensure
safe levels for your equipment. It also offers surge protection and battery
backup during power outages, allowing you to save your open files and safely
shut down your computer system.
Key Features
- Product Model: CP1000AVRL
- Surge Protection: 1080 Joules
- Battery Backup: Long-lasting maintenance-free batteries
- Automatic Voltage Regulation (AVR): Stabilizes utility power voltage to safe levels
- Power Capacity: 1000VA/550W
Product Usage Instructions
Determining Power Requirements
Before using the UPS, ensure that the equipment you connect to it does not
exceed its rated capacity of 1000VA/550W. Exceeding the rated capacity may
cause an overload condition, leading to UPS shutdown or circuit breaker
tripping. It is recommended to keep the load placed on the battery outlets
below 80% of the unit’s capacity.
Hardware Installation Guide
- Upon receiving the UPS, it is recommended to charge the battery for at least 8 hours to ensure maximum charge capacity.
- The UPS has an auto-charge feature, which charges the battery automatically when plugged into an AC outlet, regardless of whether the UPS is turned on or off.
- Note: The UPS has a safety feature that prevents it from being turned on during shipment.
Plugging In and Powering On
The first time you turn on the UPS, make sure it is connected to an AC power
source, or it will not power up. The power switch on the UPS is used as the
master on/off switch for the equipment connected to the battery power-supplied
outlets. By following these instructions, you can ensure proper installation
and usage of the CP1000AVRL UPS, providing reliable power protection and
backup for your valuable electronic devices.
PRODUCT REGISTRATION
Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at: www.cyberpowersystems.com/registration. Registration certifies your product’s warranty, confirms your ownership in the event of a product loss or theft, and entitles you to free technical support. Register your product now to receive the benefits of CyberPower ownership.
IMPORTANT SAFETY INSTRUCTIONS
This Manual Contains Important Instructions that should be followed during the
Installation and Maintenance of the UPS and batteries. CAUTION! To prevent the
risk of fire or electric shock, install in a temperature and humidity-
controlled indoor area free of conductive contaminants. (Please see
specifications for acceptable temperature and humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover
except to service the battery. Turn off and unplug the unit before servicing
the batteries. There are no user-serviceable parts inside except for the
battery.
CAUTION! Hazardous live parts inside can be energized by the battery even
when the AC input power is disconnected.
CAUTION! The UPS must be connected to an AC power outlet with a fuse or
circuit breaker protection. Do not plug into an outlet that is not grounded.
If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electric shock, turn off the unit and unplug it from
the AC power source before servicing the battery.
CAUTION! To reduce the risk of fire, connect only to a circuit provided
with 20 amperes maximum branch circuit over current protection in accordance
with the National Electric Code, ANSI/NFPA 70.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does not
sell products for life support or medical applications. DO NOT use in any
circumstance that would affect the operation and safety of life support
equipment, medical applications, or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric
shock, do not use with or near an aquarium. Condensation from the aquarium can
cause the unit to short out.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or
electric shock, do not use the unit on any transportation such as airplanes or
ships. The effect of shock or vibration caused during transit and the damp
environment can cause the unit to short out.
INSTALLING YOUR UPS SYSTEM
INTRODUCTION
Thank you for selecting a CyberPower Systems UPS product. This UPS is designed
to provide unsurpassed power protection, operation and
performance during the lifetime of the product.
UNPACKING
Inspect the UPS upon receipt. The box should contain the following: UPS (b)
User’s manual (c) USB A+B type cable
PowerPanel® Personal software is available on our website. Please visit
www.cyberpowersystems.com and go to the
Software Section for free download.
OVERVIEW
The CP1000AVRL provides complete power protection from utility power that is
not always consistent. The CP1000AVRL features 1080 Joules of surge
protection. The unit provides long-lasting battery backup during power outages
with maintenance-free batteries. The CP1000AVRL ensures consistent power to
your computer system and includes software that will automatically save your
open files and shut down your computer system during a utility power loss.
AUTOMATIC VOLTAGE REGULATOR
The CP1000AVRL stabilizes inconsistent utility power voltage to nominal levels
that are safe for equipment. Inconsistent incoming utility power may be
damaging to important data files and hardware, but with Automatic Voltage
Regulation (AVR), damaging voltage levels are corrected to safe levels. AVR
automatically increases low utility power to a consistent and safe 110/120
volts
HOW TO DETERMINE THE POWER REQUIREMENTS OF YOUR EQUIPMENT
- Ensure that the equipment plugged into the outlet does not exceed the UPS’s rated capacity (1000VA/550W for CP1000AVRL).
- Note: This UPS is designed with a safety feature to keep the system from being turned on during shipment. The first time you turn the UPS on, you will need to have it connected to AC power or it will not power up.
- With the UPS unit turned off and unplugged, connect your computer, monitor, and any other peripherals requiring battery backup to the battery power-supplied outlets. DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump, or other large electrical devices into the “Battery and Surge Protected Outlets”. The power demands of these devices may overload and damage the UPS.
- Plug the UPS into a 2-pole, 3-wire grounded receptacle (wall outlet). Make sure the wall branch outlet is protected by a fuse or circuit breaker and does not service equipment with large electrical demands (e.g. air conditioner, copier, etc.). The warranty prohibits the use of extension cords, outlet strips, and surge strips.
- Press the power switch to turn the unit on. The Power On indicator light will illuminate and the unit will “beep”. If an overload is detected, an audible alarm will sound and the unit will emit one long beep. To correct this, turn the UPS off and unplug at least one piece of equipment from the battery power-supplied outlets. Make sure the circuit breaker is depressed and then turn the UPS on.
- To maintain optimal battery charge, leave the UPS plugged into an AC outlet at all times.
- To store the UPS for an extended period, cover it and store it with the battery fully charged. While in storage, recharge the battery every three months to ensure battery life.
- Ensure the wall outlet and UPS are located near the equipment being attached for proper accessibility
BASIC OPERATION
-
Power Switch
Used as the master on/off switch for equipment connected to the battery power- supplied outlets. -
MUTE button
The button can be used to mute battery mode alerts and to set up sensitivity. For more information, please refer to the” Function -
Setup Guide” section.
Pressing the button will turn off / on the battery mode alarm, including on battery / low battery warnings. To turn the alarm off, press the MUTE button. You will hear two short beeps when the alarm is turned off. To turn the alarm back on, press the MUTE button. You will hear a short beep when the alarm is turned on. -
LED Indicators
The LEDs indicators show the UPS status, including On-Line / On Battery / AVR and Overload. -
Battery and Surge Protected Outlets
The UPS has five battery-powered/surge suppression outlets for connected equipment to ensure temporary uninterrupted operation of your equipment during a power failure. (DO NOT plug a laser printer, paper shredder, copier, space heater, vacuum, sump pump or other
Thank you for purchasing a CyberPower product. Please take a few minutes to register your product at: www.cyberpowersystems.com/ registration. Registration certifies your product’s warranty, confirms your ownership in the event of a product loss or theft, and entitles you to free technical support. Register your product now to receive the benefits of CyberPower ownership.
(SAVE THESE INSTRUCTIONS)
This Manual Contains Important Instructions that should be followed during the
Installation and Maintenance of the UPS and batteries.
CAUTION! To prevent the risk of fire or electric shock, install in a
temperature and humidity-controlled indoor area free of conductive
contaminants. (Please see specifications for acceptable temperature and
humidity range).
CAUTION! To reduce the risk of electric shock, do not remove the cover
except to service the battery. Turn off and unplug the unit before servicing
the batteries. There are no user-serviceable parts inside except for the
battery.
CAUTION! Hazardous live parts inside can be energized by the battery even
when the AC input power is disconnected.
CAUTION! The UPS must be connected to an AC power outlet with a fuse or
circuit breaker protection. Do not plug into an outlet that is not grounded.
If you need to de-energize this equipment, turn off and unplug the unit.
CAUTION! To avoid electric shock, turn off the unit and unplug it from
the AC power source before servicing the battery.
CAUTION! To reduce the risk of fire, connect only to a circuit provided
with 20 amperes maximum branch circuit over current protection in accordance
with the National Electric Code, ANSI/NFPA 70.
DO NOT USE FOR MEDICAL OR LIFE SUPPORT EQUIPMENT! CyberPower Systems does
not sell products for life support or medical applications. DO NOT use in any
circumstance that would affect the operation and safety of life support
equipment, medical applications, or patient care.
DO NOT USE WITH OR NEAR AQUARIUMS! To reduce the risk of fire or electric
shock, do not use with or near an aquarium. Condensation From the aquarium can
cause the unit to short out.
DO NOT USE THE UPS ON ANY TRANSPORTATION! To reduce the risk of fire or
electric shock, do not use the unit on any transportation such as airplanes or
ships. The effect of shock or vibration caused during transit and the damp
environment can cause the unit to short out. large electrical devices into the
“Battery and Surge Protected Outlets”. The power demands of these devices may
overload and damage the unit.)
Full-Time Surge Protection Outlets
The UPS has four surge suppression outlets.
Circuit Breaker
Located on the back of the UPS, the circuit breaker serves to provide overload
and fault protection.
Wiring Fault Indicator (red)
This LED indicator will illuminate to warn the user that a wiring problem
exists, such as bad ground, missing ground or reversed wiring. If this is
illuminated, disconnect all electrical equipment from the outlet and have an
electrician verify the outlet is properly wired. The UPS will not provide
surge protection without being plugged into a grounded and properly wired wall
outlet.
USB Ports to PC
The USB port allows connection and communication between the USB port on the
computer and the UPS unit.
REPLACING THE BATTERY
-
Replacement of batteries located in an OPERATOR ACCESS AREA.
-
When replacing batteries, replace with the same number of the following battery: CyberPower / RB1290 for CP1000AVRL.
-
CAUTION! Risk of Energy Hazard, 12 V, maximum 9 Ampere-hour battery for CP1000AVRL. Before replacing batteries, remove
conductive jewelry such as chains, wristwatches, and rings. High energy conducted through these materials could cause severe burns. -
CAUTION! Do not dispose of batteries in a fire. The batteries may explode.
-
CAUTION! Do not open or mutilate batteries. Released material is harmful to the skin and eyes. It may be toxic.
-
CAUTION : A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed when working on batteries
-
Remove watches rings, or other metal objects.
-
Use tools with insulated handles.
CAUTION – RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE.
DISPOSE OF USED BATTERIES ACCORDING
TO LOCAL REGULATIONS.
BATTERY REPLACEMENT PROCEDURE
- Turn off and unplug all connected equipment.
- Turn the UPS off and unplug it from the AC power source.
- Turn the UPS on its side.
- Remove the front panel retaining screws located on the bottom of the UPS.
- Slide the battery compartment cover (front panel) completely off of the unit.
- Disconnect the battery wires from the batteries.
- Remove the batteries from the compartment. Slide the remaining battery from left to right and remove it from the compartment.
- Disconnect the battery wires from the remaining battery.
- Install the replacement batteries by connecting the red wire (+) and the black wire (-) to the same color connectors.
- Slide back the battery compartment cover and tighten the retaining screws.
- Recharge the UPS for 8-16 hours to fully charge the battery.
REMINDER : Batteries are considered HAZARDOUS WASTE and must be disposed of properly. Most retailers that sell lead-acid batteries collect used batteries for recycling, as required by local regulations.
DEFINITIONS FOR ILLUMINATED LED INDICATORS
Indicators Illuminate | Sensitivity | Description |
---|
1
(Red)
|
Low
| If the connected equipment can tolerate more power events (example: unstable
power often associated with stormy weather), select Low Sensitivity and the
UPS will go to Battery Mode less often.
2
(Yellow, Red)
| Medium (Default)|
The UPS will go to Battery Mode if the power is unstable.
3
(Green, Yellow, Red)
|
High
|
If the connected equipment is more sensitive to power events, select High Sensitivity and the UPS will go to Battery Mode more often.
FUNCTION SETUP GUIDE – SENSITIVITY SETUP
In line mode, the AC input voltage may not be stable all the time, to prevent the connected equipment from damage caused by unexpected voltage fluctuations, please adjust the sensitivity of the unit by the steps as follows:
- Please make sure that the UPS is in LINE MODE.
- To Enter the Sensitivity Setup mode, press the MUTE Button for 6 seconds until all indicators flash rapidly.
- The unit will show the current sensitivity setting, as shown in the following table.
- To select the Low Sensitivity setting: shortly press the MUTE button until one red indicator flashes.
- To select the Medium Sensitivity setting, shortly press the MUTE button until red and yellow indicators flash.
- To select the High Sensitivity setting, shortly press the MUTE button until green, yellow and red indicators flash.
- To set up a level of sensitivity, hold down the MUTE button until the green indicator (the first one) illuminates.
- Once in setup mode, if there is no action within 7 seconds, the unit will exit setup mode without changing any settings.
TROUBLESHOOTING
Problem | Possible Cause | Solution |
---|
Circuit breaker button is projecting from the back of
the unit.
|
Circuit breaker has tripped due to an overload.
| Turn the UPS off and unplug at least one piece of equipment. Wait 10 seconds, reset the circuit breaker
by depressing the button, and then turn the UPS on.
The UPS does not perform expected runtime.
| Battery not fully charged.| Recharge the battery by leaving the UPS plugged
in.
Battery is worn out.| Please contact CyberPower Systems about replacement
batteries.
The UPS will not turn on.
| The on/off switch is designed to prevent damage from rapidly turning it off
and on.| Turn the UPS off. Wait 10 seconds, and then turn the UPS on.
The unit is not connected to an AC outlet.| The unit must be connected to a
120V 60Hz outlet.
The battery is worn out.| Please contact CyberPower Systems about replacement
batteries.
Mechanical problem.| Please contact CyberPower Systems.
PowerPanel® Personal software is inactive (all icons are gray).
|
The USB / serial cable is not connected.
| Connect the USB / serial cable to the UPS unit and an open USB / serial port on the back of the computer.
You must use the cable that came with the unit.
The USB / serial cable is connected to the wrong port.| Check the back of the computer for an additional USB / serial port. Move the cable to this port.
The unit is not providing battery power.
| Shutdown your computer and turn the UPS off. Wait 10 seconds and turn the UPS back on. This should
reset the unit.
Additional troubleshooting information can be found under “Support” at www.cyberpowersystems.com
TECHNICAL SPECIFICATIONS
*Runtime based on testing fully-charged, new batteries at normal operating conditions. The runtime curve is approximate and varies based on battery age, level of charge at test, environment, and other variables.
SYSTEM FUNCTIONAL BLOCK DIAGRAM
Model(s)
| CP1000AVRL
---|---
Capacity| 1000VA / 550W
Nominal Input Voltage| 120V
Input Frequency| 60 Hz ± 3 Hz
On-Battery Output Voltage| 120Vac ± 5%
Max. Load for UPS Outlets (5 Outlets)| 1000VA / 550W
Max. Load for Full-Time Surge Protection outlets (9 Outlets)| 12 Amp (9
outlets)
On-Battery Output Wave Form| Simulated Sine Wave
Operating Temperature| + 32°F to 104° F / 0° C to 40° C
Operating Relative Humidity| 0 to 90% non-condensing
Size (W x H x D)| 3.9″ x 9.0″ x 10.2″ (100 x 227.5 x 260mm)
Net Weight| 15lbs / 6.8kg
Battery Type| CyberPower / RB1290
Typical Battery Recharge Time
|
24 Hours to 90% from full load discharge
Recommended Battery
|
Sealed Maintenance Free Lead Acid Battery
Safety Approvals
|
UL1778(UPS), CSA C22.2 No 107.3, FCC/DoC Class B
CYBERPOWER GREENPOWER UPS™ TECHNOLOGY
Advanced Energy-Saving Patented Bypass Technology
CyberPower’s patented GreenPower UPS™ with Bypass Technology reduces UPS
energy costs by up to 75% compared to conventional UPS models. Even when
utility power is normal, conventional UPS models constantly pass power through
a transformer. By contrast, under normal conditions, the advanced circuitry of
a GreenPower UPS™ bypasses the transformer. As a result, the power efficiency
is significantly increased while decreasing waste heat, using less energy, and
reducing energy costs. When an abnormal power condition occurs, the GreenPower
UPS™ automatically runs power through its transformer to regulate voltage and
provide “safe” power. Since utility power is normal over 88% of the time, the
GreenPower UPS™ operates primarily in its efficient bypass mode. The
GreenPower UPS™ is also manufactured in accordance with the Restriction on
Hazardous Substances (RoHS) directive making it one of the most
environmentally friendly on the market today.
FCC Compliance Statement
This device complies with part 15 of the FCC rules. Operation is subject to
the following two conditions: (1) this device may not cause harmful
interference, and (2) this device must accept any interference received,
including interference that may cause undesired operation.
Note: This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful
interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the
interference by one or more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and the receiver.
- Connect the equipment to an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help”
Warning: Changes or modifications not expressly approved by the party
responsible for compliance could void the user’s authority to operate the
equipment.
Canadian Compliance Statement: CAN ICES-3 (B)/NMB-3(B)
Limited Warranty and Connected Equipment Guarantee
TERMS AND CONDITIONS OF THE CYBER-POWER LIMITED WARRANTY
Please read the following terms and conditions carefully before using
CyberPower products (the “CPS Product”). By using the CPS product, you agree
to be bound by the terms of this Limited Warranty (collectively the
“Warranty”). IF YOU DO NOT AGREE TO THE WARRANTY TERMS AND CONDITIONS, YOU
MUST RETURN THE PRODUCT BEFORE USING, IT AND OBTAIN A FULL REFUND. THIS
WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS
THAT VARY FROM ONE PLACE TO ANOTHER. YOUR ACCEPTANCE OF THIS WARRANTY MAY
MODIFY OR WAIVE ANY OTHER RIGHTS YOU HAVE. Cyber Power Systems (USA), Inc.
(“CyberPower”) provides this Limited Warranty.
WARRANTY COVERAGE
The warranty covers only the original purchaser and ends when the original
purchaser no longer owns the CPS product. The warranty covers defects in
materials and workmanship in the CPS Product under normal use and to perform
as designed, after correct installation, and under the operating conditions
described in the User’s Manual. Proof of purchase (receipt and/or invoice) is
required for warranty coverage.
The warranty period varies according to the type of product purchased. Please
check our website at
www.cyberpowersystems.com for additional
information on the applicable product.
For warranty claims:
Telephone: USA 877-297-6937
Latin America & Caribbean 800-279-6580
Or write to us at: Cyber Power Systems (USA), Inc.
4241 12th Ave. E., Suite 400
Shakopee, MN 55379
TERMS AND CONDITIONS OF THE CYBER POWER LIMITED WARRANTY
Please read the following terms and conditions carefully before using
CyberPower products (the “CPS Product”). By using the CPS product, you agree
to be bound by the terms of this Limited Warranty (collectively the
“Warranty”). IF YOU DO NOT AGREE TO THE WARRANTY TERMS AND CONDITIONS, YOU
MUST RETURN THE PRODUCT BEFORE USING, IT AND OBTAIN A FULL REFUND. THIS
WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND YOU MAY ALSO HAVE OTHER RIGHTS
THAT VARY FROM ONE PLACE TO ANOTHER. YOUR ACCEPTANCE OF THIS WARRANTY MAY
MODIFY OR WAIVE ANY OTHER RIGHTS YOU HAVE.
Cyber Power Systems (USA), Inc. (“CyberPower”) provides this Limited Warranty.
WARRANTY COVERAGE
The warranty covers only the original purchaser and ends when the original
purchaser no longer owns the CPS product. The warranty covers defects in
materials and workmanship in the CPS Product under normal use and to perform
as designed, after correct installation, and under the operating conditions
described in the User’s Manual. Proof of purchase (receipt and/or invoice) is
required for warranty coverage.
The warranty period varies according to the type of product purchased. Please
check our website at
www.cyberpowersystems.com for additional
information on the applicable product.
For warranty claims:
Telephone: USA 877-297-6937
Latin America & Caribbean 800-279-6580
Or write to us at Cyber Power Systems (USA), Inc.
4241 12th Ave. E., Suite 400
Shakopee, MN 55379
To replace the CPS Product, CyberPower will replace, at no additional cost, any CPS Product or Equipment at its sole discretion; Through the network of distributors, wholesalers, and representatives of CyberPower; And/or directly from the factory to the end user. CyberPower, in its sole discretion, may replace the defective or damaged CPS Product with a new or reconditioned product, without prior notice. CyberPower covers shipping costs when CPS products are shipped to the end user. In the case of Latin America and the Caribbean, CyberPower may choose to ship the replacement Aunit to the export agent or end-user load agent in the United States at no additional cost. The record importer (customer) is responsible for complying with all applicable US Export Laws and requirements, as well as your specific country’s import process. CyberPower may require the customer to return the warranty unit to a local dealer, or back to CyberPower, or to destroy and/or dispose of a damaged unit locally. The customer covers shipping costs only if necessary and is required to return the CPS product to CyberPower.
In the event that CyberPower determines that a warranty unit can not be replaced by an equal or equivalent product, CyberPower may reimburse the end user for the purchase price of the product, including taxes, up to a maximum of the suggested MSRP, plus applicable taxes. The refund can be processed in US dollars and converted into local currency at the time of purchase. The end user must provide valid receipts and purchase documentation for an approved channel to validate the claim. MEXICO – Cyber Power Systems (USA), Inc., under the CyberPower brand, markets products that are designed and marketed for use primarily in the United States. CyberPower may provide a Connected Equipment Guarantee (CEG) for certain products. THE CONNECTED EQUIPMENT GUARANTEE IS ONLY VALID FOR PRODUCTS INSTALLED IN THE UNITED STATES, AND IS NOT VALID IN OTHER COUNTRIES UNLESS SPECIFIED. Any reference to the Connected Equipment Guarantee in documentation, packaging, or warranty is only valid for equipment installed in the United States. Products marketed or otherwise installed in Mexico are only covered by a manufacturer’s Guarantee Policy and are not covered by a connected equipment warranty.
Cyber Power Systems S.A. Of C.V. (CyberPower): Provides a limited warranty,
depending on the product model, from the date of purchase in all its parts and
labor, against any manufacturing defect, under the following CONDITIONS:
To make this guarantee effective, you must present this policy stamped by the
establishment that sold it and/or the original invoice, without violating the
seal of warranty, together with the product at the place of purchase or at the
address:
Aniceto Ortega #634, Col. Del Valle
Del. Benito Juárez, C.P. 03100,
Ciudad de México, México
Tel: (0155) 4622-8654
Return transportation costs once repaired and resulting from their compliance, will be covered by CyberPower. The repair time, in no case, will be more than 30 days from the date the equipment is received at the Service Center. At the end of this warranty, spare parts, parts, and accessories for this product can be purchased directly from CyberPower.
THIS WARRANTY SHALL NOT BE EFFECTIVE IN THE FOLLOWING CASES
If the equipment has been used in conditions other than normal. If the
equipment has not been operated following the instructions in the instruction
manual. If the equipment has been modified, opened or repaired by unauthorized
personnel.
CyberPower product registration facilitates the management of warranty claims
and also allows notifications of product enhancements, updates and other
announcements. We suggest you create a user account on the CyberPower page
according to the instructions given here: Please contact our technical support
department for installation assistance, technical support, and general product
questions.
This Guarantee does not cover any
Software that has been corrupted or needs to be replaced due to product
failure or any data lost as a result of failure, or restoring data or records,
or reinstalling software; Use, misuse, modification, performance or storage
outside the environmental limits of the CPS product, or equipment connected to
it, nor for damage while in transit or in storage. Products that should not be
used with the CPS Product, such as laser printers, aquarium appliances,
medical or life support devices, etc.; Defects or damages due to: accidents,
fires, floods, lightning, vandalism, acts of God, neglect, abuse or misuse
among others: in shipping, storage, installation, application, and operation
or maintenance not in With industry-standard recommendations and practices.
System batteries and all other peripheral products and accessories not supplied by CyberPower (including components and software) or the installation, operation, maintenance or service of such accessories; And, the reimbursement of labor, pressure washing, access, removal, installation, employee expenses, or any other expenses you may incur in connection with the repair or replacement of the product, the accessories supplied with the product: cables, user manual, CD, etc.; Any product that the serial number printed and attached to the product has been: removed, disfigured, changed, altered, or manipulated. The only and exclusive remedies of the client are those provided by this Guarantee.
TO THE EXTENT PERMITTED BY LAW, THIS WARRANTY AND THE ESTABLISHED REMEDIES ARE EXCLUSIVE AND REPLACE ALL OTHER WARRANTIES, REMEDIES, AND CONDITIONS; WHETHER ORAL, WRITTEN, STATUTORY, EXPRESS OR IMPLIED. CYBERPOWER DISCLAIMS ALL STATUTORY AND IMPLIED WARRANTIES; INCLUDING WITHOUT LIMITATION, WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE AND WARRANTIES AGAINST HIDDEN OR LATENT DEFECTS, TO THE EXTENT PERMITTED BY LAW. CYBERPOWER LIMITS THE DURATION AND THE RESOURCES OF SUCH WARRANTIES TO THE DURATION OF THIS LIMITED WARRANTY AND, AT CYBERPOWER’S OPTION, THE REPAIR OR REPLACEMENT SERVICES DESCRIBED ABOVE. SOME STATES (COUNTRIES AND PROVINCES) DO NOT ALLOW LIMITATIONS AS TO THE TIME WHICH CAN LAST AN IMPLIED WARRANTY (OR CONDITION), SO THE ABOVE LIMITED LIMITATION MAY NOT APPLY TO YOU.
Regardless of the basis on which you are entitled to claim damages against
CyberPower; IN NO EVENT SHALL CYBERPOWER BE LIABLE TO YOU FOR INJURY OR DAMAGE
CAUSED TO BUSINESS, PROFITABILITY, RESULTS, REVENUE, TRADEMARK, GOOD FAITH, OR
FOR ANY SPECIAL, CONSEQUENTIAL, INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF
YOU HAVE BEEN ADVISED OF THE RISK AND POSSIBILITY OF SUCH DAMAGES.
In addition, the product and the equipment connected to it must have been used
properly in a suitable, appropriate environment and in accordance with any
license, the instructions in the brochure or warnings provided with the
product, and the equipment connected to it. Without limiting the foregoing:
- This Warranty is not valid unless the CPS Product and connected equipment are connected to properly grounded outlets (including compliance with the electrical and safety codes of the most recent electrical code) without the use of adapters or other connectors of any kind.
- The CPS product must be connected directly to the power source and equipment directly connected to the CPS product.
- The product must be directly connected to the CPS Product; Must not be connected “in series” with extension cables, another product or device similar to the CPS product, surge suppressor or power supply: this type of installation voids the warranty.
- The CPS product and the connected equipment must have been used correctly in a suitable environment and in accordance with any applicable license, instruction manual, and manufacturer’s warnings.
- The CPS Product must have been used at all times within the limitations in the voltage capacity of the CPS Product.
- The product is not for use in high-risk activities or connected to aquariums. The product is not intended for use in hazardous environments requiring fail-safe operation, or for any circumstance where failure of the product could lead directly to death, personal injury, or serious physical or material damage affecting the operation or The safety of any medical or life support device (collectively, “High-Risk Activities”). CyberPower expressly disclaims any express or implied warranty of fitness for high-risk or aquarium activities. Such use is improper and voids this warranty.
Cyber Power Systems (USA), Inc.
4241 12th Ave E., Suite 400
Shakopee, MN 55379
877-297-6937
Telephone: USA Latin America & Caribbean Email: Latin America & Caribbean
Sales:
lac.service@cyberpower.comlac.sales@cyberpower.com
References
- CyberPower | UPS Systems & PDUs | Professional Power Solutions
- CyberPower UPS Systems, Battery Backup, PDUs, USB Surge Protectors
- Registration | CyberPower
- CyberPower UPS Systems, Battery Backup, PDUs, USB Surge Protectors
- CyberPower UPS Systems, Battery Backup, PDUs, USB Surge Protectors
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>