MR COOL A-12-HP-115B Mini Split Inverter Wall Mount Heat Pump Instruction Manual

June 12, 2024
Mr Cool

A-12-HP-115B Mini Split Inverter Wall Mount Heat Pump

“`html

Product Information

The Advantage Series is a high-performance product designed for
professional installation. It requires the expertise of an
authorized technician for proper installation and operation. This
product manual contains important information and instructions that
should be read carefully before installation.

Please note that the information and instructions provided in
this manual are subject to change without notice. To ensure that
you have the latest version of the manual, visit www.mrcool.com/documentation.
Version Date: 01-27-22

Contents

  • Safety Precautions
  • Accessories
  • Installation Summary – Indoor Unit
  • Parts Overview
  • Indoor Unit Installation
  • Outdoor Unit Installation
  • Refrigerant Piping Connection
  • Air Evacuation
  • Electrical and Gas Leak Checks
  • Test Run
  • EU Disposal Guidelines

Product Usage Instructions

Safety Precautions

Before proceeding with installation, it is important to adhere
to the following safety precautions:

  • WARNING: Ignoring instructions may cause death
    or serious injury.

  • CAUTION: Ignoring instructions may cause
    moderate injury to your person, damage to your unit, or other
    property.

  • WARNING: Do not modify the length of the power
    supply cord or use an extension cord to power the unit. Only use
    the specified power cord. If the power cord is damaged, it must be
    replaced by the manufacturer, its service agent, or similarly
    qualified person to avoid hazards.

  • WARNING: Do not share the electrical circuit
    with other appliances. Improper or insufficient power supply can
    cause fire or electrical shock.

Installation Summary – Indoor Unit

Follow these steps for installing the indoor unit:

  1. Choose an appropriate installation location.
  2. Attach the mounting plate to the wall.
  3. Drill a wall hole for connective piping.
  4. Prepare the refrigerant piping.
  5. Connect the drain hose.
  6. Connect the signal cable.
  7. Wrap piping and cables.
  8. Connect the indoor power wire.
  9. Mount the indoor unit.

Outdoor Unit Installation

Follow these steps for installing the outdoor unit:

  1. Choose an appropriate installation location.
  2. Install the drain joint.
  3. Anchor the outdoor unit.
  4. Connect the signal and power cables.

Refrigerant Piping Connection

Follow these steps for connecting the refrigerant piping:

  1. Cut the pipe.
  2. Remove burrs.
  3. Flare pipe ends.
  4. Connect the pipes.

Air Evacuation

Follow these instructions for air evacuation:

  1. Read the evacuation instructions carefully.
  2. Note on adding refrigerant.

Electrical and Gas Leak Checks

Perform electrical and gas leak checks as instructed.

Test Run

Complete the test run as described in the manual.

EU Disposal Guidelines

Follow the guidelines for proper disposal of the EU (End of Use)
product.

“`

The Advantage Series is NOT designed for amateur installation. Installation SHOULD be performed by an authorized technician.
Please read this manual carefully before installation and keep it for future reference.
Installation Manual
Advantage Series
Due to updates and constantly improving performance, the information and instructions within this manual are subject to change without notice. Please visit www.mrcool.com/documentation to ensure you have the latest version of this manual. Version Date: 01-27-22

Contents
! Safety Precautions ……………………………. 3 1 Accessories ……………………………………….. 5 2 Installation Summary – Indoor Unit …… 7 3 Parts Overview ………………………………….. 9

4 Indoor Unit Installation ………..10
1. Installation location……………………………10 2. Attach mounting plate to wall……………11 3. Drill wall hole for connective piping…..11 4. Prepare refrigerant piping ………………..13 5. Connect drain hose……………………………14 6. Connect signal cable………………………….16 7. Wrap piping and cables……………………..17 8. Connect indoor power wire……………….17 9. Mount indoor unit……………………………..17
5 Outdoor Unit Installation …… 19
1. Installation location …………………………19 2. Install drain joint ……………………………. 20 3. Anchor outdoor unit ……………………… 21 4. Connect signal and power cables …. 22

Page 1

mrcool.com

Contents
6 Refrigerant Piping Connection …………………. 24
A. Note on Pipe Length ……………………………………………………. 24 B. Connection Instructions ­ Refrigerant Piping ……………… 24
1. Cut pipe …………………………………………………………………… 24 2. Remove burrs …………………………………………………………. 25 3. Flare pipe ends ……………………………………………………….. 25 4. Connect pipes ………………………………………………………….. 26

MC

MC

7 Air Evacuation ………………….. 28

1. Evacuation Instructions ………………… 28 2. Note on Adding Refrigerant ………….. 29

8 Electrical and Gas Leak Checks ….. 30 9 Test Run ……………………………………. 31 10 EU Disposal Guidelines ………………. 33
mrcool.com

Page 2

Safety Precautions
Safety Precautions

!

Read Before Installation Incorrect installation may cause serious damage or injury.
The seriousness of potential damage or injuries is classified as either a WARNING or CAUTION.

WARNING

This symbol indicates ignoring instructions may cause death or serious injury.

CAUTION

This symbol indicates that ignoring instructions may cause moderate injury to your person, damage to your unit, or other property.

This symbol indicates that you should never perform the indicated action.

WARNING
DO NOT modify the length of the power supply cord or use an extension cord to power the unit. Only use the specified power cord. If the power cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified person in order to avoid a hazard.
DO NOT share the electrical circuit with other appliances. Improper or insufficient power supply can cause fire or electrical shock.
DO NOT let substances or gases other than the refrigerant enter the unit when connecting refrigerant piping. The presence of other gases or substances will lower the unit’s capacity, and may cause abnormally high pressure in the operation cycle. This may cause explosion and injury.
DO NOT allow children to play with the air conditioner. Children should be supervised around the unit at all times.
DO NOT turn on power until all work/installation has been completed.
1. Installation must be performed by an authorized technician. Improper installation may cause water leakage, electrical shock, or fire. The moving and relocation of the unit also requires consulting an authorized technician for the disconnection and re-installation steps.
2. Installation must be performed according to installation instructions. Improper installation may cause water leakage, electrical shock, or fire.
3. In North America, installation must be performed in accordance with the requirement of NEC and CEC (by authorized personnel only.) Contact an authorized service technician for repair or maintenance of the unit.
4. Only use the included accessories and specified parts for installation. Using non-standard parts can cause water leakage, electrical shock, or fire and may cause the unit to fail.
5. Install the unit in a firm location that can support the unit’s weight. If the installation location cannot support the weight, or the installation is performed improperly, the unit may fall and cause serious injury and/or damage.
6. For all electrical work, follow all appropriate wiring standards, regulations, and the Installation Manual.

Page 3

mrcool.com

Safety Precautions

7. You must use an independent circuit to supply power. DO NOT connect other appliances to the same circuit. Insufficient electrical capacity or defects in electrical work can cause electrical shock or fire.
8. For all electrical work, fuse the specified cables. Connect cables tightly, and clamp them securely to prevent external forces from damaging the terminal. Improper electrical connections may overheat, causing fire and/or electrical shock.
9. All wiring must be properly arranged to ensure that the control board cover can close properly. If the control board cover is not closed properly, it can lead to corrosion and cause the connection points on the terminal to overheat , causing fire and/or electrical shock.
10. In certain functional environments, such as kitchens, server rooms, etc., the use of specially designed air-conditioning units is highly recommended. If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.
11. This appliance is not intended for use by persons (including children) with reduced physical, sensory or mental capabilities, or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety. Children should be supervised to ensure that they do not play with the appliance.
12. If connecting power to fixed wiring, the following must be incorporated within it, in accordance with the wiring rules; an all-pole disconnection device (which has at least 1/8 in (3 mm) of clearances in all poles), and have a leakage current that may exceed 10 mA, the residual current device (RCD) having a rated residual operating current not exceeding 30 mA, and disconnection all must be present.

DO NOT install the unit within 3 feet (1 meter) of combustible materials if the unit has an auxiliary electric heater.
DO NOT install the unit in a location that may be exposed to combustible gases. If combustible gas accumulates around the unit, it may cause fire.
DO NOT operate your air conditioner in a wet room such as a bathroom or laundry room. Too much exposure to water may cause electrical components to short circuit.
1. The product must be properly grounded during installation, or electrical shock may occur.
2. Install drainage piping according to the instructions in this manual. Improper drainage may cause water damage to your home and property.
Note about Fluorinated Gases:
1. This air-conditioning unit contains fluorinated greenhouse gases. 2. For specific information on the type of gas and the amount, please refer to the relevant label on the unit
itself or the Owner’s Manual. 3. Installation, service, maintenance and repair of this unit must be performed by a certified technician. 4. Product removal /un-installation and recycling must be performed by a certified technician. 5. If the system has a leak-detection system installed, it should be checked for leaks at least every 12
months. Keeping a record of all leak checks for the lifetime of the unit is strongly recommended. 6. For equipment that contains fluorinated greenhouse gases in quantities of 5 tonnes of CO2 equivalent
or more, but less than 50 tonnes of CO2 equivalent, if the system has a leak- detection system installed, it must be checked for leaks at least every 24 months.

mrcool.com

Page 4

Accessories

Safety Precautions

1

The air conditioning system includes the following accessories. Use all of the installation parts and accessories to install the air conditioner. Improper installation may result in water leakage, electrical shock, fire, or equipment failure.

PART

LOOKS LIKE…

QUANTITY

Mounting plate

1

Clip anchor
Mounting plate screw ST3.9 X 25

5-8 (depending on model)
5-8 (depending on model)

Remote control

1

Fixing screw for remote controller holder ST2.9 x 10
Remote control holder
Dry battery AAA.LR03
Air freshening filter
Seal
Drain joint (for cooling & heating models)
Neoprene

2 Optional Parts
1
2
1
1
1
1 (Sealant for Wall Sleeve)

Page 5

mrcool.com

Accessories

PART Owner’s Manual
Installation Manual
Remote Control Manual Smart Controller Kit

LOOKS LIKE…
Please read this manual carefully before installation and keep it for future reference.
Owner’s Manual
Advantage Series
For more details visit www.MrCool.com Please read this manual carefully before installation and keep it for future reference.
Installation Manual
Advantage Series
Please read this manual carefully before installation and keep it for future reference.
Please read this manual carefully before installation and keep it for future reference.
Remote Control User Manual
For more details visit www.MrCool.com

QUANTITY 1
1
1 1 (w/ Manual in Controller Box)

Line Set

Gas / Liquid

1

Pipe Assembly

1 2 3

Magnetic Ring & Belt

(if supplied, please refer

to the wiring diagram to install it on the connective cable)

Pass the belt through the hole of the Magnetic

ring to fix it on the cable

Varies by model

mrcool.com

Page 6

Installation Summary – Indoor Unit

1

Minimum Ceiling

Clearance is

5.9 in (15 cm)

4.75 in (12 cm)

For Ceilings GREATER Than 9 Foot, Suggested Floor Clearance is
90.55 in (230 cm)
For Ceilings LESS Than 9 Foot, Suggested Floor Clearance is
78.55 in (200 cm)

2

4.75 in (12 cm)

2

Select Installation Location (Page 10)

Determine Wall Hole Position (Page 11)

3

4

Attach Mounting Plate (Page 11)

Page 7

mrcool.com

Drill Wall Hole (Page 11)

Installation Summary – Indoor Unit

5

6

7

Connect Piping (Page 24)
8

Connect Wiring (Page 16)

Prepare Drain Hose (Page 13)

Wrap Piping (Page 17)
9

Mount Indoor Unit (Page 17)
mrcool.com

Page 8

Parts Overview

3

Front Panel
(with display)

Air inlet (rear)

Indoor Unit
(Interior / Air Handler)

Vertical Airflow Louver
Horizontal Airflow Grill (inside)

Air outlet (bottom)

Smart Controller Module USB Port
Wall Mounting Plate
Drainage Pipe Refrigerant Piping

Fresh Air Filter
(on front of main filter in Specified Units)

Air inlet (side)

Air inlet (rear)

Remote Control

Air outlet

Outdoor Unit
(Exterior / Condenser)

Outdoor Unit Power Cable

Remote Holder

Refrigerant Pipe Connection and Stop Valve (under cover)

NOTE ON ILLUSTRATIONS Illustrations in this manual are for explanatory purposes. The actual shape of your unit may vary.

Page 9

mrcool.com

Installation Summary – Indoor Unit
Indoor Unit Installation

4

Installation Instructions ­ Indoor Unit
PRIOR TO INSTALLATION: Before installing the indoor unit, refer to the label on the product box to make sure that the model number of the indoor unit matches the model number of the outdoor unit.
Step 1: Select installation location Before installing the indoor unit, you must choose an appropriate location. The following are standards will help you choose an appropriate location.
Proper installation locations meet the following standards:
Good air circulation
Convenient drainage
Noise from the unit will not disturb other people
Firm and solid–the location will not vibrate
Strong enough to support the weight of the unit
A location at least one meter from all other electrical devices (e.g., TV, radio, computer)

DO NOT install unit in the following locations:
Near any source of heat, steam, or combustible gas
Near flammable items such as curtains or clothing
Near any obstacle that might block air circulation
Near a doorway
In a location subject to direct sunlight
NOTE ABOUT WALL HOLE: If there is no fixed refrigerant piping: While choosing a location, be aware that you should leave ample room for a wall hole (see Drill wall hole for connective piping step) for the signal cable and refrigerant piping that connect the indoor and outdoor units. The default position for all piping is the right side of the indoor unit (while facing the unit). However, the unit can accommodate piping to left or right.

mrcool.com

Page 10

Indoor Unit Installation
Refer to the following diagram to ensure proper distance from walls and ceiling:
Minimum Ceiling
Clearance is 5.9 in (15cm)

4.75 in (12 cm)

4.75 in (12 cm)

For Ceilings GREATER Than 9 Foot, Suggested Floor Clearance is
90.55 in (230 cm)

For Ceilings LESS Than 9 Foot, Suggested Floor Clearance is
78.55 in (200 cm)

Fig. 4.1

Step 2: Attach mounting plate to wall The mounting plate is the device on which you will mount the indoor unit . 1. Remove the screw that attaches the mounting
plate to the back of the indoor unit.
Screw

Step 3: Drill wall hole for connective piping
You must drill a hole in the wall for refrigerant piping, the drainage pipe, and the signal cable that will connect the indoor and outdoor units.
1. Determine the location of the wall hole based on the position of the mounting plate. Refer to Mounting Plate Dimensions on the next page to help you determine the optimal position. Refer to Fig. 4.3 wall hole diameter and install at a slight angle to facilitate drainage.

2. Place the mounting plate against the wall in a location that meets the standards in the Select Installation Location step. (See Mounting Plate Dimensions for detailed information on mounting plate sizes.)
3. Drill holes for mounting screws in places that: · have studs and can support the weight of the unit · correspond to screw holes in the mounting plate

2. Using a core drill [3.5 in (76.2 mm) for 24K & 36K units, 2.5 in (65 mm) for all others], drill a hole in the wall. Make sure that the hole is drilled at a slight downward angle, so that the outdoor end of the hole is lower than the indoor end by about 0.2 to 0.275 in (5 mm-7 mm). This will ensure proper water drainage. (See Fig. 4.2)
NOTE: When the gas side connective pipe is 5/8 in (16 mm) or more, the wall hole should be 3.54 in (90 mm).

4. Secure the mounting plate to the wall with the screws provided.
5. Make sure that mounting plate is flat against the wall.
NOTE FOR CONCRETE OR BRICK WALLS:
If the wall is made of brick, concrete, or similar material, drill 0.2 in diameter (5 mm diameter) holes in the wall and insert the sleeve anchors provided. Secure the mounting plate to the wall by tightening the screws directly into the clip anchors.

3. Place the protective wall cuff in the hole. This protects the edges of the hole and will help seal it when you finish the installation process.
CAUTION
When drilling the wall hole, be sure to avoid wires, plumbing, and other sensitive components.

Page 11

mrcool.com

Indoor Unit Installation

Wall

Indoor

Outdoor

4 in (101 mm)

1.45 in (37 mm)

13.7 in (348.4 mm) 7.05 in (179 mm) 5.35 in (136 mm)
Indoor unit outline

1.95 in (49 mm)

11.4 in (290 mm) 1.95 in (49 mm)

0.2 – 0.3 in (5 – 7 mm)

Left rear wall hole 2.5 in (65 mm)

28.45 in (722 mm)
Series 9K Models

Right rear wall hole 2.5 in (65 mm)

7.55 in (192 mm)

16.8 in (426 mm) 9.15 in (232 mm)
5.05 in (128 mm)

1.7 in (43 mm) 1.7 in (43 mm)

11.7 in (297 mm) 1.7 in (43 mm)

Indoor unit outline

Fig. 4.2
MOUNTING PLATE DIMENSIONS
Different models have different mounting plates. For the different customization requirements, the shape of the mounting plate may be slightly different. However, the installation dimensions are the same for the same size of indoor unit. See the illustrations for Type A and Type B below for an example. In order to ensure that you have ample room to mount the indoor unit, the diagrams to the right show different types of mounting plates along with the following dimensions:
· Height & Width of mounting plate
· Height & Width of indoor unit relative to plate
· Recommended position of wall hole (both to the left and right of mounting plate)
· Relative distances between screw holes

Left rear wall hole 2.5 in (65 mm)

31.6 in (802 mm)
Series 12K Models

Right rear wall hole 2.5 in (65 mm)

1.55 in (40 mm) 2.3 in (58 mm)

12.55 in (319 mm) 2.25 in (57 mm)

5.45 in (138 mm)

20.37 in (517.4 mm) 5.65 in (144 mm)
Indoor unit outline

Left rear wall hole 2.5 in (65 mm) 1.35 in (34 mm)

38 in (965 mm)

Series 18K Models

Right rear wall hole 2.5 in (65 mm)

2.1 in (53.5 mm)

8.6 in (219 mm) 3 in (76 mm)

21.77 in (553 mm) 11.8 in (300 mm)

5.85 in (148.7 mm)

2.1 in (53.5 mm)
Indoor unit outline

13.2 in (335 mm) 1.85in (47mm)

1.85 in (47 mm)

Left rear wall

Right rear wall

hole 3.5 in (76.2 mm)

6.85

in

(174.3

mm) 42.5

in

(1080

mm)

5.95

in

(151

mm)

hole 3.5 in (76.2 mm)

Series 24K Models

Type A

Type B

Correct orientation of Mounting Plate

25.3 in (643.6 mm)

15.3 in (389 mm)

10.1 in (257 mm)

6.8 in (172 mm)

13.05 in (332 mm)

362mm (14.25in)

Indoor unit outline

Left rear wall hole 3.54 in (90 mm)

2.05 in (52 mm)
49.55 in (1259 mm)
Series 36K Models

2.05 in (52 mm)
Right rear wall hole 3.54 in (90 mm)

Fig. 4.3

mrcool.com

Page 12

Indoor Unit Installation

Step 4: Prepare refrigerant piping
The refrigerant piping is inside an insulating sleeve attached to the back of the unit. You must prepare the piping before passing it through the hole in the wall. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions on pipe flaring and flare torque requirements, technique, etc.
1. Based on the position of the wall hole relative to the mounting plate, choose the side from which the piping will exit the unit.
2. If the wall hole is behind the unit, keep the knock-out panel in place. If the wall hole is to the side of the indoor unit, remove the plastic knock-out panel from that side of the unit. (See Fig. 4.4 ). This will create a slot through which your piping can exit the unit. Use needle nose pliers if the plastic panel is too difficult remove by hand.

Fig. 4.4

Knock-out Panel

3. Use scissors to cut down the length of the insulating sleeve to reveal about 6 in (15 cm) of the refrigerant piping. This serves two purposes:
· To facilitate the Refrigerant Piping Connection process
· To facilitate Gas Leak Checks and enable you to check for dents
4. If existing connective piping is already embedded in the wall, proceed directly to the Connect Drain Hose step. If there is no embedded piping, connect the indoor unit’s refrigerant piping to the connective piping that will join the indoor and outdoor units. Refer to the Refrigerant Piping Connection section of this manual for detailed instructions.
5. Based on the position of the wall hole relative to the mounting plate, determine the necessary angle of your piping.
6. Grip the refrigerant piping at the base of the bend.
7. Slowly, with even pressure, bend the piping towards the hole. DO NOT dent or damage the piping during the process.
NOTE ON PIPING ANGLE
Refrigerant piping can exit the indoor unit from four different angles:
· Left-hand side · Left rear · Right-hand side · Right rear Refer to Fig. 4.5 for details.

Fig. 4.5
Be extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will affect the unit’s performance.

Page 13

mrcool.com

Indoor Unit Installation

Step 5: Connect drain hose
By default, the drain hose is attached to the left-hand side of unit (when you’re facing the back of the unit). However, it can also be attached to the right-hand side.
1. To ensure proper drainage, the drain hose must exit the unit on the same side as the refrigerant piping.
2. Wrap the connection point firmly with Teflon tape to ensure a good seal and to prevent leaks.
3. For the portion of the drain hose that will remain indoors, wrap it with foam pipe insulation to prevent condensation.
4. Remove the air filter and pour a small amount of water into the drain pan to make sure that water flows from the unit smoothly.
NOTE ON DRAIN HOSE PLACEMENT

Make sure there are NO kinks or dents in the
hose to ensure proper drainage.
Fig. 4.6a
NOT CORRECT Kinks in the drain hose will create water traps.

Make sure to arrange the drain hose according to Fig. 4.6a.
DO NOT kink the drain hose.
DO NOT create a water trap.
DO NOT put the end of drain hose in water or a container that will collect water.

Fig. 4.6b
NOT CORRECT Dents in the drain hose will create water traps.

ENSURE UNUSED DRAIN HOLE IS PLUGGED
To prevent unwanted leaks be sure that the factory installed rubber plug is in the unused drain hole.

Fig. 4.6c

NOT CORRECT DO NOT place the end
of the drain hose in water or in containers
that collect water. This will prevent proper drainage.

Fig. 4.6d

mrcool.com

Page 14

Indoor Unit Installation
BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
4. Power voltage should be within 90-110% of rated voltage. Insufficient power supply can cause a malfunction, electrical shock, or fire.
5. Circuit, including any switches, should have a capacity 1.5 times the maximum unit current (amps).
6. If connecting power to fixed wiring, the qualified technician must use an approved circuit breaker or switch that disconnects all poles and has a contact separation of at least 1/8 in (3 mm). It must be incorporated into the fixed wiring.
7. Make sure to properly ground the air conditioner. 8. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat,
resulting in malfunction and possible fire. 9. If the unit has an auxiliary electric heater, it must be installed at least 40 in (1 meter) away
from any combustible materials. 10. To avoid getting an electric shock, never touch the electrical components soon after the power
supply has been turned off. Always wait 10 minutes or more before touching the electrical components once the power has been turned off. 11. If connecting power to fixed wiring, a surge protector and main power switch should be installed. DO NOT connect another appliance to the same circuit. Only connect the unit to an individual branch circuit outlet.
DO NOT let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.
BEFORE PERFORMING ANY ELECTRICAL WORK, TURN OFF ALL POWER TO THE SYSTEM.

Page 15

mrcool.com

Fig. 4.7a

Indoor Unit Installation

Step 6: Connect signal cable
CHOOSE THE APPROPRIATE CABLE SIZE The size of the power supply cable, signal cable, fuse, and switch needed is determined by the maximum unit current. The maximum unit current is indicated on the nameplate located on the side panel of the unit. Refer to this nameplate to choose the right cable, fuse, or switch. NOTE: In North America, please choose the right cable size according to the Minimum Circuit Ampacity indicated on the nameplate of the unit.
TAKE NOTE OF FUSE SPECIFICATIONS The air conditioner’s circuit board (PCB) is designed with a fuse to provide overcurrent protection. The specifications of the fuse are printed on the circuit board, such as: T3.15A/250VAC, T5A/250VAC, etc.
1. Prepare the cable for connection:
2. Open front panel of the indoor unit.
3. Using a screwdriver, open the wire box cover on the right side of the unit. This will reveal the terminal block.
Terminal block Wire cover
Screw Cable clamp
Fig. 4.7b See Fig. 4.7A on previous page for wiring diagram. Wiring diagram also found inside lid of interior unit

4. Unscrew the cable clamp below the terminal block and place it to the side.
5. Facing the back of the unit, remove the plastic panel on the bottom left- hand side.
6. Feed the signal wire (protected by conduit) through this slot, from the back of the unit to the front.
7. Facing the front of the unit, match the wire colors with the labels on the terminal block, connect the u-lug and firmly screw each wire to its corresponding terminal.

DO NOT MIX UP LIVE AND NULL WIRES This is dangerous, and can cause the air conditioning unit to malfunction.
8. After checking to make sure every connection is secure, use the cable clamp to fasten the signal cable to the unit. Screw the cable clamp down tightly.
9. Replace the wire cover on the front of the unit, and the plastic panel on the back.

THE WIRING CONNECTION PROCESS MAY DIFFER SLIGHTLY BETWEEN UNITS AND REGIONS.
North America

Model Series

Appliance Amps (A)

(Indoor Unit) MCA MOP

All Capacity Wall Mounted Air

3 15

Handlers

All wiring must be performed in accordance with the wiring diagram Fig. 4.7a shown on the previous page.
mrcool.com

Page 16

Indoor Unit Installation

Step 7: Wrap piping
Before passing the piping and drain hose through the wall hole, you must bundle them together to protect them, insulate them, and save space.
1. Bundle the drain hose and refrigerant pipes according to Fig. 4.8.
Indoor Unit

Space behind unit

Refrigerant piping Insulation tape

Drain hose

Fig. 4.8

DRAIN HOSE MUST BE ON BOTTOM
Make sure that the drain hose is at the bottom of the bundle. Putting the drain hose at the top of the bundle can cause the drain pan to overflow, which may lead to fire or water damage.

SIGNAL CABLE PROTECTION
The signal cable must be protected by conduit before being pushed through the wall hole.

2. Using vinyl tape, attach the drain hose to the underside of the refrigerant pipes.
3. Using insulation tape, wrap the refrigerant pipes and drain hose tightly together. Double-check that all items are bundled in accordance with Fig. 4.8.
DO NOT WRAP ENDS OF PIPING
When wrapping the bundle, keep the ends of the piping unwrapped. You need to access them to test for leaks at the end of the installation process (refer to Electrical Checks and Leak Checks section of this manual).

Step 8: Mount indoor unit
If you installed new connective piping to the outdoor unit, do the following:
1. If you have already passed the refrigerant piping through the hole in the wall, proceed to Step 4.
2. Otherwise, double-check that the ends of the refrigerant pipes are sealed to prevent dirt or foreign material from entering the pipes.
3. Slowly pass the wrapped bundle of refrigerant pipes and drain hose through the hole in the wall.
4. Hook the top of the indoor unit on the upper hook of the mounting plate.
5. Check that unit is hooked firmly on mounting plate by applying slight pressure to the left and right-hand sides of the unit. The unit should not jiggle or shift.
6. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate.
7. Again, check that the unit is firmly mounted by applying slight pressure to the left and the right-hand sides of the unit.

Page 17

mrcool.com

Indoor Unit Installation

If refrigerant piping is already embedded in the wall, do the following:
1. Hook the top of the indoor unit on the upper hook of the mounting plate.
2. Use a bracket or wedge to prop up the unit, giving you enough room to connect the refrigerant piping, signal cable, and drain hose. Refer to Fig. 4.9 for an example.

30°

Wedge

3. Connect drain hose and refrigerant piping (refer to Refrigerant Piping Connection section of this manual for instructions).
4. Keep piping connections exposed to perform the leak test (refer to Electrical Checks and Leak Checks section of this manual).
5. After the leak test, wrap the piping connection points with insulation tape.
6. Remove wedge bracket or wedge that is propping up the unit.
7. Using even pressure, push down on the bottom half of the unit. Keep pushing down until the unit snaps onto the hooks along the bottom of the mounting plate

Fig. 4.9
UNIT IS ADJUSTABLE
Keep in mind that the hooks on the mounting plate are smaller than the holes on the back of the unit. If you find that you do not have ample room to connect embedded pipes to the indoor unit, the unit can be adjusted left or right by about 1.25 in -1.95 in (30 mm – 50 mm), depending on the model. (See Fig. 4.10)

1.2 in – 1.95 in (30 mm – 50 mm)

1.2 in – 1.95 in (30 mm – 50 mm)

Move to left or right
Fig. 4.10
mrcool.com

Page 18

Indoor Unit Installation
Outdoor Unit Installation

5

Installation Instructions ­ Outdoor Unit
Step 1: Select installation location Before installing the outdoor unit, you must choose an appropriate location. The following standards will help you choose an appropriate location.
Proper installation locations meet the following standards:
Meets all spatial requirements shown in Installation Space Requirements (Fig. 5.1).
Good air circulation and ventilation.
Firm and solid location that can support the unit and will cause vibration.
Noise from the unit will not disturb others.
Protected from prolonged periods of direct sunlight or rain.
Where snowfall is anticipated, raise the unit above the base pad to prevent ice buildup coil damage. Mount the unit high enough to be above the average accumulated area snowfall. The minimum height must be 18 inches.

i7n9firnino(n(22t0000cmcm) )

24inin((6600cmcm) ) above

Ground Installed: 12 in (30 cm) Bracket Installed: 6 in (15 cm) clearance between back and wall

12inin((3300cmcm) ) on left side

24inin((6600cmcm) ) on right side

Fig. 5.1
DO NOT install unit in the following locations:
Near an obstacle that will block air inlets and outlets

Near a public street, crowded areas, or where noise from the unit will disturb others

Near animals or plants that will be harmed by hot air discharge

Near any source of combustible gas or in a location that is exposed to large amounts of dust

In a location exposed to a excessive amounts of salty air

Page 19

mrcool.com

Outdoor Unit Installation

SPECIAL CONSIDERATIONS FOR EXTREME WEATHER If the unit is exposed to heavy wind: Install unit so that air outlet fan is at a 90° angle to the direction of the wind. If needed, build a barrier in front of the unit to protect it from extremely heavy winds. Ensure the wind barrier does not block necessary airflow. See Fig. 5.2 and Fig. 5.3 below.
Strong wind

Strong wind

Fig. 5.2

Wind Baffle

If the drain joint comes with a rubber seal (see Fig. 5.4 – A), do the following:
1. Fit the rubber seal on the end of the drain joint that will connect to the outdoor unit.
2. Insert the drain joint into the hole in the base pan of the unit.
3. Rotate the drain joint 90° until it clicks in place facing the front of the unit.
4. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.
If the drain joint doesn’t come with a rubber seal (see Fig. 5.4 – B), do the following:
1. Insert the drain joint into the hole in the base pan of the unit. The drain joint will click in place.
2. Connect a drain hose extension (not included) to the drain joint to redirect water from the unit during heating mode.

Strong wind
Fig. 5.3
If the unit is frequently exposed to heavy rain or snow: Build a shelter above the unit it to protect it from the rain or snow. Be careful not to obstruct air flow around the unit. If the unit is frequently exposed to salty air (seaside):
Use the outdoor unit that is specially designed to resist corrosion.
Step 2: Install drain joint Heat pump units require a drain joint. Before bolting the outdoor unit in place, you must install the drain joint at the bottom of the unit. NOTE: that there are two different types of drain joints depending on the type of outdoor unit.

Base pan hole of outdoor unit Seal
Seal

Drain joint

(A)

(B)

Fig. 5.4

CAUTION
In cold climates, make sure that the drain hose is as vertical as possible to ensure swift water drainage. If water drains too slowly, it can freeze in the hose and flood the unit.

mrcool.com

Page 20

Outdoor Unit Installation

A
Air Inlet

Air Inlet

H

D

B

Air Outlet

W

Fig. 5.5

Step 3: Anchor outdoor unit
The outdoor unit can be anchored to the ground or to a wall-mounted bracket with bolts (M10). Prepare the installation base of the unit according to the dimensions below.

Outdoor Unit Dimensions
Width (W) x Height (H) x Depth (D)

A-09-HP-C-115B & 30.31 x 21.85 x 11.81 in.

A-09-HP-C-230B

(770 x 555 x 300 mm)

A-12-HP-C-115B & 31.50 x 21.81 x 13.11 in.

A-12-HP-C-230B

(800 x 554 x 333 mm)

A-18-HP-C-230B

31.50 x 21.81 x 13.11 in. (800 x 554 x 333 mm)

A-24-HP-C-230B

33.27 x 27.64 x 14.29 in. (845 x 702 x 363 mm)

A-36-HP-C-230B

37.24 x 31.89 x 16.14 in. (946 x 810 x 410 mm)

UNIT MOUNTING DIMENSIONS
The following is a list of different outdoor unit sizes and the distance between their mounting feet. Prepare the installation base of the unit according to the dimensions below.

Units: Inches (millimeters)

Mounting Dimensions

Width (A)

Depth (B)

19.2 in. (487.68 mm)

11.73 in. (297.94 mm)

19.2 in. (487.68 mm)

11.73 in. (297.94 mm)

19.2 in. (487.68 mm)

11.73 in. (297.94 mm)

21.26 in. (540 mm)

13.8 in. (350.52 mm)

26.5 in. (673 mm)

15.9 in. (403 mm)

If you will install the unit on the ground or on a 6. Remove the nuts from expansion bolts, and place

concrete mounting platform, do the following:

outdoor unit on the bolts.

1. Mark the positions for four expansion bolts based on dimensions in the Unit Mounting Dimensions chart.
2. Pre-drill holes for expansion bolts.

7. Put a washer on each expansion bolt, then replace the nuts.
8. Using a wrench, tighten each nut until snug.

3. Clean concrete dust away from holes.
4. Place a nut on the end of each expansion bolt.
5. Hammer expansion bolts into the pre-drilled holes.

WHEN DRILLING INTO CONCRETE, EYE PROTECTION IS RECOMMENDED AT ALL TIMES.

Page 21

mrcool.com

Outdoor Unit Installation

If you will install the unit on a wall-mounted bracket, do the following:
Before installing a wall-mounted unit, make sure that the wall is made of solid brick, concrete, or of similarly strong material. The wall must be able to support at least FOUR times the weight of the unit.
1. Mark the position of bracket holes based on dimensions in the Unit Mounting Dimensions chart.
2. Pre-drill the holes for the expansion bolts.
3. Clean dust and debris away from holes.
4. Place a washer and nut on the end of each expansion bolt.
5. Thread expansion bolts through holes in mounting brackets, put mounting brackets in position, and hammer expansion bolts into the wall.
6. Ensure that the mounting brackets are level.
7. Carefully lift the unit and place its mounting feet on the brackets.
8. Using a wrench, bolt the unit firmly to the brackets.
TO REDUCE VIBRATION OF WALLMOUNTED UNIT If allowed, you can install the wall- mounted unit with rubber gaskets to reduce vibration and noise.
Step 4: Connect signal and power cables
The outside unit’s terminal block is protected by an electrical wiring cover on the side of the unit. A comprehensive wiring diagram is printed on the inside of the wiring cover.

BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS
1. All wiring must comply with local and national electrical codes, and must be installed by a licensed electrician.
2. All electrical connections must be made according to the Electrical Connection Diagram located on the panels of the indoor and outdoor units.
3. If there is a serious safety issue with the power supply, stop work immediately. Explain your reasoning to the client, and refuse to install the unit until the safety issue is properly resolved.
4. Power voltage should be within 90-100% of rated voltage. Insufficient power supply can cause malfunction, electrical shock, or fire.
5. Circuit, including any switches, should have a capacity 1.5 times the maximum unit current (amps).
6. The qualified technician must use an approved circuit breaker or switch that disconnects all poles and has has a contact separation of at least 1/8 in (3 mm).
7. Make sure to properly ground the air conditioner.
8. Every wire must be firmly connected. Loose wiring can cause the terminal to overheat, resulting in malfunction and possible fire.
9. If the unit has an auxiliary electric heater, it must be installed at least 40 in (1 meter) away from combustible materials.
DO NOT connect another appliance to the same circuit.
DO NOT let wires touch or rest against refrigerant tubing, the compressor, or any moving parts within the unit.

mrcool.com

Page 22

Outdoor Unit Installation

BEFORE PERFORMING ANY ELECTRICAL OR WIRING WORK, TURN OFF THE MAINPOWER TO THE SYSTEM.
1. Prepare the cable for connection:

USE THE RIGHT CABLE · See table below for gauge requirements

North America Minimum Wire Gauge for Power Cables

Model Appliance Capacity Amps (A)

AWG

(BTU/hr) MCA MOP Min. Pref.

115V

9K 12K

9K

15 20 14 12 15 20 14 12 10 15 14 14

208/

12K

230V

18K

24K

36K

15 15 14 12

15 20 14 12

20 25 12 10

25 35 10

8

2. Remove the electrical wiring cover from the unit by loosening the 3 retaining screws. Refer to Fig. 5.6.

3. Remove the caps on the conduit panel.

4. Temporarily mount the conduit tubes (not included) on the conduit panel.

5. Properly connect both the power supply and low voltage lines to the corresponding terminals on the terminal block.

6. Ground the unit in accordance with local codes.

7. Be sure to size each wire so that it allows for it to be several inches longer than the required length for wiring.

8. Use lock nuts to secure the conduit tubes.

9. Replace the wire cover and reinstall the 3 screws.

Terminal block Over 1.57 in.(40 mm)

Connecting cable
G
Power supply cord

Conduit panel

Wire Cover

Please select the appropriate through-hole according to the diameter of the wire.
Fig. 5.6

ALL WIRING MUST PERFORMED STRICTLY IN ACCORDANCE WITH THE WIRING DIAGRAM LOCATED INSIDE THE OUTDOOR UNIT’S WIRE COVER.

Page 23

mrcool.com

Refrigerant Piping Connection

66

When connecting the refrigerant piping, DO NOT let substances or gases other than the specified refrigerant enter the unit. The presence of other gases or substances will lower the unit’s capacity,and can cause abnormally high pressure in the refrigeration cycle. This could cause an explosion and/or injury.

NOTE ON PIPE LENGTH
The length of refrigerant piping will affect the performance and energy efficiency of the unit. Nominal efficiency is tested on units with a pipe length of 16.5 ft (5 m). In North America, the standard pipe length is 25 ft (7.5 m). A minimum pipe run of 9.8 ft (3 m) is required to minimize vibration and excessive noise.
Refer to the table below for specifications on the maximum length and drop height of piping.
Maximum Length and Drop Height of Refrigerant Piping per Unit Model

Model
R410A Inverter Split Air Conditioner

Capacity (BTU/h)
< 15,000 15,000 and < 24,000 24,000 and < 36,000
36,000

Max. Length (ft/m)
82 ft (25 m) 98.5 ft (30 m) 164 ft (50 m) 213 ft (65 m)

Max. Drop Height (ft/m)
33 ft (10 m) 66 ft (20 m) 82 ft (25 m) 98 ft (30 m)

Connection Instructions ­ Refrigerant Piping
Step 1: Cut pipes
When preparing refrigerant pipes, take extra care to cut and flare them properly. This will ensure efficient operation and minimize the need for future maintenance.
1. Measure the distance between the indoor and outdoor units.

2. Using a pipe cutter, cut the pipe a little longer than the measured distance.
3. Make sure that the pipe is cut at a perfect 90° angle. Refer to Fig. 6.1 for bad cut examples.

90°

Oblique Rough Warped

Fig. 6.1

mrcool.com

Page 24

Refrigerant Piping Connection

DO NOT DEFORM PIPE WHILE CUTTING
Be extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the heating efficiency of the unit.
Step 2: Remove burrs
Burrs can affect the air-tight seal of refrigerant piping connection. They must be completely removed.
1. Hold the pipe at a downward angle to prevent burrs from falling into the pipe.
2. Using a reamer or deburring tool, remove all burrs from the cut section of the pipe.

Pipe

Reamer

Flare nut
Copper pipe
Fig. 6.3 4. Remove PVC tape from ends of pipe when
ready to perform flaring work. 5. Clamp flare form on the end of the pipe. The
end of the pipe must extend beyond the edge of the flare form in accordance with the dimensions shown in the table below.

Point down
Fig. 6.2
Step 3: Flare pipe ends Proper flaring is essential to achieve an airtight seal. 1. After removing burrs from cut pipe, seal the
ends with PVC tape to prevent foreign materials from entering the pipe. 2. Sheath the pipe with insulating material. 3. Place flare nuts on both ends of pipe. Make sure they are facing in the right direction, because you cannot put them on or change their direction after flaring. See Fig. 6.3.

Fig. 6.4

PIPING EXTENSION BEYOND FLARE FORM

Outer Diameter of Pipe (in/mm)
Ø 0.25″ (Ø 6.35) Ø 0.375″ (Ø 9.52) Ø 0.5″ (Ø 12.7) Ø 0.63″ (Ø 16) Ø 0.75″ (Ø 19)

A (in/mm)

Min.

Max.

0.0275″ (0.7) 0.05″ (1.3)

0.04″ (1.0)

0.063″ (1.6)

0.04″ (1.0)

0.07″ (1.8)

0.078″ (2.0) 0.086″ (2.2)

0.078″ (2.0) 0.094″ (2.4)

Flare form
A

Pipe

Fig. 6.5

Page 25

mrcool.com

Refrigerant Piping Connection

Step 3: Flare pipe ends continued
6. Place flaring tool onto the form.
7. Turn the handle of the flaring tool clockwise until the pipe is fully flared.
8. Remove the flaring tool and flare form, then inspect the end of the pipe for cracks and even flaring.

Radius 4 in (10 cm)

Step 4: Connect pipes

Fig. 6.6

When connecting refrigerant pipes, be careful not to use excessive torque or to deform the piping in any way. You should first connect the low-pressure pipe, then the high-pressure pipe.

MINIMUM BEND RADIUS When bending refrigerant piping, the minimum bending radius is 10 cm. See Fig 6.6.

TORQUE REQUIREMENTS
1. Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque requirements shown in the table below.
2. You can find the Outer Pipe Diameter stamped (in inches) on the valve set of the condenser. Refer to this when finding and applying the torque values in the table below.
3. Note that there may be differences in Torque Wrenches (i.e. automotive torque wrench versus a HVAC torque wrench) and that a socket style wrench cannot be used here.

Outer Diameter of Pipe (in/mm)

TORQUE REQUIREMENTS TABLE

Tightening Torque (lb·ft/N·m)

Flare Dimension (B) (in/mm)

Ø0.25″ (Ø 6.35 mm) 13.28-14.75 lb·ft (18-20 N·m) 0.33″-0.34″ (8.4-8.7 mm)

Ø0.375″ (Ø 9.52 mm) 23.60-28.76 lb·ft (32-39 N·m) 0.52″-0.53″ (13.2-13.5 mm)

Ø0.5″ (Ø12.7 mm) 36.14-43.52 lb·ft (49-59 N·m) 0.64″-0.65″ (16.2-16.5 mm)

Ø0.63″ (Ø16 mm) 42.04-52.37 lb·ft (57-71 N·m) 0.76″-0.78″ (19.2-19.7 mm)

Ø0.75″ (Ø19 mm) 49.42-74.49 lb·ft (67-101 N·m) 0.91″-0.93″ (23.2-23.7 mm)

Flare Shape
90°±4 45°±2
B
R0.4~0.8

mrcool.com

Page 26

Refrigerant Piping Connection
Instructions for Connecting Piping to Indoor Unit
1. Align the center of the two pipes that you will connect. See Fig. 6.7. 2. Tighten the flare nut as tightly as possible by hand. 3. Using an adjustable wrench, grip the nut on the unit tubing. 4. While firmly gripping the nut on the unit tubing, use a torque wrench to tighten the flare nut according to
the torque values in the Torque Requirements table. Loosen the flaring nut slightly, then tighten again.

Indoor unit tubing

Flare nut Pipe

Fig. 6.7

Instructions for Connecting Piping to Outdoor Unit
1. Unscrew the cover from the packed valve on the side of the outdoor unit. (See Fig. 6.9)

Fig. 6.8
USE ADJUSTABLE WRENCH TO GRIP MAIN BODY OF VALVE
Torque from tightening the flare nut can snap off other parts of valve. See Fig. 6.10.

Valve cover

Fig. 6.9
2. Remove protective caps from ends of valves.
3. Align flared pipe end with each valve, and tighten the flare nut as tightly as possible by hand.
4. Using an adjustable wrench, grip the body of the valve. Do not grip the nut that seals the service valve. (See Fig. 6.10)

Fig. 6.10
5. While firmly gripping the body of the valve, use a torque wrench to tighten the flare nut according to the correct torque values.
6. Loosen the flaring nut slightly, then tighten again.
7. Repeat Steps 3 to 6 for the remaining pipe.

Page 27

mrcool.com

Refrigerant Piping Connection
Air Evacuation

7

MC

MC

Preparations and Precautions

Evacuation Instructions

Air and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which can damage the air conditioner, reduce its efficiency, and cause injury. Use a vacuum pump and manifold gauge to evacuate the refrigerant circuit, removing any non-condensable gas and moisture from the system. Evacuation should be performed upon initial installation and when unit is relocated.
BEFORE PERFORMING EVACUATION
Check to make sure that both high-pressure and low-pressure pipes between the indoor and outdoor units are connected properly in accordance with the Refrigerant Piping Connection section of this manual.
Check to make sure all wiring is connected properly.

Before using the manifold gauge and vacuum pump, read their operation manuals to familiarize yourself with how to use them properly.
Manifold Gauge Compound gauge Pressure gauge

-76cmHg
Low pressure valve Pressure hose / Charge hose

High pressure valve
Charge hose
Vacuum pump

Low pressure valve

Fig. 7.1

1. Connect the charge hose of the manifold gauge to
service port on the outdoor unit’s low-pressure valve.

2. Connect another charge hose from the manifold gauge to the vacuum pump.

mrcool.com

Page 28

Air Evacuation

3. Open the low-pressure side of the manifold gauge. Keep the high-pressure side closed.
4. Turn on the vacuum pump to evacuate the system.
5. Run the vacuum for at least 15 minutes, or until the Compound Meter reads -76 cmHG (-105 Pa).
6. Close the low-pressure side of the manifold gauge, and turn off the vacuum pump.
7. Wait for 5 minutes, then check that there has been no change in system pressure.
8. If there is a change in system pressure, refer to Gas Leak Check section for information on how to check for leaks. If there is no change in system pressure, unscrew the cap from the packed valve (high-pressure valve).
9. Insert hexagon wrench into the packed valve (high-pressure valve) and open the valve by turning the wrench in a 1/4 counter clockwise turn. Listen for gas to exit the system, then close the valve after 5 seconds.
10. Watch the Pressure Gauge for one minute to make sure that there is no change in pressure. The Pressure Gauge should read slightly higher than atmospheric pressure.

Flare nut Valve stem

Cap

Valve body

Fig. 7.2

11. Remove the charge hose from the service port.

12. Using hexagon wrench, fully open both the high-pressure and low-pressure valves.

13. Tighten valve caps on all three valves (service port, high-pressure, low- pressure) by hand. You may tighten it further using a torque wrench if needed.

OPEN VALVE STEMS GENTLY
When opening valve stems, turn the hexagonal wrench until it hits against the stopper. DO NOT try to force the valve to open further.

Note on Adding Refrigerant

Some systems require additional charging depending on pipe lengths. The standard pipe length varies according to local regulations. For example, in North America, the standard pipe length is 25 ft (7.5 m). In other areas, the standard pipe length is 16 ft (5 m). The refrigerant should be charged from the service port on the outdoor unit’s low pressure valve. The additional refrigerant to be charged can be calculated using the following formula:

Connective Pipe Length (m)

ADDITIONAL REFRIGERANT PER PIPE LENGTH

Air Purging Method

Additional Refrigerant

Standard pipe length Vacuum Pump

N/A

N/A

Standard pipe length

Vacuum Pump

Liquid Side: Ø 0.25″ (ø 6.35) Inverter R410A:
(Pipe length ­ standard length) x 15 g/m (Pipe length ­ standard length) x 0.16 oZ/ft
Fixed-frequency R410A: (Pipe length ­ standard length) x 20 g/m (Pipe length ­ standard length) x 0.21 oZ/ft

Liquid Side: Ø 0.375″ (ø 9.52) Inverter R410A:
(Pipe length ­ standard length) x 30 g/m (Pipe length ­ standard length) x 0.32 oZ/ft
Fixed-frequency R410A: (Pipe length ­ standard length) x 40 g/m (Pipe length ­ standard length) x 0.42 oZ/ft

CAUTION
DO NOT mix refrigerant types.
Page 29

mrcool.com

Refrigerant Piping Connection
ElEecletrcitcrailcaanldaGnadsGLaeaskLCehaekckCshecks

88

Electrical Safety Checks
After installation, confirm that all electrical wiring is installed in accordance with local and national regulations, and according to the Installation Manual.
BEFORE TEST RUN
Check Grounding Work Measure grounding resistance by visual detection and with grounding resistance tester. Grounding resistance must be less than 4. Note: This may not be required for some locations in the US.
DURING TEST RUN
Check for Electrical Leakage
During the Test Run, use an electro-probe and multimeter to perform a comprehensive electrical leakage test.
If electrical leakage is detected, turn off the unit immediately and call a licensed electrician to find and resolve the cause of the leakage.
Note: This may not be required for some locations in the US.
WARNING ­ RISK OF ELECTRIC SHOCK
ALL WIRING MUST COMPLY WITH LOCAL AND NATIONAL ELECTRICAL CODES, AND MUST BE INSTALLED BY A LICENSED ELECTRICIAN.

Gas Leak Checks
There are two different methods to check for gaseous leaks. Soap and Water Method Using a soft brush, apply soapy water or liquid detergent to all pipe connection points on the indoor unit and outdoor unit. The presence of bubbles indicates a leak. Leak Detector Method If using leak detector, refer to the device’s operation manual for proper usage instructions.
AFTER PERFORMING GAS LEAK CHECKS
After confirming that the all pipe connection points DO NOT leak, replace the valve cover on the outside unit.

Check-point of indoor unit

Check-point of outdoor unit
D

B

C

A

A: Low pressure stop valve B: High pressure stop valve C&D: Indoor unit flare nuts

mrcool.com

Page 30

Test Run

Refrigerant Piping Connection

9

Before Test Run
Only perform test run after you have completed the following steps:
· Electrical Safety Checks ­ Confirm that the electrical system is safe and operating properly
· Gas Leak Checks ­ Check all flare nut connections and confirm that the system is not leaking
· Confirm that gas and liquid (high and low pressure) valves are fully open
Test Run Instructions
You should perform the Test Run for at least 30 minutes. 1. Connect power to the unit. 2. Press the ON/OFF button on the remote
controller to turn it on. 3. Press the MODE button to scroll through the
following functions, one at a time: · COOL ­ Select lowest possible temperature · HEAT ­ Select highest possible temperature 4. Let each function run for 5 minutes, and perform each of the checks listed in the table to the right:

List of Checks to Perform

PASS/FAIL

No electrical leakage

Unit is properly grounded
All electrical terminals properly covered
Indoor and outdoor units are solidly installed
All pipe connection points Outdoor (2): Indoor (2): do not leak
Water drains properly from drain hose
All piping is properly insulated
Unit performs COOL function properly
Unit performs HEAT function properly
Indoor unit louvers rotate properly
Indoor unit responds to remote control

Page 31

mrcool.com

Testing
DOUBLE-CHECK PIPE CONNECTIONS During operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not present during your initial leak check. Take time during the Test Run to double-check that all refrigerant pipe connection points do not have leaks. Refer to Gas Leak Check section for instructions.
5. After the Test Run is successfully complete, and you confirm all check points in List of Checks to Perform have PASSED, do the following:
a. Using remote control, return unit to normal operating temperature.
b. Using insulation tape, wrap the indoor refrigerant pipe connections that you left uncovered during the indoor unit installation process.
IF AMBIENT TEMPERATURE IS BELOW 63°F (17°C)
You cannot use the remote controller to turn on the COOL function when the ambient temperature is below 63°F. In this instance, you can use the MANUAL CONTROL button to test the COOL function.
1. Lift the front panel of the indoor unit, and raise it until it clicks in place.
2. The MANUAL CONTROL button is located on the right-hand side of the unit. Press it 2 times to select the COOL function. See Fig.9.1.
3. Perform Test Run as normal.

Manual control button Fig. 9.1

mrcool.com

Page 32

Refrigerant Piping Connection
EU Disposal Guidelines

10

This appliance contains refrigerant and other potentially hazardous materials. When disposing of this appliance, the law requires special collection and treatment. DO NOT dispose of this product as household waste or unsorted municipal waste. When disposing of this appliance, you have the following options:
· Dispose of the appliance at a designated municipal electronic waste collection facility. · When buying a new appliance, the retailer will receive the old appliance free of charge. · The manufacturer will receive the old appliance free of charge. ·
Special notice
Disposing of this appliance in the forest or other natural surroundings endangers your health and is bad for the environment. Hazardous substances may leak into the ground water and enter the food chain.

Page 33

mrcool.com

Advantage Series
ELECTRICIAN and/or HVAC TECHNICIAN: LICENSE #: INSTALLATION DATE: INSTALLATION LOCATION: SERIAL NUMBER:
The design and specifications of this product and/or manual are subject to change without prior notice. Consult with the sales agency or manufacturer for details.

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals