PHILIPS BN126C CoreLine Batten Emergency Light Instruction Manual
- June 12, 2024
- Philips
Table of Contents
CoreLine Batten
BN126C Emergency
Instruction Manual
BN126C CoreLine Batten Emergency Light
TYPE| Energy efficiency class| P
(W)| ( W) System light
output (Lm)| System light output
Emergency mode (Lm)|
---|---|---|---|---|---
BN126C LED41s/840 PSU ELB3 L1200| D| 36| 4100| 480| 1.45
BN126C LED52s/840 PSU ELB3 L1500| D| 44| 5200| 500| 1.70
BN126C LED80s/840 PSU ELB3 L1500| D| 64| 8000| 500| 1.75
- **** The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
- The light source of this luminaire is not replaceable; when the light source reaches its end of life the whole luminaire shall be replaced.
- Luminaire must not be used or stored in corrosive environment where hazardous materials such as Sulphur, chlorine, phthalates, etc, are present.
- Water entering into IP20 luminaire is strictly prohibited. IP20 luminaire is not protected against wet condition, water ingress may cause electrical failure or unsafe conditions.
- Luminaire is rated at IP40 from the front (part 1) and IP20 for a complete housing (part 2).
ATTENTION OBSERVE PRECAUTIONS FOR HANDLING ELECTROSTATIC SENSITIVE DEVICES
Service data for battery change:
Battery Unit
Manufacturer| Philips
Unit:| TrustSight 6,4V 4cell
3000 mAh battery LFP
Technology| LFP
Capacity| 3000 mAh
Power| 4,8 W
Duration| 3 h
Nominal voltage| 6,4 V
Maintenance instructions
To assure the lighting quality of this unique LED lighting concept there are only a few instructions regarding the maintenance of this LED luminaire:
- Do not stare into LED light beam.
- The luminaire shall be installed by a qualified electrician and wired in accordance with the latest IEE electrical regulations or the national requirements.
- Above average concentration of sulfur effects the useful lifetime of the product. E.g: Light color changes from white to blue. Typically in chicken & pig farms.
Functional Notice for Emergency Lighting
Automatic emergency time selection
After installation and power up the driver will detect the battery and start
the automatic detection process.
- During automatic detection, the indicator LED will light up with short green flashes.
- Between minimum 6 and maximum 30 seconds the Trust Sight driver will set the battery type (number of cells) and will set the emergency output power accordingly.
After that, the sister is defined and fully operational. The battery type
definition has influence on the performance during the self-test and on the
battery charge method. When the automatic battery detection process is
disrupted, e.g. by switching off the permanent mains, the detection process is
stopped and the Trust Sight emergency driver will go into emergency made with
the lowest output power. At a nex t power up, the automatic detection process
will start again.
Periodic testing
Periodic tests of emergency lighting luminaires must be performed according to
ENS0172 clause 7.2.3 and 7.2.4. Switch on in the emergency mode each month by
simulation of a failure of the supply to the normal lighting for a period
sufficient to ensure that each lamp is illuminated. Twice per year, each
luminaire shall be tested for its full rated duration (at least 3hrs).
For more information please consult the Trust Sight Gen 3 Design in guide. The
latest version is available online.
LED indicator (color/ flashing)| Error condition| Cause|
Solution
---|---|---|---
Green / no flashing| | System 01( battery fully charged
Off| | Mains off, EM mode, Rest mode, test in progress
Green / slow (0.25s on, 1.25s off)| | System OK battery is charging
Green / fast (025s on, 0.25s off)| | System OK, recently tested (< 5 days,
Australia mode only)
Red/no flashing
ga| Battery voltage too high or too low| No battery connected| Connect battery
| Wrong or bad battery connected| Replace battery
Red / fast (0.25s on, 0.25s off)| Output voltage too low or too high| Wrong
LED load connected| Conned right load and perform functional test
No load connected or output shorted| Wrong connection| Connect right load and
perform functional test
Red /slow (0.25s on, 1.25s off)| Failed test due to battery| Battery end of
life Charger failure| Replace battery and perform duration test Replace driver
Red-green / fast
Fast flashing: (on-time = 0.25s, off-time = 0.25s)
Slow flashing: (on-time = 0.25s, off-time = 1.25s)| | DALI device
identification|
Green / short
on-time = 50ms, off-time = 0.95s)| | Battery detection|
Signify Holding.
All rights reserved. This document contains information relating to the
product portfolio of Signify which information may be subject to change. No
representation or warranty as to the accuracy or completeness of the
information included herein is given and any liability for any action in
reliance thereon is disclaimed. The information presented in this document is
not intended as any commercial offer and does not form part of any quotation
or contract. Philips and the Philips Shield Emblem are registered trademarks
of Koninklijke Philips N.V.. All other trademarks are owned by Signify Holding
or their respective owners.
Emergency Luminaires
In case a self-contained emergency driver has been added, this is how to set
the timers ilEC62034 (§6.3.2)):
DAIJ version: Check IEC 62386 part 202.
PRO version: The first test is randomized. Then a fixed schedule is
maintained, there is no need to set the timers or take special precautions
when powering
BASIC version: No timers available, only manual testing through the test
button.
http://www.lighting.philips.com/main/systems/themes/service- tag.html
To get an overview of all spare parts for a luminaire, please refer to detailed instructions in the service manual available via the Signify Service tag apps (Android and i0S).
https://play.google.com/store/apps/details?id=com.philips.servicetag
Disconnect Befor servicing
Luminaire has basic insulation between Low Voltage supply control connector
The Light source ante Cat clear armor the external Bettie cal In tis lunitalre
Vial be ream) Tie Mr. Igniter rib Its service agent or a snare q parson
Stooge, Installation, use. worn anti martensite teem weds mats to to promos
rami academy tiptoes n ?Is view+ ax ore( ratoons as may to Imam oy Ls to
gatarom care use or me wow Qin crave e cane to moat- ID Ise rsr-Jacris 17fa
mite }cu emeriti to wan ants. ton natation a ult.* zing!, m me caving, rem ‘JD
zed uptorn ist a Lariat.< tuque rrt,asscrom oats hem be repower asap vie
reflect xrwespeancation n assume-e mans- lienor over mom.
This part tartans a Nit smite of energy eluent amass: see lathe or label.
©2022 Signify Holding
All rights rimmed. This document contains information relating to the product
portfolio of Signify which information may be s abject to change. No
representation or warranty as to the accuracy or completeness of the
information included herein b given and any liability for any action in
reliance thereon is disclaimed. The information presented in this document is
riot intended as any cornmenial offer and does not form part of any quotation
or contract. Philips and the Philips Shield Emblem are registered trademarks
of Koninkkke Philips N.V.. M other trademarks are owned by Signify Holding or
their respective owners.