nVent RAYCHEM S-150 Low Profile Splice Kit User Guide

June 10, 2024
nVent RAYCHEM

nVent RAYCHEM S-150 Low Profile Splice Kit

nVent RAYCHEM S-150 Low Profile Splice Kit

TOOLS REQUIRED

nVent RAYCHEM S-150 Low Profile Splice Kit 1

SAFETY WARNING

WARNING:

  • To prevent electrical shock or fire, this product must be installed correctly. Water ingress must be avoided before and during the installation.
  • De-energise circuits before installation or servicing.Maximum nominal current rating of over-current protection:
  • 40 A Persons involved in the installation and testing of electric heat tracing systems shall be suitably trained in all special techniques required.
  • Installation shall be carried out under the supervision of a qualified person Ground fault equipment protection must be used on each heating cable circuit as arcing may not be stopped by conventional circuit breakers. Before installing this product, read the instructions completely.
  • Keep ends of heating cables and kit components dry before and during installation.
  • The electrically conductive covering (braid) of the heating cable shall be connected to a suitable earthing terminal.
  • The presence of the heating cables shall be made evident by the posting of caution signs or markings at appropriate locations and/or at frequent intervals along the circuit
  • The insulation resistance of the heating cable shall be measured and recorded after installation and shall not be less than 20 MOhm
  • The purchaser should make the manufacturer aware of any external effects or aggressive substances that the equipment may be exposed to.

CAUTION:
Prolonged or repeated contact with the sealant in the core sealer may cause skin irritation. Wash hands thoroughly. Overheating or burning the sealant will produce fumes that may cause polymer fume fever. Avoid contamination of cigarettes or tobacco. Consult MSDS VEN 0058 for further information

Schedule of limitations

The maximum surface temperature depends on the configuration of the heat tracing system, determined in accordance with IEC/IEEE 60079-30-1.

  • Minimum ambient temperature: –55°C
  • Maximum ambient temperature: +55°C
  • Maximum operating temperature, power “on”: +150°C
  • Maximum exposure temperature, power “off”: +200°C

Installation instruction for low profile insulation splice kit nVent RAYCHEM S-150. For use with nVent RAYCHEM BTV, QTVR, XTV and KTV heating cables.

  • Rated Voltage: 277 V
  • Rated Current: 40A

INSTALLATION INSTRUCTION

nVent RAYCHEM S-150 Low Profile Splice Kit 2 nVent RAYCHEM S-150 Low Profile Splice Kit 3 nVent RAYCHEM S-150 Low Profile Splice Kit 4 nVent RAYCHEM S-150 Low Profile Splice Kit 5 nVent RAYCHEM S-150 Low Profile Splice Kit 6 nVent RAYCHEM S-150 Low Profile Splice Kit 7 nVent RAYCHEM S-150 Low Profile Splice Kit 8 nVent RAYCHEM S-150 Low Profile Splice Kit 9

United Kingdom
Tel 0800 969 013
Fax 0800 968 624
salesthermalUK@nVent.com

References

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

nVent RAYCHEM User Manuals

Related Manuals