iO HVAC Controls ZP3-HPS 3 Heat 2 Cool Heat Pump Instruction Manual
- June 12, 2024
- iO HVAC Controls
Table of Contents
ZP3-HPS 3 Heat 2 Cool Heat Pump
Instruction Manual
ZP3-HPS Installation and Operation Instructions
3 Heat / 2 Cool Heat Pump with Fossil Fuel option
Auto Changeover – First Call Priority – Time Share
Sequence of Operation:
The ZP3-HPS is a residential / light commercial zone control system that
allows a single HVAC unit to have up to three separate zones. Each zone is
controlled by its own space thermostat and motorized zone damper. If a zone
thermostat calls for heating or cooling, the zones not calling will have their
dampers powered closed, and the zone calling will have its damper opened. The
heating or cooling equipment will also be brought on at the same time. When
the zone calling is satisfied, the heating or cooling equipment turns off. If
one zone calls for heating and another zone calls for cooling, the first zone
to call receives priority. When the first call is satisfied, the system will
changeover and take care of the opposite call. If a zone being served (heating
or cooling) has not been satisfied within 20 minutes while an opposite call is
taking place, the system will changeover. When the zone is satisfied or 20
minutes has elapsed, the system will again changeover if an opposite call
exists. This is referred to as Auto Changeover – First Call Priority – Time
Share. In the event of a tie, cooling will receive priority. The changeover
valve only changes position when the mode of operation changes.
High and Low Limit Protection:
The ZPA-DTS Discharge Temperature Sensor should be mounted on the discharge
air plenum of the HVAC unit and wired to the DA terminals on the panel. The
sensor is used for both high and low limit protection. The high limit setting
can be adjusted using the two slide switches located on the panel. (See switch
location and settings on page 2) The low limit is fixed at 45° F. When the
discharge air temperature rises above the high limit setting or falls below
the low limit setting, the panel will cycle the equipment off while the fan
continues to run. The LIMIT LED blinks when high or low limit is reached.
Ventilation Mode:
Zone ventilation is established by the individual zone thermostat fan setting.
Any thermostat set in the fan AUTO mode will not receive ventilation air when
there are no heating or cooling calls. Any thermostat set in the fan ON mode
will receive ventilation air whenever there are no heating or cooling calls
taking place.
Power Requirements:
The ZP3-HPS requires a separate 24 Vac transformer. A 40 VA transformer will
power the panel and up to four (4) dampers. A75 VA transformer will power the
panel and up to seven (7) dampers. If more than three (3) dampers for an
individual zone are required, a RY-1-HB relay should be used with an
additional properly sized transformer. iO Systems HD-XXXX rectangular and iO
D-XX round dampers are powered closed / spring return open. Damper actuators
are rated at 10 VA. If 3-wire dampers (powered open / powered closed) are
installed, VA ratings will vary depending on the damper actuator used.
Wiring:
All wiring should be conventional 18 gauge thermostat wire. Thermostats and
zone dampers may be located up to 300 feet from the ZP3-HPS panel.
Installation
Mounting the Panel:
Carefully remove the ZP3-HPS panel and cover from the shipping carton. Slide
the PC board out of the snap track base and mount the base to a flat surface
either on or near the HVAC indoor unit in an area that will facilitate easy
accessfor wiring. Reinstall the PC board by carefully centering it over the
base and snapping it back into the track groves.
Wiring the Zone Thermostats and Dampers:
Refer to the logic panel wiring diagram. Wire zone 1 thermostat and its
associated damper to the ZONE 1 terminals on the logic panel. Wire zone 2 and
3 thermostats and dampers in the same manner.
Wiring the HVAC Equipment:
Wire the HVAC unit to the ZP3-HPS HVAC UNIT terminals. Note: Do not wire the
equipment common to the ZP3-HPS panel.
Installing and Wiring the ZPA-DTS Discharge Temperature Sensor :
Drill a 15/32” hole in the middle of the main discharge air plenum
approximately 18″ to 30″ from the heat pump electric strip heater or the
furnace heat exchanger in a fossil fuel application. Slide the discharge air
probe into the hole and use two self-tapping sheet metal screws to secure the
base to the plenum. Use conventional 18-2 thermostat wire and wire nuts to
attach the sensor leads. Replace the cover with the wire nut connections
inside. Strip 1/8” insulation off of each wire at the otherend and and the
wires to the screw terminals marked DAon the panel. Wiring the Transformer
:
Wire a separate 24 Volt transformer of the proper VA to the logic panel
terminals marked (R) and (X). Do not power the panel up until wiring is
completed.
Test, Check and Startup:
- Verify that all component wires have been connected to the proper terminals and are secure.
- Disconnect the HVAC equipment (R) terminal wire atthe panel and apply 24 Volts to panel.
- Take a jumper wire and momentarily short the DA terminals. This will put the panel’s time delays in “speed up” mode.
- Place the zone thermostats in the OFF position.
- The panel accepts 2-wire (power close / spring open) or 3-wire (power open / power close) zone dampers. 2-wire dampers should be wired to the (C)and (PC)terminals.
- Place zone one thermostat in the fan ON mode. ZD1 LED will remain on and ZD2 and ZD3 LED willgo out. The (G) FAN LED will come on.
- Confirm that zone one damper is in the open position and zone two and three dampers are closed.
- Leave zone one thermostatin fan ON and place zone two thermostat in the fan ON mode. ZD2 LED willcome on.
- Confirm that both zone one and zone two dampers are in the open position and zone three damperis closed.
- Leave zone one and zone two thermostats in Fan ON and place zone three thermostat in the fan ON mode. ZD3 LED will come on. Confirm that all zone dampers are in the open position.
- Place all zone thermostats in the Auto fan mode.
- Remove 24 Volts to the panel and reconnect the HVAC ® wire.
- When 24 Volts is applied again to the panel, the internal time delays will be activated.
- Place zone thermostats in proper mode of operation.
- Confirm that the LIMIT LED is ON. If not, check LIMIT wiring. If the system goes out on high orlow limit, the LIMIT LED will blink.
Fossil Fuel Applications:
Fossil fuel may be used as the auxiliary heat source with the iO-ZP3-HPS
allowing for up to 2 stages of cooling and 3 stages of heating. For systems
having a 2 stage furnace, W1 and W2 are jumpered at the furnace. This method
utilizes the internal furnace upstage timer to bring on second stage fossil
fuel.
Sequence of Operation:
2 Heat/1 Cool
When a zone thermostat calls for heating and the outdoor temperature is above
the balance point as established by the iO-ZP3-OTS, the heat pump operates as
first stage heat. If there is a call for second stage heat (auxiliary), or if
any thermostat is placed in the emergency heat mode, the panel will
automatically de-energize the heat pump and bring on the furnace. When the
outdoor temperature falls below the balance point, the heat pump will be
locked out and the furnace will become first stage.
3 Heat/2 Cool
When a zone thermostat calls for heating and the outdoor temperature is above
the balance point as established by the i0-ZP3-OTS, both compressor stages of
the heat pump will operate as normal. If there is a call for third stage heat
(auxiliary), or if any thermostat is placed in the emergency heat mode, the
panel will automatically de-energize all heat pump stages and bring on the
furnace. When the outdoor temperature falls below the balance point, the heat
pump will be locked out and the furnace will become first stage.
Installing and wiring the i0-ZP3-OTS
The i0O-ZP3-OTSis an adjustable electronic sensor used for both selecting the
outdoor balance point and measuring the outdoor temperature. This information
determines when the heat pump will be locked out and only the furnace will be
used for heating.
Before installing the iO-ZP3-OTS, remove the retaining cover and select the
outdoor balance point temperature using the slide switches. Mount the iO-ZP3-OTS on a vertical surface inside the heat pump
cabinet to avoid direct sunlight, freezing rain or snow.
i0-ZP3-0TS
Specifications
Panel Dimensions:
Height:
Width:
Depth:| 8.0 Inches
6.0 Inches
1.375 Inches
Mounting:
Snap Track with 2 back plate screws
Operating Temperature Rating:
-40°F to 150°F
Operating Humidity:
5% to 90% RH non-condensing
Wiring:
18-gauge wire for all equipment and system connections
Time Delays:
3 minutes minimum off between heating and cooling calls
3 minutes minimum off on high and low limit
20 minute time share Purge ON = 1 minute
Thermostats:
Single or multi-stage heat pump
Programmable or non-programmable
Auto or manual changeover
Terminal Designations
Thermostats:
C
R
w
Y1
Y2
G| 24Vac (Common)
24Vac (Hot)
Auxiliary or Emergency Heat
First Stage Compressor
Second Stage Compressor
Fan
Dampers:
PC| Powered Closed
C| Common
PO| Powered Open
High / Low Limit
DA | Land to ZPA-DTS |
---|---|
DA | Land to ZPA-DTS |
Outdoor Thermostat
OTS | Land to iO-ZP3-OTS |
---|---|
OTS | Land to iO-ZP3-OTS |
HVAC Equipment:
RH | 24Vac Heating Transformer |
---|---|
RC | 24Vac Cooling Transformer |
w | Auxiliary or Emergency Heat |
Y1 | First Stage Compressor |
Y2 | Second Stage Compressor |
G | Fan |
o/B | Reversing Valve |
Panel Power :
R | 24Vac (Hot) |
---|---|
X | 24Vac (Common) |
Typical System Layout
Indianapols, IN 46237
www.iohvaccontrols.com
For Technical Support Call Toll Free:
866-225-5032
10-06-1167-011218
References
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>