iO HVAC Controls ZP4-ESP 4 Zone Control Panel Owner’s Manual
- June 9, 2024
- iO HVAC Controls
Table of Contents
ESP 4 ZONE PANEL
ZP4-ESP
ZONE CONTROL PANEL
The ZP4-ESP is a 4 zone panel that integrates our award winning ESP technology
to completely eliminate the need to install a bypass damper. This 3H/2C zone
panel comes with a static pressure sensor. The system works like any standard
zone control system with one exception; a static pressure sensor continuously
monitors the system static pressure. If the static pressure goes above
setpoint, the ESP panel will power the selected non-calling zone dampers open
just enough to relieve the excess pressure. Tests indicate that bleeding a
small amount of conditioned air for a short time into non-calling zones has
little to no impact on the zone temperature.
The panel can be used with single-stage, multi-stage, heat pump or dual fuel
equipment. A wide range of control options provide ultimate application
flexibility including adjustable high/low limits, adjustable high/low balance
point, and 2 zone, 2nd stage capacity control.
Static pressure sensor & panel cover included
*For ESP functionality, 3-wire MD dampers and static pressure sensor must be used
NO BYPASS REQUIRED!
Features and Benefits:
- 4 zone universal panel with ESP capability
- Smallest universal panel offered by iO
- Up to 2H/2C conventional or 3H/2C heat pump and dual fuel
- Auto changeover
- First call priority with time share
- 2 zone, 2nd stage capacity control
- Purge cycle option
- Adjustable high and low limits
- Adjustable high and low balance points
- Easy switch configuration
- Fused protected inputs and outputs
Warranty:
- 10 Years
Specifications:
Construction | Aluminum enclosure with snap-on panel cover |
---|---|
Mounting | Snap track with 2 back plate screws |
Dimensions | 8.75″ Height x 7″ Width x 1.5″ Depth |
Operating Temperature | -40° F to 150° F |
Time Delays | 5 minute changeover; 3 minute off on high or low limit 20 minute |
time share
Discharge Air Limits| Low Limit (30° F to 55° F); High Limit (100° F to 180°
F)
BOARD DIAGRAM
1. 3 AMP FUSE PROTECTS PRINTED CIRCUIT BOARD
2. 24 VOLT TRANSFORMER TERMINALS
3. ZONE 1 DAMPER TERMINALS
4. ZONE 2 DAMPER TERMINALS
5. ZONE 3 DAMPER TERMINALS
6. ZONE 4 DAMPER TERMINALS
7. DISCHARGE AIR SENSOR TERMINALS
8. OUTDOOR TEMPERATURE SENSOR TERMINALS
9. STATIC PRESSURE SENSOR TERMINALS
10. SPARE 3 AMP FUSES
11. HVAC EQUIPMENT TERMINALS
12. 3 AMP FUSE PROTECTS THE RELAY CONTACTS
13. PANEL POWER LED
14. ZONE DAMPER 1 LED
15. ZONE DAMPER 2 LED
16. ZONE DAMPER 3 LED
17. ZONE DAMPER 4 LED
18. ESP LED
19. HIGH LIMIT POTENTIOMETER
20. LOW LIMIT POTENTIOMETER
21. DISCHARGE AIR SENSOR LED| 22. HIGH BALANCE POINT POTENTIOMETER
23. LOW BALANCE POINT POTENTIOMETER
24. OUTDOOR TEMPERATURE SENSOR LED
25. Y1 RELAY LED
26. Y2 RELAY LED
27. W1/AUX RELAY LED
28. W2/OB RELAY LED
29. G FAN RELAY LED
30. ZONE 1 BYPASS JUMPER
31. ZONE 2 BYPASS JUMPER
32. ZONE 3 BYPASS JUMPER
33. ZONE 4 BYPASS JUMPER
34. ZONE 1 THERMOSTAT TERMINALS
35. ZONE 2 THERMOSTAT TERMINALS
36. ZONE 3 THERMOSTAT TERMINALS
37. ZONE 4 THERMOSTAT TERMINALS
38. TIME DELAY SPEED UP LED
39. TIME DELAY SPEED UP BUTTON
40. SYSTEM CONFIGURATION SELECTOR SWITCHES
41. SYSTEM CONFIGURATION SWITCH DEFINITIONS
---|---