IO HVAC Controls ZP3-HPS-ESP 3 Heat / 2 Cool Heat Pump or Dual Fuel Instruction Manual
- June 4, 2024
- iO HVAC Controls
Table of Contents
- IO HVAC Controls ZP3-HPS-ESP 3 Heat / 2 Cool Heat Pump or Dual Fuel
- ZP3-HPS-ESP Installation and Operation Instructions3 Heat / 2 Cool Heat
- OVERVIEW:
- SEQUENCE OF OPERATION:
- HIGH AND LOW LIMIT PROTECTION:
- VENTILATION MODE:
- POWER REQUIREMENTS:
- ZP3-HPS-ESP Panel Layout
- ZP3-HPS-ESP TERMINAL DESIGNATIONS
- ZP3-HPS-ESP TERMINAL DESIGNATIONS
- ZP3-HPS-ESP LED STATUS DEFINITIONS
- SELECTOR SWITCHES
- SPEED UP BUTTON
- BALANCE POINT DIALS
- ESP ZONE BYPASS SELECTOR PINS
- MOUNTING THE ENCLOSURE:
- NOTE:
- WIRING ZONE THERMOSTATS:
- WIRING ZONE DAMPERS:
- WIRING TO THE HVAC EQUIPMENT:
- Note: Do not wire the equipment common to the HVAC UNIT terminals on the
- INSTALLING AND WIRING THE ZPA-SPS STATIC PRESSURE SENSOR:
- INSTALLING AND WIRING THE ZP3-HPS-ESP
- WIRING THE ZPA-OTS OUTDOOR SENSOR FOR HIGH AND LOW BALANCE POINT CONTROL:
- TEST, CHECK AND STARTUP:
- TEST, CHECK AND STARTUP:
- Enclosure:
- Panel Dimensions:
- PC Board Mounting:
- Operating Temperature Rating:
- Operating Humidity:
- Wiring:
- Time Delays:
- Thermostats:
- FIELD WIRING TERMINALS:
- HVAC Equipment:
- High / Low Limit
- Outdoor Temperature Sensor
- Panel Power:
- Damper Outputs
- Pressure Sensor:
- SPECIAL ADDENDUM
- Read More About This Manual & Download PDF:
- References
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
IO HVAC Controls ZP3-HPS-ESP 3 Heat / 2 Cool Heat Pump or Dual Fuel
Instruction Manual
ZP3-HPS-ESP Installation and Operation Instructions3 Heat / 2 Cool Heat
Pump or Dual Fuel
Auto Changeover – First Call Priority – Time Sharewith Integrated ESP
Static Pressure Module
OVERVIEW:
The ZP3-HPS-ESP is a residential/light commercial zone control panel that
includes integrated ESP static pressure control logic designed to eliminate
the need for a conventional
bypass damper when used with 3-wire zone dampers.
SEQUENCE OF OPERATION:
The panel allows a single HVAC unit to have up to three separate zones. Each
zone is controlled by its own thermostat. When a zone thermostat calls for
heating or cooling, the zones not calling
will have their dampers powered closed, and the zones calling will have their
dampers powered opened. The heating or cooling equipment will also be brought
on.
As zone dampers open and close, the ZPA-SPS Static Pressure Sensor
continuously monitors the system static pressure. If the static pressure goes
above the static pressure setpoint, the panel will send a signal to all
selected noncalling zone dampers to start to open to a point where the static
pressure setpoint is maintained.
The SPS LED will come on with the non-calling zone LEDs until the static
pressure reaches setpoint and then the LEDs will turn off. The
small amount of air allowed to bleed into noncalling zones eliminates air
noise and assures proper airflow through the HVAC system. This also prevents
coil freeze up and high temperature issues. When all calls are satisfied, all
zone dampers will go to the full open position provided none of the
thermostats are calling for ventilation mode. If opposite calls take place,
the first zone to call receives priority. When the first call is satisfied,
the system will changeover and take care of the opposite call. If zones being
served (heating or cooling) have not been satisfied within 20 minutes while an
opposite
call is taking place, the system will changeover.
When the zone is satisfied or 20 minutes has elapsed, the system will again
changeover if an opposite call exists. This is referred to as Auto-
Changeover – First Call Priority – Time Share. In the event of a tie, cooling
will receive priority. The heat pump reversing valve only changes position
when the mode of operation changes.
HIGH AND LOW LIMIT PROTECTION:
The ZPA-DTS Discharge Temperature Sensor should be mounted on the discharge
air plenum of the HVAC unit and wired to the DA terminals on the panel. The
sensor is used for both high (adjustable) and low (fixed) limit protection.
The high limit setting can be adjusted using the two slide switches located on
the panel. (See switch location and settings on page 2) Low limit is fixed at
45° F.
When the discharge air temperature rises above the high limit setting or falls
below the low limit setting, the panel will cycle the equipment off while the
fan continues to run. The LIMIT LED blinks when high or low limit is reached
and a 3 minute time delay is activated to prevent short cycling of the
equipment.
VENTILATION MODE:
Zone ventilation is established by the individual zone thermostat fan setting.
When no calls are taking place, any thermostat set in the fan AUTO mode will
not receive ventilation air and its zone
damper will be closed. Any zone thermostat set in the fan ON mode will receive
ventilation air and its zone damper will be opened. Heating or cooling calls
take priority over ventilation mode. The ESP
function will continue to maintain the system static pressure by modulating
open non-calling ventilation zones as required.
POWER REQUIREMENTS:
The panel is powered by a single 24VAC, 40VA transformer. Never use the equipment
ZP3-HPS-ESP Panel Layout
ZP3-HPS-ESP TERMINAL DESIGNATIONS
ZP3-HPS-ESP TERMINAL DESIGNATIONS
ZP3-HPS-ESP LED STATUS DEFINITIONS
SELECTOR SWITCHES
CON/FOSSIL
OFF = CONVENTIONAL HEAT PUMP ON = FOSSIL FUEL SYSTEM O/B
OFF = ‘O’ REVERSING VALVE (ENERGIZES IN COOLING)
ON = ‘B’ REVERSING VALVE (ENERGIZES IN HEATING) PURGE
OFF = NO FAN PURGE ON = 1 MINUTE FAN PURGE AFTER CALL DROPS OUT
SPEED UP BUTTON
The Speed Up button can be used to put the internal panel time delays in speed
up mode. When the button is pushed, the Speed
Up LED will blink. Pushing the bottom again will reset the time delays and the
LED will turn off or will automatically reset in 10minutes.
BALANCE POINT DIALS
(USED WITH OPTIONAL Z-300-OTS OUTDOOR SENSOR)
When a ZPA-OTS outdoor sensor is wired to the OT terminals on the panel, both
High and Low balance points settings can be adjusted using the calibrated
balance point dials. High BP is adjustable from 45° F to 65° F. Low BP is
adjustable from 0° F to 40° F. High and Low balance point control can be used
for both conventional heat pumps and fossil fuel systems. If the outdoor
temperature goes above the High BP setting, the system will not stage
auxiliary heat. If the outdoor temperature falls below the Low BP setting,
only the auxiliary heat source will be used. High BP can be overridden by
placing any zone thermostat in the emergency heat mode
ESP ZONE BYPASS SELECTOR PINS
Each zone has an ESP Zone Bypass selector pin. The panel comes from the
factory with all zones set to ON.
By placing a zones selector pin in the OFF position, this will prevent air
from bleeding into the zone when it is not calling even if the static pressure
goes above the setpoint. This is sometimes useful for basement zones or zones
with small CFM requirements providing other non-calling zones have the CFM
capacity to allow enough air to bleed without causing air noise without over
heating and cooling.
MOUNTING THE ENCLOSURE:
Carefully remove the panel from the shipping carton. Remove the cover and any
packing material. Locate the panel on a flat, noncondensating, vertical
surface near the indoor
unit that will facilitate ease of wiring and service access. Use appropriate
anchors and screws to secure the panel to the surface.
NOTE:
The panel utilizes home run wiring. Tag each zone thermostat cable and its associated zone damper cable to minimize wiring errors.
WIRING ZONE THERMOSTATS:
Use conventional 18-8 thermostat wire. After removing the outer jacket, strip approximately 1/8” insulation off of each wire. Land each wire to its designated screw terminal.
WIRING ZONE DAMPERS:
Use conventional 18-3 thermostat wire. After removing the outer jacket, strip approximately 1/8” insulation off of each wire. Land each wire to its designated screw terminal
WIRING TO THE HVAC EQUIPMENT:
Use conventional 18-6 thermostat wire. After removing the outer jacket, strip
approximately 1/8” insulation off of each wire. Land each wire into its
designated screw terminal on the HVAC
UNIT terminals
Note: Do not wire the equipment common to the HVAC UNIT terminals on the
panel.
INSTALLING AND WIRING THE ZPA-DTS DISCHARGE TEMPERATURE SENSOR:
Drill a 15/32” hole in the middle of the main discharge air plenum
approximately 18” to 30” from the heat pump electric strip heater or the
furnace heat exchanger in a fossil fuel application. Slide the discharge air
probe into the hole and use two self-tapping sheet metal screws to secure the
base to the plenum. Use conventional 18-2 thermostat wire and wire nuts to
attach the sensor leads. Replace the cover with the wire nut connections
inside. Strip 1/8” insulation off of each wire at the other end and land the
wires to the screw terminals marked DA on the panel.
INSTALLING AND WIRING THE ZPA-SPS STATIC PRESSURE SENSOR:
The ZPA-SPS pressure sensor should be installed on a flat, surface so that the
diaphragm is in the vertical position. Use the 1/4” x 36” tubing provided and
connect one end to the (P1+) high
pressure fitting on the sensor. The other end of the tubing should be
connected to the plastic sensing probe mounted in the main discharge air
plenum prior to any zone dampers or duct transitions. The
sensing probe is 3-1/8” x 1/4” O.D. Install and mount the probe with the arrow
in the direction of airflow. The ZPA-SPS is factory set for 0.35” W.C. but is
fully adjustable from 0.08” to 1.20” W.C. The
terminals are not polarity sensitive. Use 18-2 thermostat wire. After removing
the outer jacket, strip approximately 1/8” insulation off of each wire. Land
the wires to the 2 and 3 terminal on the
pressure sensor. Repeat the process on the other end and land the wires to the
screw terminals on the panel marked SPS 2 and 3.
INSTALLING AND WIRING THE ZP3-HPS-ESP
WIRING THE TRANSFORMER:
Wire the separate 24 Volt transformer to the 24VAC POWER ‘R’ and ‘C’
terminals. Use conventional 18-2 thermostat wire. After removing the outer
jacket, strip approximately 1/8” insulation off of each wire. Land each lead
to the 24VAC POWER screw terminals marked C and R.
WIRING THE ZPA-OTS OUTDOOR SENSOR FOR HIGH AND LOW BALANCE POINT CONTROL:
The balance point feature can be used for both conventional or fossil fuel
applications allowing up to 2 stages of cooling and 3 stages of heating.
For fossil fuel systems having a 2 stage furnace, ‘W1’ and ‘W2’ are jumpered
at the furnace. This method utilizes the internal furnace upstage timer to
bring on second stage fossil fuel. The
ZPA-OTS Outdoor Sensor can be used for both high and low balance point control
by adjusting the onboard balance point dials on the panel. High BP is
adjustable from 45° F to 65° F. Low BP
is adjustable from 0° F to 40° F. If the outdoor temperature goes above the
High BP setting, the system will not stage auxiliary heat. If the outdoor
temperature falls below the Low BP setting, only the auxiliary heat source
will be used. High BP can be overridden by placing any zone thermostat in the
emergency heat mode
Mount the sensor inside the heat pump cabinet to avoid direct sunlight,
freezing rain or snow.
The sensor requires separate 18-2 thermostat wire. Connect the sensor leads
using wire nuts. Land the other end to the SENSOR screw terminals marked OT on
the panel.
TEST, CHECK AND STARTUP:
- Verify that all component wires have been connected to the proper terminals and are secure.
- Make sure that the selector switches on the panel are in their proper position for the specific application.
- Apply 24 Volt powerto the panel.
- Place all zone thermostats in the OFF mode with Auto fan.
- With no calls taking place, the following panel LEDs should be lit: 24V LIMIT ZD1 ZD2 ZD3 6. Visually confirm that all zone dampers are in the open position.
- Place zone 1 thermostat in the continuous fan ON mode and the system blower should come on.
The following panel LEDs should be lit: 24V G LIMIT ZD1 Note: If system static pressure goes above setpoint, the SPS LED will light along with the non- calling zone LEDs until non-calling zone dampers modulate to relieve the static pressure then both LEDs will turn off. 8. Put zone 1 thermostat in Auto fan and repeat the same steps for zone 2 and zone 3. The only change in LED status will be ZD2 LED will light for zone 2 and ZD3 LED will light for zone 3. 9. Once the ventilation test is completed, and the zone thermostat fan modes are set to Auto, place zone 1 thermostat in the cooling mode and adjust the setpoint above the space temperature until it calls for cooling. Keep in mind that the zone thermostat may have a time delay and that the panel has a 3 minute short cycle time delay before allowing the equipment to come on. Once the cooling cycle is energized, the following panel LEDs should be lit: 24V Y1 G 0/B (If reversing valve = 0 cooling) LIMIT ZD1
TEST, CHECK AND STARTUP:
10. Repeat the same step for zone 2 and zone 3. LED status should be the same
with the exception that ZD2 light for the zone 2 thermostat cooling test and
ZD3 LED will light
for the zone 3 thermostat test. 11. The same test can be done for a heating
call from each zone.
12. Once testing is confirmed, place zone thermostats in their proper mode of
operation.
Enclosure:
Aluminum
Panel Dimensions:
Height: 8.0”
Width: 6.0”
Depth 2.25”
PC Board Mounting:
Individual Snap Track mounted to enclosure base
Operating Temperature Rating:
-40° F to 150° F
Operating Humidity:
5% to 90% RH non-condensing
Wiring:
18-gauge wire for all equipment and component connections.
Time Delays:
3 minutes off between heating and cooling calls.
3 minutes off on high or low limit
20 minute time share
Purge ON = 1 minute
Thermostats:
Single or multi-stage heat pump
Programmable or non-programmable
Auto or manual changeover
FIELD WIRING TERMINALS:
Zone Thermostats:
C 24Vac (Common)
R 24Vac (Hot)
W Auxiliary or Emergency Heat
Y1 First Stage Compressor
Y2 Second Stage Compressor
G Fan
O/B Reversing Valve
HVAC Equipment:
R 24Vac Equipment Hot
W Auxiliary or Emergency Heat
Y1 First Stage Compressor
Y2 Second Stage Compressor
G Fan
O/B Reversing Valve
High / Low Limit
DA Land to ZPA-DTS
DA Land to ZPA-DTS
Outdoor Temperature Sensor
OT Land to ZPA-OTS
OT Land to ZPA-OTS
Panel Power:
C 24Vac (Common)
R 24Vac (Hot)
Damper Outputs
PC Power Close
C Common
PO Power Open
Pressure Sensor:
2 Land to ZPA-SPS
3 Land to ZPA-SPS
SPECIAL ADDENDUM
USING ESP ZONING PANELS WITH GAS FURNACES HAVING DIRECT SPARK IGNITION
(DSI)
DSI functions by creating a rapid series of high-voltage electric sparks,
which means DSI controls generate electromagnetic interference (EMI) during
their trial for ignition. This electronic noise can sometimes interfere with
ESP zoning panels as well as other nearby electronic components and even with
the ignition control itself.
When using an ESP zoning panel with a gas furnace having DSI, we recommend
that the panel be mounted at least ten feet away from the furnace to reduce
any effects of EMI that can cause sporadic cycling of the relay outputs.