Edimax Pro DP-150W54V IGS-1 Industrial Railmount Gigabit Managed Switch Installation Guide

June 13, 2024
Edimax Pro

Edimax Pro DP-150W54V IGS-1 Industrial Railmount Gigabit Managed Switch Installation Guide
Edimax Pro DP-150W54V IGS-1 Industrial Railmount Gigabit Managed
Switch

INTRODUCTION

DP-150W Series DIN-Rail Power Supply can be mounted on TS35/7.5 or TS35/15 standard DIN Rail.
Introductions

INSTALLATION

DIN-Rail Mounting

Please follow below instruction to mount the DIN-Rail Power Supply on the DIN- Rail track.

  1. Insert the unit upper end of the DIN-Rail mounting bracket into the DIN-Rail track from its upper side.

  2. Slide it downward until it hits the stop.

  3. Lightly push the bottom of the DIN-Rail mounting bracket into the track.

  4. Check if the DIN-Rail mounting bracket is tightly attached to the track.

NOTE:

  • Mount the unit on DIN-Rail rack in vertical position to keep the input terminals at the bottom and output on the top. Other positions are not allowed such as desktop, upside down or horizontal mounting.
  • Disconnect AC power before installing wiring.

Wiring AC Power Inputs and DC Output

  1. Maintaining good ventilation clearances for DIN Rail power supply, 10mm left and right, 40mm above and 20mm below, in order to prevent it from overheating.
  2. To dissipate heat, please keep 15 cm away from the adjacent heat source.
  3. The AC input (100-240V) and DC output (48~55V) wire recommended at least 0.8mm²(AWG18) and UL1007 (withstand temperature > 80°C).
    AWG| 18
    ---|---
    Rated Current of Equipment(Amp)| 7A
    Cross-section of Lead (mm²)| 0.8mm²

Recommended wire strapping length: 6.5mm(0.255”)

  1. AC Power Input Wiring: For AC (100~240V) power input wiring, please connect to L (Live line), N (Null Line) and GND (Ground) terminals. Tighten the screws to prevent the wires from loosening.
  2. DC Power Output Wiring: Insert the Negative / Positive DC wires into the PWR terminals (V54-,V54+) respectively. Tighten the screws to prevent the wires from loosening.
  3. “+ V Adj “ DC Output Voltage Regulator can adjust the DC voltage from 48V to 55V
  4. Insert the wires (no electrical polarity) into the “DC OK” terminal block (Fault Alarm Relay). Tighten the screws to prevent the wires from loosening.

Wiring AC Power

LED STATUS

Function Status Description
DC OK On ( Green ) Power on, ready to supply DC 48-55V
Off Power off or malfunction

PRODUCT SPECIFICATION

Model DP-150W series
Output Rated voltage
Rated current 2.8A
Current range 0-2.8A
Rated power 151.2W
Ripple <120mV
Voltage regulation ±1%
Adjustable output voltage range 48-55VDC
Input Voltage range

Frequency range| 47Hz-63Hz
Protection Functions| Short circuit protection| Swing self-recovery
Over current protection| Swing self-recovery
Environment| Working temperature| -25 oC to 70 oC
Operating humidity| 20% – 90%RHnon-condensing
Storage temperature| -40 oC to 85 oC
Store humidity| 10% – 95%RHnon-condensing

Warning Caution!!!

  1. Risk of electrical shock and energy hazard. All failure should be examined by a qualified technician. Please do not remove the case of the power supply by yourself!
  2. Risk of electric arcs and electric shock (danger to life). Connecting both the primary and the secondary sides together is not allowed.
  3. Risk of burn hazard. Do not touch the unit in operation and shortly after disconnection!
  4. Risk of fire and short circuit. The openings should be protected from foreign objects or dripping liquids.
  5. Only install the unit in a pollution degree 2 environment .
  6. Please do not install the unit in places with high moisture or near the water.
  7. Please do not install the unit in places with high ambient temperature or near fire source.
  8. Output current and output wattage must not exceed the rated values on its specification.
  9. Pollution Degree 2 applies where there is only non-conductive pollution that might temporarily become conductive due to occasional condensation. Generally refer to dry, well-ventilated locations, such as control cabinets.

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

Related Manuals