IO HVAC Controls RD-XX Series Retro Damper Instructions

October 30, 2023
iO HVAC Controls

IO HVAC Controls RD-XX Series Retro Damper

RD-XX SERIES RETRO DAMPERTM

The RD-XX Series Retro Dampers are devices that can be used with most zone control panels that have the ability to directly power a 3-wire actuator. Each Retro Damper is rated at 24Vac, 2VA. The zone control system transformer must be sized to handle the total VA of all dampers. In some applications, additional dampers may require a relay and separate transformer.

PRODUCT INSTALLATION AND WIRING INSTRUCTIONS

Follow the steps below to install and wire the RD-XX Series Retro Damper:

  1. Each RD-XX Retro Damper is supplied with a self-adhesive template that is applied to the round section of duct where the damper is to be installed. The template should run parallel to the duct work.
    • Use the template to drill two 1″ holes. Cut out the area between the two holes.
    • Drill four 1/8″ holes in corners to mount the damper to existing duct work.
  2. The damper blade must be parallel to the damper frame. Press in on the gear release tab to manually position the blade.
  3. Slide the damper into the duct and secure it with the four supplied mounting screws.
  4. Attach the three wires to the correct terminals:
    • 1 = Common
    • 2 = Powered Close
    • 3 = Powered Open

Contact iO HVAC Controls at www.iohvaccontrols.com or call toll-free at 866-225-5032 for technical support.

INSTALLATION AND WIRING INSTRUCTIONS

RD-XX Series Retro Dampers can be used with most zone control panels which have the ability to directly power a 3-wire actuator. Each Retro Damper is rated at 24Vac, 2VA. The zone control system transformer must be sized to handle the total VA of all dampers. In some applications, additional dampers may require a relay and separate transformer.

INSTALLATION AND WIRING

  1. Each RD-XX Retro Damper is supplied with a self-adhesive template that is applied to the round section of duct where the damper is to be installed. The template should run parallel to the duct workIO-HVAC-Controls-RD-XX-Series-Retro-Damper-FIG-1 IO-HVAC-Controls-RD-XX-Series-Retro-Damper-FIG-2
  2. Drill two 1” holes and four 1/8” mounting holes as noted on the templateIO-HVAC-Controls-RD-XX-Series-Retro-Damper-FIG-3
  3. Cut out the area between the holes.IO-HVAC-Controls-RD-XX-Series-Retro-Damper-FIG-4
  4. The damper blade must be parallel to the damper frame. Press in on the gear release tab to manually position the blade.
  5. Slide the damper into the duct and secure it with the four supplied mounting screws.
  6. Attach the three wires to the correct terminals.
  7. = Common
  8. = Powered Close
  9. = Powered Open

www.iohvaccontrols.com
For Technical Support Call Toll Free: 866-225-5032

References

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

iO HVAC Controls User Manuals

Related Manuals