KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter User Guide

June 12, 2024
KACO

KACO blue planet 50.0 TL3
KACO blue planet 60.0 TL3

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter

Quick guide
Photovoltaic feed-in inverter KACO blue planet
50.0 + 60.0 TL3

General information

WARNING
Danger due to improper handling of the device!
Read and follow the operating instructions in full.

NOTE
This quick guide will assist you in handling the device. This quick guide does not replace the description in the comprehensive operating instructions under www.kaco-newenergy.com/de/downloads

Safety

The quick guide that is provided is a constituent part of the device.
  Read and observe the quick guide and keep it accessible at all times.

2.1 Proper use
The device is a trans for merless PV inverter which converts the direct current of the PV generator into grid-compatible three-phase alternating current and then feeds the three-phase alternating current into the public power grid.
The device is built using state-of-the-art technology and in accordance with the recognized safety rules. Nevertheless, improper use may cause lethal hazards for the operator or third parties, or may result in damage to the product and other property.
The device is intended for indoor and outdoor applications and may only be used in countries for which it has been approved or for which it has been released by KACO new energy and the grid operator.1 Operate the device only with a permanent connection to the public power grid. The country and grid type selection must be commensurate with the respective location and grid type.
The requirements of the grid operator must be met for grid connection to take place. The permission of the relevant authorities may also be required in order to secure authorisation to connection to the grid.
The name plate must be permanently attached to the product and must be in legible condition.

2.2 Improper use of the product
Any other or additional use is not considered proper or intended use and can lead to an annulment of the product guarantee. This includes:

  • Use of a distribution system that is not described (grid type)
  • Use of sources other than PV-strings.
  • Mobile use
  • Use in rooms where there is a risk of explosion
  • Use in direct sunlight, rain or a storm or other harsh environmental conditions
  • Use in an outdoor area that does not meet the environmental conditions set down in Technical Data/Environmental Data in the comprehensive operating instructions
  • Operation outside the specification intended by the manufacturer
  • Overvoltage on the DC connection of over 1,100 V
  • Device modification
  • Standalone mode

2.3 Warnings on the device
A warning sticker is affixed to the device, see the figure on the title page.

  1. Read the warnings carefully
  2. Do not remove the warning sticker.
  3. If the warning sticker is missing or illegible, contact a KACO representative or dealer.
  • Article number: 3009476

2.4 Personnel qualification
1 WARNING! The blue planet 60.0 TL3 is not intended for use in residential areas and cannot ensure adequate protection of radio reception in such environments.
The operator may only monitor the LEDs, request measurement and status data via the LCD display, carry out visual checks and clean the housing of the device. All other work may only be carried out by a qualified electrician, see the comprehensive operating instructions under www.kaco- newenergy.com/de/downloads

Qualifications that the electrician must have:

  • Education concerning the installation and start-up of electrical units and plants.
  • Training in the handling of hazards and risks during the installation and operation of electrical devices and systems.
  • Knowledge about how an inverter functions and operates
  • Knowledge about IP-based network protocols
  • Knowledge of the Modbus specifications
  • Knowledge of the Sun Spec Modbus specifications
  • Knowledge of applicable standards and directives.
  • Knowledge and adherence to this document with all safety notices.

2.5 Residual risks
Lethal voltages are still present in the connections and cables of the device even after the device has been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.

  • The device must be mounted in a fixed position before being connected electrically.
  • Comply with all safety regulations and current technical connection specifications of the responsible power supply company.
  • The device is only permitted to be opened and serviced by a qualified electrician.
  • Switch off the grid voltage by turning off the external circuit breakers.
  • Check that all AC and DC cables are completely free of current using a clip-on ammeter.
  • Do not touch the cables and/or terminals/busbars when switching the device on and off.
  • Keep the device closed when in operation.

Risk of fatal injury due to contact voltages
XL Version: Removing the plug connections before disconnecting the device from the PV generator may lead to injuries and damage the device.

  • During installation: Electrically disconnect the DC positive and DC negative from the protective earth (PE).
  • Disconnect the device from the PV generator using the integrated DC isolator switch.
  • Using a clip-on ammeter, check that there is no current in any of the DC cables before disconnecting the connectors one after the other.

Dangerous voltage due to two operating voltages
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched. The discharge time of the capacitors is up to 5 minutes.

  • Only appropriately qualified electricians authorised by the mains supply network operator are permitted to open and maintain the device.
  • Observe warnings on the device housing warning label.
  • Before opening the device: Disconnect the AC and DC sides and wait at least 5 minutes.

Risk of burns due to hot housing components!
Housing components can become hot during operation.

  • During operation, only touch the housing cover on the device.

Damage to the device from electrostatic discharge
Components inside the device can be damaged beyond repair by static discharge.

  • Observe the ESD protective measures.
  • Before touching a component, ground it by touching an earthed object.

Property damage as a result of condensation
During pre-assembly of the device, moisture can penetrate into the interior via the dust-protected threaded connections. The resulting condensate can cause damage to the device during installation and start-up.

  • Prior to installation, check the inner area for condensation and if necessary, allow it to dry sufficiently before installation.
  • Store in accordance with the technical data > Environmental data – see Manual http://www.kaco-newenergy.com/de/downloads in the „String-inverter/manual“ category.

2.6 Monitoring and protection functions
The following monitoring and protection functions are integrated in the device:

  • RCMU (Residual Current Monitoring Unit)
  • Overvoltage conductor / varistor to protect the power semiconductors from high-energy transients on the grid and generator sides.
  • Device temperature monitoring system
  • EMC filter to protect the inverter from high-frequency grid interference
  • Grid-side varistors grounded to earth to protect the product against burst and surge pulses
  • Anti-islanding detection according to the current standards.
  • Isolation detection / residual current monitoring and disconnection function to detect isolation faults

NOTE
If the device is connected, the overvoltage conductors / varistors contained in the device have an impact on the electrical system insulation resistance test as per HD 60364-6 / IEC 60364-6 Low-voltage installations Part 6: Verification.
IEC 60364-6 6.4.3.3 describes two options for this case. The first option is to disconnect devices with an overvoltage conductor or, if this is not practicable, then the test voltage can be reduced to 250V.

Assembly and preparation

3.1 Choosing the installation location
DANGER
Risk of fatal injury due to fire or explosions!
Fire caused by flammable or explosive materials in the vicinity of the device can lead to serious injuries.
› Do not mount the inverter in potentially explosive atmospheres or in the vicinity of highly flammable materials.

CAUTION
Property damage due to gases that have an abrasive effect on surfaces when they come into contact with ambient humidity caused by weather conditions.
The device housing can be seriously damaged due to gases in combination with air humidity resulting from weather conditions (e.g. ammonia, sulphur).
› If the device is exposed to gases, the installation must be carried out at observable locations.
› Perform regular visual inspections.
› Immediately remove any moisture from the housing.
› Ensure adequate ventilation at the installation location.
› Immediately remove dirt, especially on vents.
› Failure to observe these warnings may lead to device damage which is not covered by the manufacturer warranty.

NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or installation conditions will be billed to the customer

Installation space

  • As dry as possible, climate-controlled, the waste heat must be dissipated away from the device.
  • Unobstructed air circulation.
  • Close to the ground, accessible from the front and sides without requiring additional resources.
  • Protected on all sides against direct weather exposure and sunlight (thermal heating) in outdoor areas. Implementation where necessary via constructional measures, e.g. wind breaks.
  • For easy operation during installation, ensure that the display is slightly below eye level.

Installation surface

  • Must have adequate load-bearing capacity
  • Must be accessible for installation and maintenance
  • Must be made out of heat-resistant material (up to 90 °C )
  • Must be flame resistant
  • Minimum clearance during installation: See comprehensive operating instructions under www.kaco-newenergy.com/de/downloads

3.2 Tools used

Code (s) Shape of the connector
W External hexagon
A Internal hexagon
T Torx
S Slot

Tab. 1: Key and description of tool codes

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - symbol
4

3.3 Fastening the mount
WARNING
Hazard when using unsuitable fixing materials!
If unsuitable fixing materials are used, the device could fall and persons in front of the device may be seriously injured.
› Use only fixing materials that are suitable for the mounting base. The fastening materials supplied are only to be used for masonry and concrete.
› Only install the device in an upright hanging position.

Installation

4.1 Opening the device

↻ Mount the device to the wall.
↻ Wipe off any moisture on the housing door frame to nullify any potential liability this could cause.
1 Open the housing door by unlocking the upper and lower lock with the double bit key provided.
2 Open the housing door carefully.
» Proceed with the installation of the device.

4.2 Making the electrical connection
NOTE
Select conductor cross-section, safety type and safety value in accordance with the following basic conditions:
Country-specific installation standards; power rating of the device; cable length; type of cable installation; local temperature

Detailed information on tightening torques: See comprehensive operating instructions under http://www.kaco-newenergy.com/de/downloads
4.3 Connecting the device to the power grid
4.3.1 Prepare the grid connection

TN-S-System, TN-C-S-System, TT-System
↻ A connection cable with 5 wires is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.

  1. Unfasten the cable fitting for the AC connection [ W_68].
  2. Remove the outer cladding of the AC cables.
  3. Push an M8 cable lug onto the PE line.
  4. Remove the cover of the AC filter using the 4 screws[ T_15].
  5. Unscrew the screws on the contact bridge and remove the contact bridge[ _T20].
  6. Insert the AC cables through the cable fitting into the connection area.
  7. Strip the AC lines [approx. 25 mm].
    » Make the grid connection.

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - fig
2

1 Cover
2 Screws for contact bridge
3 Contact bridge
4 Earthing bolt

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - fig
3

Key

  1. AC connection terminal
  2. Base AC overvoltage protection
  3. DC isolator switch
  4. DC connection with protection against contact
  5. Base DC overvoltage protection

TN-C system
↻ Connection cable with 4 wires is provided on the device.
↻ Nominal grid voltage matches the VAC nom name plate details.

  1. Unfasten the cable fitting for the AC connection [ W_68].
  2. Remove the outer cladding of the AC cables.
  3. Insert the AC cables through the cable fitting into the connection area.
  4. Strip the AC lines [approx. 25mm].
    » Make the grid connection.

4.3.2 Make the grid connection
5 core connection for TN-S system, TN-C-S system, TT-System

↻ Grid connection is prepared.

  1. Loosen nut and lock washer at the marked grounding point.
  2. Lay the grounding cable onto the grounding point. Secure using the corresponding nut and lock washer [ W_13/ 10 Nm].
  3. Connect wires in accordance with the labels on the screw terminal [ T_45 / 10 Nm].
  4. Check secure fit of all connected cables.
  5. Tighten the cable fittings [ W_68 / 20 Nm].
  6. Secure cover using the 4 screws [ _T15 / 2.3 Nm].

» The device is connected to the power grid.
» NOTE: If there is a 5-core connection, an inserted contact bridge may trigger any RCD that is present. The instructions given above must therefore be carefully followed.

4-core connection, TN-C system
↻ Grid connection is prepared.

  1. Connect lines in accordance with the labels on the name plate on the screw terminal [ T_45/ 10 Nm].
  2. Check secure fit of all connected cables.
  3. Tighten the cable fittings [ W_68 / 20 Nm].
    » The device is connected to the power grid.

NOTE
If an external residual current circuit breaker is necessary due to the installation specification, a type A residual current circuit breaker must be used.
If the type A is used, the insulation threshold must be set to greater than/equal to (≥) 200 k Ohm in the “Parameters” menu [see Menu].
For questions regarding the appropriate type, please contact the installer or our KACO new energy customer service.

Detailed information on grid connection: See comprehensive operating instructions under http://www.kaco-newenergy.com/de/downloads in the “string inverter” category.

4.4 Connect PV generator to device
The DC connection is intended exclusively for PV generators. Other sources fall within the scope of improper operation (e.g. batteries).
↻ DC generators comprehensively checked to ensure there is no ground fault
↻ DC polarity checked before connection made to inverter.

  1. Activate the connection power at the switchbox or string combiner with the DC isolator switch.
  2. Check the DC polarity before making the connection to the inverter.
  3. Only connect DC generators that have been comprehensively checked to ensure there is no ground fault.

4.4.1 Connecting the PV generator
Connecting the DC cable (S, Basic + M version)
↻ PV generator is dimensioned according to the performance characteristics of the unit.

  1. Loosen the cable fittings [ W_36(M32 )].
  2. Remove the outer cladding of the DC cables and insert them through the cable fitting [Ø 15 – 21 (M32) mm ].
  3. Strip the insulation from the DC cables.
  4. Fit DC lines with an ring cable lug [max. width b 20 mm].
  5. Remove the protection against contact from the PV+ and PV- terminal.
  6. Screw the cable ends of the PV generator onto the DC connection according to the polarity of the battery [ T_TX35 / 15-22 Nm ].
  7. Check secure fit of all connected cables.
  8. Remove the protection against contact from the PV+ and PV- terminal.
  9. Tighten the cable fittings [ W_36 / 4 Nm].
    » The device is connected to the PV generator.

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - fig
6

Connecting the DC cable (XL variant)
↻ PV generator is dimensioned according to the performance characteristics of the unit.

  1. Remove protective cap from the DC connection plugs required.
    NOTE: For each plug connector pair, the power output can be connected in relation to the string fuse size used.

  2. Connect the PV generator to the DC plug connectors on the underside of the unit according to the polarity of the PV generator.
    NOTE: Meet the requirements of protection class IP65 by closing the unused plug connectors with protective caps.
    » The device is connected to the PV generator.

4.5 Inserting the overvoltage protection
NOTE
The M and XL versions of the unit series blue planet 50.0 TL3 allow you to upgrade the AC and DC lightning and overvoltage protection in a straightforward and cost-efficient manner.
In this respect, please refer to the documentation “blue planet 50.0-60.0 TL3 Application note – Installing a surge protection device” on our website.

Information on the overvoltage protection: See http://www.kaco- newenergy.com/de/downloads in the “string inverter/manual” category.

4.6 Creating equipotential bonding
NOTE
Depending on the local installation specifications, it may be necessary to earth the device with a second ground connection. To this end, the threaded bolt on the underside of the device can be used.

↻ The device has been installed on the mount.

  1. Strip the insulation from the equipotential bonding cable.
  2. Furnish the stripped cable with an M8 ring cable lug.
  3. Lay the cable for equipotential bonding onto the grounding point and attach with an additional M8 nut and lock washer [ W_17/ 10 Nm].
  4. Check that the connected cable is fitted securely.
    » The housing is included in the equipotential bonding.

4.7 Connecting the interfaces
4.7.1 Overview
DANGER
Risk of fatal injury due to electric shock!
Severe injury or death may result from improper use of the interface connections and failure to observe protection class III.
› The SELV circuits (SELV: safety extra low voltage) can only be connected to other SELV circuits with protection class III.

All interfaces are located on the communication circuit board on the inside of the housing door.

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - fig
9

1 Communication circuit board
2 ERR – Connection for fault signal relay
3 USB – Connection for update
4 Ethernet – Connection for communication
5 RS485 – Connection for data loggers
6 DIP switch – Activate terminator
7 INV OFF – Connection for remote controls
8 Optional connection of extension module

4.7.2 Insert and lay the cables
Shielding the Ethernet and RS485 cable

  1. Open and close the door completely to check that the cables (1) are not subject to tensile or compressive forces.
  2. Mark the position for connecting the shield on the clamping ring (2) of the EMC screw fitting.
  3. Pull out the cables and strip them down to the mesh wire to the marked position (approx. 10 mm).
  4. Pull the cables back to the shielding point until full shielding is provided by the clamping ring and the connecting cable cannot be displaced. [See figure 14] [} Page 10]

4.7.3 Ethernet connection
NOTE
The connection plug of an RJ45 cable is larger than the opening of an M25 cable fitting when it is installed.
For this reason, remove the sealing insert before installation and thread the Ethernet cable outside of the cable fitting through the sealing insert.
NOTE
Use a suitable category 5 network cable. The maximum length of a network segment is 100 m. Ensure that the cable is correctly assigned. The Ethernet connection of the device supports auto-sensing. You can use both crossed and 1:1 protectively-wired Ethernet connection cables.

↻ Connecting cable inside the device.

  1. Plug in an Ethernet cable at one of the two Ethernet ports on the communication circuit board.
  2. Lay the Ethernet cable correctly in the lower AC supply area and loosely fasten it using the cable ties provided.
  3. Tighten the cable fittings [[ W_29 / 4 Nm].

4.8 Sealing the connection area

  1. The requirements of protection class IP65 are met by closing the unused cable fittings with blind caps.
  2. Close the housing door and lock it with a control cabinet key.
    » The device has been mounted and installed.

Configuration and operation

KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - symbol
7

Operating status LED Icon Display Description
Start The green “Operation” LED is on when the AC voltage is present,

independent of the DC voltage.
Feed-in start| | Power fed into the grid or measured values| The green “Operat ing” LED is lit.
The green “Feed-in” LED is lit after the country-specific waiting period*.
Ready for grid operation.
The interface switch engages audibly.
Feed-in operation| | Power fed into the grid or measured values| The green “Operating” LED is lit. The green “Feed-in” LED is lit.
The “Feed-in” icon appears on the LD display.
The device feeds into the grid.
It Feed-in mode with reduced power| | Power fed into the grid or measured values| The green “Operating” LED is lit.
The green LED “Feed” is flashing because one of the modes: internal power reduction, external power reduction, idle power request or standalone mode is active.
The device feeds into the grid.
The interface switch engages audibly.
Non grid feed mode| | Status message| The display shows the corresponding message.
Error| | Fault message| The display shows the corresponding error message.
The red “Fault” LED is lit.

Accessories

6.1 Inverter off
When using suitable KACO inverters, the shutdown can be carried out via the grid separation relay integrated into the inverters and the “Inverter OFF” digital output instead of via interface switch.
Information about the “Inverter off” function: See manual under www.kaco- newenergy.com/de/downloads in the “string inverter” category.

Maintenance and troubleshooting

Repairs may only be carried out by the authorised electrician.

7.1 Visual inspection by the operator

  1. Inspect the product and cables for visible external damage and note the operating status display, where applicable.
  2. Notify the installer if there is any damage.

Cleaning

8.1 By operator
CAUTION
Risk of damage to the device during cleaning!
› Do not use compressed air or high-pressure cleaners.
› Use a vacuum cleaner or a soft brush to remove dust from the fan cover and from the top of the device on a regular basis.
› Remove dust from the ventilation inlets if necessary.

Clean the housing.
8.2 By authorised electrician
WARNING
Risk of injury from starting fans!
If the device is not completely disconnected from the voltage source, the fan may start up unexpectedly and sever or injure limbs.
› Make sure that the device is disconnected from all voltage sources before starting work on the device.
› After disconnecting from all voltage sources, wait at least 5 minutes before starting maintenance activities.

The maintenance activities listed may only be performed by qualified specialist personnel. For further information on this and the maintenance tasks listed:
See manual under http://www.kaco-newenergy.com/de/downloads in the “string inverter” category.

Decommissioning, disassembly and disposal

CAUTION
Risk to the environment if disposal is not carried out in the correct manner
For the most part, both the device and the corresponding transport packaging are made from recyclable raw materials.
Unit: Do not dispose of faulty devices or accessories together with household waste. Ensure that the old devices and any accessories are disposed of in a proper manner.
Packaging: Ensure that the transport packaging is disposed of properly.

Further information: See manual http://www.kaco-newenergy.com/de/downloads in the “string inverter” category.

Technical data

10.1 Electrical data

blueplanet| 50.0 TL3 – 5 50.0 TB – 50.0 TB – 50.0 TL3 – 50.0 TL3 – 50.0 TL3 – 50.0 TL3 – Basic M M – HU XL – HU XL XL – FR
---|---
DC Input levels| Input levels (DC)
Maximum recommended PV gen-orator power| 100 kW
MPPrange@Pnom| 610 V [@240/415V];
580 V [@230/400V];
560 V [@220/380V]-900 V
Working range| 610 V [@240/415V];
580 V [@230/400V];
560 V [@220/380V]-1050 V
Rated voltage| 600 V
Starting voltage| 670 V
Open circuit voltage| 1,100 V
Max. input current 4| 90 A
Number of strings| 1| 10
‘Number of MPP controls| 1
.Max. short-circuit current (ISC max.)| 190 A
‘Input source feedback current| 0 A
Polarity safeguard| no
DC overvoltage protection| no| optional (type 1+2)| type 1+2
String fuse| no| yes
DC+ fuse holder| no| yes
DC- fuse holder| I no| retrofitted
Blueplanet| 60.0Tl3-Basic
60.0Tl3-M
60.0Tl3-XL
60.0Tl3-XL-FR
---|---
DC Input levels| Input levels (DC)
Maximum recommended PV generator power| 100 kW
MPPrange@Pnom| 610 V [@240/415V];
580 V [@230/400V];
560 V [@220/380V]-900 V
Working range| 610 V [@240/415V];
580 V [@230/400V];
560 V [@220/380V]-1050 V
Rated voltage| 600 V
Starting voltage| 670 V
Open circuit voltage| 1,100 V
Max. input current’| 107 A

4 The “Max. input current” is the maximal theoretical value for operation with full power when the feed-in power is low. The device is limited to the maximum AC power. The “Max. short-circuit current (ISC max)” defines together with open circuit voltage (UD Coax) the characteristic of the connected PV generator. This is the relevant value for string sizing and is the absolute maximal limit for in-verger protection. The connected PV-Generator must be designed, that the max short circuit current is below or equal to the ISC max of the inverter under all foreseeable conditions and therefore complies with IEC 61730 Class A. In no condition the design may result in a greater short circuit current than IS Coax of the inverter [See section 7.6.5 Page 301.

blueplanet 60.0113 – Basic 60.0 TL3 – M 60.0 113 – XL 60.0 TL3 – XL – FR
Number of strings 1
Number of MPP controls 1
Max. short-circuit current (ISC max.) 190 A
Input source feedback current 0A
Polarity safeguard no
DC overvoltage protection no
String fuse no
DC+ fuse holder no
DC- fuse holder no
blueline OD TO – 5T0:0 TL3 – 50:0 n3 – 50.071:3 – 502TO – SO.

Basic M M – HU XL – HU XL XL-FR
---|---
AC Output levels| Output levels (AC)
Nominal power| 50.0 kVA [@220V]; 50.0 kVA [@230V]; 50.0 kVA [@240V]| 49.9 kVA [@220V];
49.9 kVA [@230V];
49.9 kVA [@240V]| 50.0 kVA [@220V]; 50.0 kVA [@230V]; 50.0 kVA [@240V]
Rated voltage| 240 / 415 V [3/N/PE];
230 / 400 V [3/N/PE];
220 / 380 V 13/N/PE]
Voltage range: continuous opera- tion| 176 V – 276 V [Ph-N];
305 V – 480 V [Ph-Ph]
Rated current| 3x 69.6 A [@415V];
3x 72.2 A [@400V];
3x 76.0 A [@380V]
Max. continuous current| 3 x 76.5 A
Contribution to peak short-circuit current ip| 136.11 A
Initial short-circuit alternating current (lk” first single period effect- ive value)| 77.93 A
Short circuit current continuous Ems] (max output fault current)| 96.7 A
Inrush current| 1.21 A [RMS (20ms)]
Rated frequency| 50/60 Hz
Frequency range| 42 – 68 Hz
Reactive power| 0-100 % Snow
cos phi| 0.3 – 1 and/cap
Number of feed-in phases| 3
Distortion factor (THD)| < 1,6 %
Max. voltage range (up to 100 s)| 520V [Ph-Ph]
AC overvoltage protection| no| retrofitted| Base
blueline| 60.0 TL3 -Basic  –  60.0 TL3 – M – 60.0 TL3 – XL- 60.0 TL3 – XL-FR
---|---
Output levels (AC)
AC Output levels
Nominal power| 60.0 kVA [@220V];
60.0 kVA [@230V];
60.0 kVA [@240V]
Rated voltage| 240 / 415 V [3/N/PE];
230 / 400 V [3/N/PE];
220 / 380 V [3/N/PE]
blueline| 60.0 TL3 -Basic  –  60.0 TL3 – M – 60.0 TL3 – XL- 60.0 TL3 – XL-FR
---|---
Voltage range: continuous operation| 305 V – 480 V [Ph-Ph]
Rated current| 3x 86.7 A [@400V]
Max. continuous current| 3 x 90 A
Contribution to peak short-cir-cuit current| 147 A
Initial short-circuit alternating current (lk” first single period effective value)| 97.2 A
Short circuit current continuous [ms] (max output fault cur- rent)| 95.8 A
Inrush current| 5.66 A [RMS (20 ms)]
Rated frequency| 50/60 Hz
Frequency range| 42 – 68 Hz
Reactive power| 0-100 % Snow
cos phi| 0.3 – 0.3 ind/cap
Number of feed-in phases| 3
Distortion factor (THD)| < 1,6 %
Max. voltage range (up to 100 s)| 520V [Ph-Ph]
AC overvoltage protection| no| Base

10.2 General Data

blueline| 50.0 TL3 – S 50.0 TB – 50.0 TB – 50.0 TL3 – 50.0 TB – 50.0113 – 50.0 TL3 -Bask M M – HU XL – HU XL XL – FR
---|---
General electrical data
Max. efficiency| 99.%
European efficiency| 98.%
Self consumption: Standby| 2.5 W
Feed-in from| 120 W
“Inverter Off” signal trip-off time| 20 ms
Transformer unit| no
Protection class / over voltage category| I / III (AC) II (DC)
Grid monitoring| Country-specific
Distribution system| TN-C-System, TN-C-S-System, TN-S-System, TT-System
blueline| 50.0 TB – S 50.0 TB – 50.0 TB – 50.0 TB – 50.0 TB – 50.0 TB – 50.0 TB -Basic M M – HU XL – HU XL XL – FR
General Data
Number of fans| 2
Interfaces| 2 x Ethernet, USB, RS485, 4 optional digital inputs/outputs, error relay (30V potential free contact); 4-DI
Controls| 4-way button + 2 buttons
Noise emission| 61 db(A)
Weight| 70 kg| 71 kg| 73 kg
HxWxD| 760 mm x 500 mm x 425 mm
Housing material| Alu
Menu languages| DE; EN; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
4blueplanet| 50.0 TL3 – S 50.0 TB – 50.0 TB – 50.0 TL3 – 50.0 TB – 50.0 TB – 50.0 TL3 – Basic M M – HU XL- HU XL XL – FR
---|---
Display| Graphical display 240 x 128 pixels + LEDs
DC isolator switch| no I yes
Potential-free relay| yes
AC isolator switch| no
Communication| TCP/IP, Modbus TCP, Sun spec
Cooling| temp. controlled fan
Safety| EN 62109-1, EN 62109-2
Interference immunity/interference emission/grid feedback| EN 61000-6-1 / EN61000-6-2, /
EN 55011 – group 1 Class B /
EN 61000-3-11, EN 61000-3-12
“‘Certifications| Overview: see homepage / download area
frueplanet| 60.0 TL3 -Basic  –  60.0 TL3 – M – 60.0 TL3 – XL- 60.0 TL3 – XL-FR
---|---
General electrical data
Max. efficiency| 99.%
European efficiency| 97.6 %
Self consumption: Standby| 2.5 W
Feed-in from| 120 W
“Inverter Off” signal trip-off time| 20 ms
Transformer unit| no
Protection class / over voltage category| I / Ill (AC) II (DC)
Grid monitoring| Country-specific
Distribution system or| TN-C-System, TN-C-S-System, TN-S-System, -7-System
blueline| 60.0 TL3 -Basic  –  60.0 TL3 – M – 60.0 TL3 – XL- 60.0 TL3 – XL-FR
---|---
General Data
Number of fans| 2
Interfaces| 2 x Ethernet, USB, RS485, 4 optional digital inputs/outputs, error relay (30V potential
free contact); 4-DI
Controls| 4-way button + 2 buttons
Noise emission| 61 db(A)
Weight| 70 – 73 kg
HxWxD| 760 mm x 500 mm x 425 mm
Housing material| Alu
Menu languages| DE; EN; FR; IT; ES; PL; NL; PT; CZ; HU; SL; TR; RO
Display| Graphical display 240 x 128 pixels + LEDs
DC isolator switch| yes
Potential-free relay| yes
AC isolator switch| no
Communication| TCP/IP, Modbus TCP, Sun spec
Cooling| temp. controlled fan
Safety| EN 62109-1, EN 62109-2
Interference immunity/inter- refence emission/grid feed- back| EN 61000-6-1, EN 610000-6-2, EN 6290 Class A /
EN 55011 – group 1 Class A, EN 61000-6-4 /
EN 61000-3-11, EN 61000-3-12
blueplanet| 60.0 TL3 – Basic 60.0 TL3 – M 60.0 TL3 – XL 60.0 TL3 – XL – FR
---|---
Certifications| Overview: see homepage / download area

10.3 Environmental data

blueplanet 60.0 TL3 – Basic 60.0 TL3 – M 60.0 TL3 – XL 60.0 TL3 – XL – FR
,Installation height I 3000m (derating from 2000m)
Installation distance from coast >2000 m OD+ >500 m*)
,Ambient temperature -20 °C to +60 °C
Ambient temperature (storage) -20 °C to +60 °C
Power derating from 40 °C
Protection rating (KACO installation location) IP65
Humidity range (non-condense-ing) [%] 100%
Pollution level inside the en-closure 2
Pollution level outside the en-closure 3
Item number 1001981
Name on nameplate KACO blueline

60.0 TL3 M1 WM OD
GB| KACO blueline
60.0 TL3 M1 WM OD
GM| KACO blueplanet
60.0 TL3 M1 WM OD
GX| KACO blueplanet
60.0 TL3 M1 WM OD
FRGX
blueplanet| 50.0 TL3 – S 50.0 TL3 – 50.0 TL3 – 50.0 TL3 – 50.0 TL3 – 50.0 TL3 – 50.0 TL3 -M – HU XL- HU XL XL-FR
---|---
Installation height| 3000m (derating from 2000m)
Installation distance from coast| >2,000m 1 >2000 m OD+ >500 m*)
Ambient temperature| -20 °C to +60 °C
Ambient temperature (storage)| -20 °C to +60 °C
Power derating from| +50 °C
Protection rating (KACO installation location)| IP65
Humidity range (non-condensing) rol| 100%
Pollution level inside the enclosure| 2
Pollution level outside the enclosure| 3
Item number| 1001722;
1001751| 1001450;
1001653; 1001730; 1001832; 1001840; 1001850| 1001336; 1001582; 1001613; 1001851| 1001780| 1001781| 1001430;
1001672;
1001852| 1001555;
1001581
Name on nameplate| KACO blue-
planet 50.0
TL3 M1
WM OD
IIGS| KACO blue-
planet 50.0
TL3 M1
WM OD
IIGB| KACO blue-
planet 50.0
TL3 M1
WM OD
MGM| KACO blue-
planet 50.0
TL3 M1
WM OD
HUGM| KACO blue-
planet 50.0
TL3 M1
WM OD
HUGX| KACO blue-
planet 50.0
TL3 M1
WM OD
IIGX| KACO blue-
planet 50.0
TL3 M1
WM OD
FRGX

*) For installation in aggressive environmental conditions (e.g. possibility of corrosion) you must contact the KACO Sales team  (pv-projects.kaco.de@siemens.com)
10.4 Accessories

Accessories KACO order no.
String fuses (Fuse-PV 14x51MM 1100V 15A) (10pc) 3009902
String fuses (Fuse-PV 14x51MM 1100V, 15A) (12pc) 3012698
‘String fuses (Fuse-PV 14x51MM 1100V 20A) 3013905
PID Accessory Kit (Warning la-bel) NOTE: Warning label is mandatory when

using a PID solution (for PID regen-eration).
Contact our sales team immediately via sales@kaco-newenergy.de. You will receive the warning sticker for each connected inverter free of charge.

10.5 Fastening the mount
KACO blueplanet 50.0 TL3 Photovoltaic Feed-In Inverter - fig
11

Key

1 Mount| 5 Screw for securing purposes (lx)
2 Fixings for mounting [S12 — 0 12mm/ 90mm]| 6 Bracket to prevent device displacement
3 Lock washer| 7 Marking as installation aid
4 Screws for mounting (5x) [SW 13]| 8 Seating recess
A Minimum clearance: 120 mm (without device 370 mm ) recommended distance: 400 mm (without device 550 mm )| C Minimum clearance: 500 mm
B Minimum clearance: 300 mm| D Recommended clearance: 550 mm
DC- side| S variant| M variant| B variant| X variant| FR-X
---|---|---|---|---|---
Max. conductor cross- section| 95 mm2 (max. 120
mm21| 95 mm2 (max. 120
mm2)| 95 mm2 (max. 120 mm2)| –| –
Min. cable cross-sec-tions| in accordance with local installation standards
Length of insulation
to be stripped off| Depending on the cable lug| 15 mm
Tightening torque| 15-22 Nm| – Nm – Nm
Recommended cable type| Solar cable|
Fuse size (electrical
data)| –| 1100V gave max. 20A
Fuse size (mechanical
data)| mm| 14 x 51 mm
Combiner box| External with DC isolator switch preferable| Integrated DC isolator switch
Cable diameter for
cable fitting| 15 – 21(M32) mm| 1.8 – 2.75 (2mm2 – 6mm2) mm
Fitting for DC connect-tions| M32| SW15
Torque for cable fit-ting| 4 Nm| 1.8 Nm
AC-side|
---|---
Max. conductor cross-section| 95 mm2
Max. cable cross-section (without wire sleeves)| 95 mm2 (AL or CU)
Min. cable cross-section| in accordance with local installation standards
Length of insulation to be stripped off| 25 mm
Tightening torque| 10 Nm
Connection type| Screw terminal
Ground conductor connection| M8
Fuse protection for installation provided by customer| min. 100 A / max.125 A
Fitting for AC connection| M63
Cable diameter for cable fitting| 32 – 42 mm
Torque for cable fitting| 20 Nm
Interfaces**|
Cable diameter for cable fitting| 11- 17 (M25) 5 – 9.5 (M16) mm
RS485 connection type| Connector
RS485 terminal cable cross-section| 0.25 – 1.5 mm2
Ethernet connection type| 8145
Torque for cable fitting| 4 (M25) 1.5 (M16) Nm

Legal provisions
The information contained in this document is the property of KACO new energy GmbH.
Publication, in whole or in part, requires the written permission of KACO new energy GmbH.
KACO warranty
For current warranty conditions contact your system integrator. http://www .kaco-newenergy.com
Definitions on product designations
In these quickguide, the product “Photovoltaic feed-in inverter” is referred to as “device” for ease of reading.
Service and warranty
If you need help solving a technical problem with one of our KACO products, please contact our service hotline.
Please have the following information ready so that we can help you quickly and efficiently:

  • Device name / serial number
  • Date of installation / Start-up report
  • Fault message shown on the display / Description of the fault / Did you notice anything unusual? / What has already been done to analyses the fault?
  • Module type and string circuit
  • Consignment identification / Delivery address / Contact person (with telephone number)
  • Information about the accessibility of the installation site.

You can find the following items and other information at our web site Kaco- newenergy:

  • our current warranty conditions,
  • a complaint form,
  • a form for registering your device. Please register your device without delay. In this manner, you can assist us in providing you with the quickest service possible.

Werner-von-Siemens-Allee 1
74172 Neckarsulm
Germany
Tel. +49 7132 896-1000
info@kaco-newenergy.de 
www.kaco-newenergy.de
The text and figures reflect the current technical state at the time of printing.
Subject to technical changes.
No liability for printing errors.

http://kaco-newenergy.com/downloads/KACO blueplanet 50.0 TL3 Photovoltaic
Feed-In Inverter - bar code

Read User Manual Online (PDF format)

Read User Manual Online (PDF format)  >>

Download This Manual (PDF format)

Download this manual  >>

Related Manuals