S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature Measuring Instruction Manual

June 12, 2024
S S REGELTECHNIK

THERMASGARD ® **ALTM 1
THERMASGARD® ALTM 2
THERMASGARD ALTM1 Surface Contact Tube Contact Temperature Measuring
Instruction Manual**

THERMASGARD ALTM1 Surface Contact Tube Contact Temperature Measuring

Operating Instructions, Mounting & Installation
Surface contact ⁄ tube contact temperature measuring transducers, including strap, calibratable, with multi-range switching and active output

ALTM 2
with remote sensor| ALTM 2 – Q
with M12 connector| ALTM 1
---|---|---
S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring| S
S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring 1| S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring 2

Dimensional drawing

S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring - Dimensional drawing| S S
REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring - Dimensional drawing 1
---|---

High-performance encapsulation against vibration, mechanical stress and humidity

PERFECT SENSOR PROTECTION

Calibratable surface-contact temperature measuring transducer THERMASGARD ® ALTM 1 (compact variant) and ALTM 2 (detached variant) with eight switchable measuring ranges, continuous output, in an impact-resistant plastic housing with quick-locking screws, optionally with ⁄ without display, cable sensor with a pipe feeder (ALTM 2), incl. strap.
The surface-contact sensor is used to detect the temperature on lines, pipes (e.g., cold and warm water) or on heating sections for heating control. The sensor is factory-calibrated; an environmental precision adjustment by an expert is possible.

TECHNICAL DATA

Power supply:| 24 V AC ⁄ DC (± 10 %) for U variant 15…36 V DC for I variant, depending on working resistance, residual ripple stabilized ± 0.3 V
---|---
Working resistance:| Ra (ohm)   =   (Ub -14 V)  ⁄  0.02 A  for I variant, see working resistance diagram
Load resistance:| RL > 5 kOhm for U variant
Power consumption:| < 1.0 VA  ⁄  24 V DC;  < 2.2 VA  ⁄  24 V AC
Insulating resistance:| ≥ 100 MΩ, at +20 °C (500 V DC)
Sensor:| Pt1000, DIN EN 60751, class B  Perfect Sensor Protection at IP68) sensor external
Measuring ranges:| multi-range switching with 8 switchable measuring ranges, see table  (other ranges optional) with manual zero point correction  (± 10 K)
ALTM 1: compact variant,
T max up to +100 °C, operating range  –50…+100 °C
ALTM 2: detached sensor variant,
T max over +100 °C, operating range  –50…+150 °C
Deviation, temperature:| typically ± 0.2 K at +25 °C
Output:| 0  – 10 V  or  4…20 mA
Connection type:| 2- or 3-wire connection
Cable connection:| cable gland, plastic (M 16 x 1.5; with strain relief, exchangeable, max. inner diameter 10.4 mm) or
M12 connector (male, 5-pin, A-code) according to DIN EN 61076-2-101
Housing:| plastic, UV-resistant, material polyamide, 30 % glass-globe reinforced, with quick-locking screws (slotted ⁄ Phillips head combination), colour traffic white (similar to RAL 9016),, housing cover for display is transparent!
Housing dimensions:| 72  x  64  x  37.8 mm  (Tyr 1 without display)
72  x  64  x  43.3 mm  (Tyr 1 with display)
Sensor cable: :| ALTM 2:   Silicone, SiHF, 2 x 0,25 mm²; cable length (KL)  = 1.5m (other lengths and jacket materials, e.g. PTFE or glass fibre with steel mesh, available on request)
Sensor protection:| ALTM 2: pipe feeder made of stainless steel V4A (1.4571), Ø = 6 mm, L = 50 mm
Electrical connection:| 0.14 – 1.5 mm²  via terminal screws
Process connection:| endless strap with metal tightener (included in the scope of delivery) Ø = 13 – 92 mm (¼ – 3″), L = 300 mm
Ambient temperature:| measuring transducer –30…+70 °C
Humidity:| < 95 % r. H., non-precipitating air
Protection class:| III  (according to EN 60 730)
Protection type housing:| IP 65    (according to EN 60 529) Housing tested,
TÜV SÜD, Report No.713139052 (Tyr 1)
Protection type sensor:| ALTM 2:
IP 65 (according to EN 60 529)
sleeve humidity-tight (standard)
IP 68   (according to EN 60 529)
sleeve water-tight (optional)
Standards:| CE conformity, electromagnetic compatibility according to EN 61326, according to EMC directive 2014 ⁄ 30 ⁄ EU
Optional:| Two-line display with illumination, cutout approx. 36 x15 mm (W x H), for displaying the ACTUAL temperature and the internal diagnostics (measuring range exceeded, measuring range not reached, sensor breakage, sensor short circuit)

Display and internal diagnostics

| Standard
---|---
| Measuring range exceeded
| Measuring range not reached
| Sensor breakage
| Sensor short circuit

THERMASGARD ® ALTM 2 ⁄ ALTM 2 – Q Surface contact ⁄ tube contact temperature measuring transducers

Type ⁄ WG01| Sensor| Output| Type| Display = Q| Item No.
---|---|---|---|---|---
A LT M 2 – I| Pt1000| 4…20 mA| Remote sensor|  | 1101-1122-0219-920
A LT M 2 – I LCD| Pt1000| 4…20 mA| Remote sensor| ■| 1101-1122-2219-920
A LT M 2 – U| Pt1000| 0 -10 V| Remote sensor|  | 1101-1121-0219-920
A LT M 2 – U LCD| Pt1000| 0 -10 V| Remote sensor| ■| 1101-1121-2219-920
ALTM 2 – Q| (with M12 connector)
A LT M 2 – I Q| Pt1000| 4…20 mA| Remote sensor| | 2001-2121-2100-001
A LT M 2 – I Q LCD| Pt1000| 4…20 mA| Remote sensor| ■| 2001-2122-2100-001
A LT M 2 – U Q| Pt1000| 0 -10 V| Remote sensor| | 2001-2121-1100-001
A LT M 2 – U Q LCD| Pt1000| 0 -10 V| Remote sensor| ■| 2001-2122-1100-001
Housing variant “Q”:| Cable connection with M12 connector (male, 5-pin, A-code)
Extra charge:| Other ranges optional, Protection type IP 68 (Sensor sleeve watertight compound-filled)
2-wire connecting leads, per running meter (silicone / PTFE / glass fibre)| on request
ACCESSORIES
WLP-1| Heat-conductive paste, silicone-free| 7100-0060-1000-000

Measuring transducers, calibratable, with active output

TEMPERATURE RANGES: When selecting measuring transducer ranges, it is necessary to ensure that the maximum temperatures permissible for sensor ⁄ enclosure are not exceeded !
Ambient temperature for measuring transducers: – 30 …+ 70 °C, Apparent ohmic resistance = see load resistance diagram

S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring - diagram

SUPPLY VOLTAGE :
For operating voltage reverse polarity protection, a one-way rectifier or reverse polarity protection diode is integrated in this device variant. This internal one-way rectifier also allows operating 0 – 10 V devices on AC supply voltage.
The output signal is to be tapped by a measuring instrument. Output voltage is measured her against zero potential (O V) of the input voltage! When this device is operated on DC supply voltage, the operating voltage input UB+ is to be used for 15…36 V DC supply and UB – or GND for ground wire!

S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring - SUPPLY VOLTAGE

When several devices are supplied by one 24 V AC voltage supply, it is to be ensured that all ”positive“ operating voltage input terminals (+) of the field devices are connected with each other and all ”negative“ operating voltage input terminals (–) (= reference potential) are connected together (in-phase connection of field devices). All outputs of field devices must be referenced to the same potential!
In case of reversed polarity at one field device, a supply voltage short- circuit would be caused by that device. The consequential short-circuit current flowing through this field device may cause damage to it.
Therefore, pay attention to correct wiring!

THERM ASGARD ® **ALTM 1** Surface contact ⁄ tube contact temperature measuring transducers (compact)

Type ⁄ WG01| Sensor| Output| Type| Display| Item No.
A LT M 1- I| Pt1000| 4…20 mA| Compact|  | 1101-1112-0219-920
A LT M 1- I LCD| Pt1000| 4…20 mA| Compact| ■| 1101-1112-2219-920
A LT M 1- U| Pt1000| 0 -10 V| Compact|  | 1101-1111-0219-920
A LT M 1- U LCD| Pt1000| 0 -10 V| Compact| ■| 1101-1111-2219-920
Extra charge:| Other ranges optional
Cable connection with M12 connector according to DIN EN 61076-2-101| on request

Installation and Commissioning

Devices are to be connected under dead-voltage condition. Devices must only be connected to safety extra-low voltage. Consequential damages caused by a fault in this device are excluded from warranty or liability. These devices must be installed and commissioned by authorised specialists. The technical data and connecting conditions shown on the device labels and in the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our pro ducts. In case of any modifications made by the user, all warranty claims are forfeited. Operating this device close to other devices that do not comply with EMC directives may influence functionality. This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
Modifications of these records are not permitted.
In case of a complaint, only complete devices returned in original packing will be accepted.
Notes on commissioning:
This device was calibrated, adjusted and tested under standardised conditions. When operating under deviating conditions, we recommend performing an initial manual adjustment on-site during commissioning and subsequently at regular intervals.
Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations and standards applicable for the place of measurement (e.g. such as welding instructions, etc.). Particularly the following shall be regarded:

  • VDE ⁄ VDI directive technical temperature measurements, measurement set – up for temperature measurements.
  • The EMC directives must be adhered to.
  • It is imperative to avoid parallel laying of current-carrying lines.
  • We recommend to use shielded cables with the shielding being attached at one side to the DDC ⁄ PLC.

Before mounting, make sure that the existing thermometer‘s technical parameters comply with the actual conditions at the place of utilization, in particular in respect of:

  • Measuring range
  • Permissible maximum pressure, flow velocity
  • Oscillations, vibrations, shocks are to be avoided (< 0.5 g)

CONNECTING CONDITIONS
Output: 0 – 10 V
The output voltage follows linear to the temperature signal applied at the input terminals and generates a proportional output signal of 0 – 10 V. The voltage outputs are short-circuit proof against ground wire. Applying voltage supply to the output terminals will destroy the device.
Output: 4 … 20 mA
In case of the 4 … 20 mA measuring transducer, display and evaluating elements are connected in series in the current loop. The measuring transducer thereby liWiths the flowing current in variance of the input signal. 4 mA are for the measuring transducer‘s internal current consumption. The apparent ohmic resistance can either be connected in the plus or minus path of the measuring transducer. In case of an apparent ohmic resistance in the plus path, power supply and resist.
SAFETY REGULATIONS
These devices shall only be used for their intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The buyer has to ensure adherence to the building and safety regulations and has to avoid all dangers of any kind. We do not assume any warranty for faults or damages arising or resulting from improper use of our equipment or from non-observance of operating instructions. These instruments
must be installed by authorised specialists only!
Preferably shielded cables should be used in order to prevent damages ⁄errors. It is imperative to avoid laying parallel with current- carrying lines. EMC directives must be adhered to.

General notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.
In addition In addition, the following points are to be observed:

  • These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!
  • Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device (e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to be observed.
  • This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their control authorities, the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to prevent perils of any kind.
  • No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
  • Consequential damages caused by a fault in this device are excluded from warranty or liability.
  • These devices must be installed and commissioned by authorised specialists.
  • The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous improvement of our products.
  • In case of any modifications made by the user, all warranty claims are forfeited.
  • This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.
  • Operating this device close to other devices that do not comply with EMC directives may influence functionality.
  • This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury, or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.
  • Dimensions of housing or housing accessories may show slight tolerances on the specifications provided in these instructions.
  • Modifications of these records are not permitted.
  • In case of a complaint, only complete devices returned in original packing will be accepted.

Commissioning is mandatory and may only be performed by qualified personnel!
These instructions must be read before installation and commissioning and all notes provided therein are to be regarded!

ALTM 2 – U
Pin assignment

ALTM 2 – I
Pin assignment

  1. +UB 24 V AC/DC
  2. Output temperature 0 -10 V [°C]
  3. free
  4. –UB GND
  5. Shield

© Copyright by S+S Regeltechnik GmbH
Reprint in full or in parts requires permission from S+S Regeltechnik GmbH.
Subject to errors and technical changes. All statements and data herein represent our best knowledge at date of publication. They are only meant to inform about our products and their application potential, but do not imply any warranty as to certain product characteristics. Since the devices are used under a wide range of different conditions and loads beyond our control, their particular suitability must be verified by each customer and/or end user themselves. Existing property rights must be observed. We warrant the faultless quality of our products as stated in our General Terms and Conditions.
Connecting diagram
S S REGELTECHNIK THERMASGARD ALTM1 Surface Contact Tube Contact Temperature
Measuring - Connecting diagram

Measuring ranges (adjustable)| DIP 1| DIP 2| DIP 3
---|---|---|---
– 20 °C … + 150 °C| O N| O N| O N
– 50 °C … + 50 °C| OFF| O N| O N
– 20 °C … + 80 °C| O N| OFF| O N
– 30 °C … + 60 °C| OFF| OFF| O N
0 °C …  + 40 °C| O N| O N| OFF
0 °C+ 50 °C (default)| OFF| O N| OFF
0 °C … + 100 °C| O N| OFF| OFF
0 °C … + 150 °C| OFF| OFF| OFF

*Connection:
2-wire connection for devices with ⁄ without display (not illuminated)
3-wire connection for devices with illuminated display
(observe max. permissible temperature ranges!)**

S+S REGELTECHNIK GMBH