MEAN WELL EDR-75-12 75W Single Output Industrial DIN RAIL Instruction Manual
- June 12, 2024
- MEAN WELL
Table of Contents
MEAN WELL EDR-75-12 75W Single Output Industrial DIN RAIL Instruction
Manual
Features
- Universal AC input / Full range
- Protections: Short circuit / Overload / Over voltage / Over temperature
- Cooling by free air convection
- Can be installed on DIN rail TS-35/7.5 or 15
- UL 508 (industrial control equipment) approved
- BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
- 100% full load burn-in test
- 2 years warranty
Applications
- Industrial control system
- Semiconductor fabrication equipment
- Factory automation
- Electro-mechanical apparatus
GTlN CODE
MW Search: https://www.meanwell.com/serviceGTIN.aspx
Description
EDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input f rom 90 VAC to 264 VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
EDR-75 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20℃ and 60℃ under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-75 a very competitive power supply solution for industrial applications
Model Encoding
SPECIFICATION
MODEL | EDR-75-12 | EDR-75-24 | EDR-75-48 |
---|---|---|---|
OUTPUT | DC VOLTAGE | 12V | 24V |
RATED CURRENT | 6.3A | 3.2A | 1.6A |
CURRENT RANGE | 0 ~ 6.3A | 0 ~ 3.2A | 0 ~ 1.6A |
RATED POWER | 75.6W | 76.8W | 76.8W |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 150mVp-p |
VOLTAGE ADJ. RANGE | 12 ~ 14V | 24 ~ 28V | 48 ~ 55V |
VOLTAGE TOLERANCE **Note.3** | ±2.0% | ±1.0% | ±1.0% |
LINE REGULATION | ±0.5% | ±0.5% | ±0.5% |
LOAD REGULATION | ±1.0% | ±1.0% | ±1.0% |
SETUP, RISE TIME | 1200ms, 60ms/230VAC 2000ms, 60ms/115VAC |
at full load
HOLD UP TIME (Typ.)| 60ms/230VAC 12ms/115VAC at full load
INPUT| VOLTAGE RANGE Note.6| 90 ~ 264VAC 127 ~ 370VDC
[DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 85.5%| 87.5%| 88.5%
AC CURRENT (Typ.)| 1.45A/115VAC 0.9A/230VAC
INRUSH CURRENT (Typ.)| 20A/115VAC 35A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION| OVERLOAD| 105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after
fault condition is removed
OVER VOLTAGE| 14 ~ 17V| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -20 ~ +60℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X,
Y, Z axes; Mounting: Compliance to IEC60068-2-6
**SAFETY & **EMC (Note 4)| SAFETY STANDARDS| UL508, TUV BS
EN/EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/
70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class A, BS
EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS
EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),heavy industry level, EAC TP
TC 020
OTHERS| MTBF| 2777.2K hrs min. Telcordia SR-332 (Bellcore) ;
506.6K hrs min. MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.51Kg; 28pcs/15.3Kg/1.22CUFT
NOTE|
- All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
- Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
- Tolerance : includes set up tolerance, line regulation and load regulation.
- The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
- Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
- Derating may be needed under low input voltage. Please check the derating curve for more details.
- The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).
※ Product Liability Disclaimer:For detailed information, please refer to https://[www.meanwell.com/serviceDisclaimer.aspx](http://www.meanwell.com/serviceDisclaimer.aspx)
Block Diagram
Derating Curve
Static Characteristics
Mechanical Specification
Terminal Pin No. Assignment (TB1)
Pin No. | Assignment |
---|---|
1 | FG |
2 | AC/N or DC – |
3 | AC/L or DC + |
Terminal Pin No. Assignment (TB2)
Pin No. | Assignment |
---|---|
1,2 | DC OUTPUT -V |
3,4 | DC OUTPUT+V |
Installation Instruction
ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)
This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.
Installation Manual
Please refer to : http://www.meanwell.com/manual.html
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>