Features

  • Universal AC input / Full range
  • Protections: Short circuit / Overload / Over voltage / Over temperature
  • Cooling by free air convection
  • Can be installed on DIN rail TS-35/7.5 or 15
  • UL 508 (industrial control equipment) approved
  • BS EN/EN61000-6-2(BS EN/EN50082-2) industrial immunity level
  • 100% full load burn-in test
  • 2 years warranty

Applications

  • Industrial control system
  • Semiconductor fabrication equipment
  • Factory automation
  • Electro-mechanical apparatus

GTlN CODE

MW Search: https://www.meanwell.com/serviceGTIN.aspx

Description

EDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5 or TS-35/15 mounting rails. The body is designed 32mm in width, which allows space saving inside the cabinets. The entire series adopts the full range AC input f rom 90 VAC to 264 VAC and conforms to BS EN/EN61000-3-2, the norm the European Union regulates for harmonic current.

EDR-75 is designed with metal housing that enhances the unit’s power dissipation. With working efficiency up to 88.5%, the entire series can operate at the ambient temperature between -20℃ and 60℃ under air convection. It is equipped with constant current mode for over-load protection, fitting various inductive or capacitive applications. The complete protection functions and relevant certificates for industrial control apparatus (UL508, TUV BS EN/EN62368-1, and etc.) make EDR-75 a very competitive power supply solution for industrial applications

Model Encoding

Model Encoding

SPECIFICATION

MODEL EDR-75-12 EDR-75-24 EDR-75-48
OUTPUT DC VOLTAGE 12V 24V
RATED CURRENT 6.3A 3.2A 1.6A
CURRENT RANGE 0 ~ 6.3A 0 ~ 3.2A 0 ~ 1.6A
RATED POWER 75.6W 76.8W 76.8W
RIPPLE & NOISE (max.) Note.2 80mVp-p 120mVp-p 150mVp-p
VOLTAGE ADJ. RANGE 12 ~ 14V 24 ~ 28V 48 ~ 55V
VOLTAGE TOLERANCE **Note.3** ±2.0% ±1.0% ±1.0%
LINE REGULATION ±0.5% ±0.5% ±0.5%
LOAD REGULATION ±1.0% ±1.0% ±1.0%
SETUP, RISE TIME 1200ms, 60ms/230VAC              2000ms, 60ms/115VAC

at full load
HOLD UP TIME (Typ.)| 60ms/230VAC       12ms/115VAC at full load
INPUT| VOLTAGE RANGE Note.6| 90 ~ 264VAC           127 ~ 370VDC [DC input operation possible by connecting AC/L(+), AC/N(-)]
FREQUENCY RANGE| 47 ~ 63Hz
EFFICIENCY (Typ.)| 85.5%| 87.5%| 88.5%
AC CURRENT (Typ.)| 1.45A/115VAC        0.9A/230VAC
INRUSH CURRENT (Typ.)| 20A/115VAC        35A/230VAC
LEAKAGE CURRENT| <1mA / 240VAC
PROTECTION| OVERLOAD| 105 ~ 130% rated output power
Protection type : Constant current limiting, recovers automatically after fault condition is removed
OVER VOLTAGE| 14 ~ 17V| 29 ~ 33V| 56 ~ 65V
Protection type : Shut down o/p voltage, re-power on to recover
OVER TEMPERATURE| Shut down o/p voltage, re-power on to recover
ENVIRONMENT| WORKING TEMP.| -20 ~ +60℃ (Refer to “Derating Curve”)
WORKING HUMIDITY| 20 ~ 95% RH non-condensing
STORAGE TEMP., HUMIDITY| -40 ~ +85℃, 10 ~ 95% RH
TEMP. COEFFICIENT| ±0.03%/℃ (0 ~ 50℃)
VIBRATION| Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
**SAFETY & **EMC (Note 4)| SAFETY STANDARDS| UL508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet BS EN/EN60204-1)
WITHSTAND VOLTAGE| I/P-O/P:3KVAC I/P-FG:2KVAC  O/P-FG:0.5KVAC
ISOLATION RESISTANCE| I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25℃/ 70% RH
EMC EMISSION| Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A
EMC IMMUNITY| Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55035, BS EN/EN61000-6-2 (BS EN/EN50082-2),heavy industry level, EAC TP TC 020
OTHERS| MTBF| 2777.2K hrs min.        Telcordia SR-332 (Bellcore) ; 506.6K hrs min.           MIL-HDBK-217F (25℃)
DIMENSION| 32125.2102mm (WHD)
PACKING| 0.51Kg; 28pcs/15.3Kg/1.22CUFT
NOTE|

  1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature.
  2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
  3. Tolerance : includes set up tolerance, line regulation and load regulation.
  4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives.
  5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended.
  6. Derating may be needed under low input voltage. Please check the derating curve for more details.
  7.  The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft).

※ Product Liability Disclaimer:For detailed information, please refer to https://[www.meanwell.com/serviceDisclaimer.aspx](http://www.meanwell.com/serviceDisclaimer.aspx)

Block Diagram

Block Diagram

Derating Curve

Derating Curve

Static Characteristics

Static Characteristics

Mechanical Specification

Mechanical Specification

Terminal Pin No. Assignment (TB1)

Pin No. Assignment
1 FG
2 AC/N or DC –
3 AC/L or DC +

Terminal Pin No. Assignment (TB2)

Pin No. Assignment
1,2 DC OUTPUT -V
3,4 DC OUTPUT+V

Installation Instruction

Installation Instruction
ADMISSIBLE DIN rail:TS35/7.5 OR TS35/15
(For reference only. Not included with unit.)

This series fits DIN rail TS35/7.5 or TS35/15.
For installation details, please refer to the Instruction manual.

Installation Manual

Please refer to : http://www.meanwell.com/manual.html

Read User Manual Online (PDF format)

Loading......

Download This Manual (PDF format)

Download this manual  >>

MEAN WELL User Manuals

Related Manuals