Schneider Electric LC1 D115 Reversing Contactors Instruction Manual

June 1, 2024
Schneider Electric

LC1 / LC2 D115 D150

www.se.com

Contactors / Reversing contactors


LC1 D115                                                 LC1 D1156
LC1 D115004                                      LC1 D1150046
LC2 D115                                                 LC2 D1156
LC2 D115004                                      LC2 D1150046
LC1 D150                                                LC1 D1506
LC2 D150                                                LC2 D1506


“For motor starting use Schneider Electric TeSys Protect – Deca overload relays”


W9 1511301 0123 15
11 – 2023

PLEASE NOTE

  • Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.

  • No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material.

WARNING: This product can expose you to chemicals including Antimony oxide (Antimony trioxide), which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov.

WARNING

HAZARD OF FIRE OR ELECTRIC SHOCK
(FOR CONTACTOR WITH UL HI-FAULT SHORT CIRCUIT CURRENT RATINGS ONLY)

  • The opening of the branch-circuit protective device may be an indication that a fault current has been interrupted.
  • To reduce the risk of fire or electric shock, current-carrying parts and the other components of the controller should be examined and replaced if damaged.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Schneider Electric LC1 D115 Reversing Contactors - a1

a) LAD 11567

b) LA1 D•
LAD N•

c) LA1 D•
LAD N•
LAD C•

d) LA6 DK20

e) LA2 D•
LA3 D•
LAD R•
LAD S•
LAD T•

f) LA8 D•
LAD 8•

g) LA1 D•
LA2 DT•
LA3 DR•
LA6 DK20

h) LAD N•
LAD C•
LAD R•
LAD S•
LAD T•


LA8 D•
LAD 8•

LC1

3P                                    4P


LC2

3P                                                                       4P


        Schneider Electric LC1 D115 Reversing Contactors -
a12

a) c = 1,2 N.m
c = 10 lb.in.

Schneider Electric LC1 D115 Reversing Contactors - a13

a) C = 1,7 Nm
C = 15 lb.in


inches = mm x 0.0394

Schneider Electric LC1 D115 Reversing Contactors - b4

  1. 168 (LA2 D, LA3 D, LADT, LADR, LADS)
  2. 155 (LA6 DK20)
  3. 150 (LA1 D, LADN, LADC)

inches = mm x 0.0394

|

LC1

---|---
mm| | 3P|

4P

a

| |

120

|

155

c

| D115••
D115••6|

132
115

|

132
115

D150••
D150••6|

132
115

|


c1

| D1156|

122

|

122

D1506|

122

|

G

| D115|

96/110

|

130/144

D150|

96/110

|

d

| AM1 DP200|

2

|

2

AM1 DE200|

9,5

|

9,5

DANGER

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Disconnect all power before servicing equipment.
Failure to follow these instructions will result in death or serious injury.

inches = mm x 0.0394

|

LC2

---|---
mm| 3P|

4P

a

| 266| 334
b1| 56|

b2

| 18| 60
c| 148|

148

G

|

D115

| 242/256| 310/324

D150

| 242/256|

WARNING

UNEXPECTED EQUIPMENT OPERATION
Use a torque wrench to apply the right tightening torques.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
| [mm²]| [mm2²]| [mm²]| [mm²]| [mm²]| [mm²]| [mm]| PH2/PZ2| [mm]|

N.m

---|---|---|---|---|---|---|---|---|---|---
D 115
D 150| | 10
:
120| 10…120

  • 10…50| 10
    :
    120| 10…120
  • 10…50| 10
    :
    120| 10…120

  • 10…50| 20| –| 4| 12±1
    LX-D
    LA-D| | 1…2,5| 1…2,5

  • 1…2,5| 1…2,5| 1…2,5

  • 1…2,5| 1…2,5| 1…2,5

  • 1…2,5| 20| 6| –| 1.2
    |

AWG

| AWG| AWG| AWG| AWG| AWG| [in.]| PH2/PZ2| [mm]|

lb.in.

---|---|---|---|---|---|---|---|---|---|---
D 115
D 150| | AWG 8…
250 MCM| AWG 8…
250 MCM

  • 8…0| AWG 8…
    250 MCM| AWG 8…
    250 MCM
  • 8…0| AWG 8…
    250 MCM| AWG 8…
    250 MCM

  • 8…0| 25/32| –| 5/32| 100±9
    LX-D
    LA-D| | 18…40| 18…40

  • 18…40| 18…40| 18…40

  • 18…40| 18…40| 18…40

  • 18…40| 25/32| 6| –| 10
    |

[mm]

| [mm]| [mm]| [mm]| PH2/PZ2| [mm]|
---|---|---|---|---|---|---|---
D 115…6
D 150…6| | –| M8| 25| 25| | 13|

12±1N.m
/
100±9lb.in.

LX-D
LA-D| | M3,5| –| 8| | Ø6
mm| |

1.2N.m
/
10lb.in.

inches = mm x 0.0394

Serial timer : on-delay|
LA4 DT••| Schneider Electric LC1 D115 Reversing Contactors -
d6
---|---|---
Relay interface|
LA4 DF••
Auto – 1|
LA4 DL•
Solid state interface|
LA4 DW•
Auto – 0 – 1|
LA4 DM•
|

3P

| 4P
---|---|---
   | LA9 D115603|

LA9 D115604

   |

LA9 D115503

| LA9 D115504
 | LA9 D115703|

LA9 D115704

| (D115)
LA5 D11550| (D115)
LA5 D115450
(D150)
LA5 D15050| –
| (D115)
LA5 D1158031| (D115)
LA5 D115804
(D150)
LA5 D150803| –
|

LAD 9ET4

Contents of Toxic or Hazardous Substances or Elements


|

Toxic or hazardous Substances and Elements

Part Name|

(Pb)

| (Hg)| (Cd)| (Cr6+)| (PBB)|

(PBDE)

Electronics Board |

X

| O| O| O| O|

O

O: Indicates that this toxic or hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement in SJ/T11363-2006.
X: Indicates that this toxic or hazardous substance contained in at least one of the homogeneous materials used for this part is above the limit requirement in SJ/T11363-2006
Note: The products on sale may or may not contain all the parts/components listed here.
3P AC TeSys Deca contactors (LC1D115 -> LC1D150) are grade 3 according to GB 21518.
Maximum power consumption lower than 36.6 VA.

Open

| (A)

    1 mm

| (B)

---|---|---

Close

| (A’)

    12 mm

| (B’)

The product’s manufacture date is coded PPYYWWD, where:

  • PP: plant code
  • YY: year of manufacture
  • WW: week of manufacture
  • (D: weekday of manufacture (Monday = 1))

Schneider Electric Limited
Stafford Park 5
Telford, TF3 3BL
United Kingdom
www.se.com/uk

Schneider Electric Industries SAS
35, rue Joseph Monier
CS30323
F – 92500 Rueil-Malmaison
www.se.com

W9 1511301 0123 15          © 2023 Schneider Electric – All rights reserved.