POWER-LITE LED3W-ENM-B LED Emergency Light Instruction Manual

October 30, 2023
POWER-LITE

POWER-LITE LED3W-ENM-B LED Emergency Light Instruction Manual
POWER-LITE LED3W-ENM-B LED Emergency Light

Precautions

Normal Operation: The green LED indicator stays on when connected to mains supply. The indicator will turn off when the mains supply fails, or when the internal charger malfunctions, or when the luminaire is in test mode.

Battery: LiFePO4 rechargeable battery pack. Battery should be replaced when it reaches the end of its lifetime. To avoid damage to the luminiare and ensure its performance, the battery should be replaced with same type.

Test Switch: Press the test button, LED indicator will turn off and the luminaire will be powered by the battery pack. The light source is non- replaceable. When the light source reaches the end of its lifetime, the whole luminaire shall be replaced.

Installation Procedure


Turn Off Power Supply

WARNING

  1. Switch off before installation or maintenance.
  2. Switch on only after complete installation and examination of the circuit.
  3. Professional electrician for installation and maintenance only. Turn Off Power Supply Installation Procedure Recessed Mount Precautions
  4. This luminaire is not intended for use in high-risk task area lighting.

Read instructions and check you have all the tools and accessories to complete the installation correctly.

Recessed Mount

  1. Cutout:
    D55 Cover: 42-50mm
    D80 Cover: 66-70mm
    D140 Cover: 85-105mm
    Recessed Mount

  2. Go directly to the next step if no need D80/D140 cover.
    Recessed Mount

  3. Wire diameters: 0.5-0.75mm²
    Recessed Mount
    Standard wiring
    Recessed Mount
    DALI wiring
    Recessed Mount

Change Lens

Change Lens

Photometric Data

Round lens for open area application
Photometric Data
AVERAGE BEAM ANGLE(50%): 145.9 DEG

Mounting height Spacing distance
2.1m 11.5m
3.3m 18.1m
5.0m 25.2m

AS/NZS 2293.1:2018 (MINIMUM LIGHT LEVEL OF 0.2LUX)
Round lens| C0: D63
C90: D63

Oval lens for pathway application
Photometric Data
AVERAGE BEAM ANGLE(50%): 103.9 DEG

Mounting height Spacing distance
2.1m 9.0m
3.3m 14.1m
5.0m 18.6m

AS/NZS 2293.1:2018 (MINIMUM LIGHT LEVEL OF 0.2LUX)
Oval lens| C0: A50
C90: E63

Dual Colour LED Status Indicator Meaning

  • Green indicator solid on: Ready/ Normal Operation
  • Red indicator flashes: Require service
 • One flash, 4s pause Battery disconnected
 •• Two flashes, 4s pause Low battery voltage
 ••• Three flashes, 4s pause Charge board fault
 •••• Four flashes, 4s pause AC/DC transfer fault
 ••••• Five flashes, 4s pause LED lamp fault

Button Test

Press test button once run a 30s duration test
Press test button twice within 2s run a 3mins duration test
Press test button 3 times within 2s run a 30mins duration test
Press test button 4 times within 2s run a 2H duration test

Status indication for Self-Testing

System status is indicated by a bi-colour LED and by a DALI status flag.

**LED indication**

| **Status| Commentary
---|---|---
**
Permanent green| System OK|
Fast flashing green(0.1 sec. on – 0.1 sec. off)|
Function test underway|
Slow flashing green(1 sec. on – 1 sec. off)| Duration test|
Red LED on| Load failure| Open circuit /  Short circuit / LED failure
Slow flashing red(1 sec. on – 1 sec. off)| Battery failure| Battery failed the duration test or function test/ Battery is defect / Incorrect battery voltage
Fast flashing red(0.1 sec. on – 0.1 sec. off)|
Charging failure| Incorrect charging current
Double pulsing green| Inhibit mode| Switching into inhibit mode via controller
Binary transmission of address via green/red LED| Address identification| During address identification mode
Green and red off| Emergency mode| Battery operation (Emergency mode)