Precautions
Normal Operation: The green LED indicator stays on when connected to mains supply. The indicator will turn off when the mains supply fails, or when the internal charger malfunctions, or when the luminaire is in test mode.
Battery: LiFePO4 rechargeable battery pack. Battery should be replaced when it reaches the end of its lifetime. To avoid damage to the luminiare and ensure its performance, the battery should be replaced with same type.
Test Switch: Press the test button, LED indicator will turn off and the luminaire will be powered by the battery pack. The light source is non- replaceable. When the light source reaches the end of its lifetime, the whole luminaire shall be replaced.
Installation Procedure
Turn Off Power Supply
WARNING
- Switch off before installation or maintenance.
- Switch on only after complete installation and examination of the circuit.
- Professional electrician for installation and maintenance only. Turn Off Power Supply Installation Procedure Recessed Mount Precautions
- This luminaire is not intended for use in high-risk task area lighting.
Read instructions and check you have all the tools and accessories to complete the installation correctly.
Recessed Mount
-
Cutout:
D55 Cover: 42-50mm
D80 Cover: 66-70mm
D140 Cover: 85-105mm
-
Go directly to the next step if no need D80/D140 cover.
-
Wire diameters: 0.5-0.75mm²
Standard wiring
DALI wiring
Change Lens
Photometric Data
Round lens for open area application
AVERAGE BEAM ANGLE(50%): 145.9 DEG
Mounting height | Spacing distance |
---|---|
2.1m | 11.5m |
3.3m | 18.1m |
5.0m | 25.2m |
AS/NZS 2293.1:2018 (MINIMUM LIGHT LEVEL OF 0.2LUX)
Round lens| C0: D63
C90: D63
Oval lens for pathway application
AVERAGE BEAM ANGLE(50%): 103.9 DEG
Mounting height | Spacing distance |
---|---|
2.1m | 9.0m |
3.3m | 14.1m |
5.0m | 18.6m |
AS/NZS 2293.1:2018 (MINIMUM LIGHT LEVEL OF 0.2LUX)
Oval lens| C0: A50
C90: E63
Dual Colour LED Status Indicator Meaning
- Green indicator solid on: Ready/ Normal Operation
- Red indicator flashes: Require service
• | One flash, 4s pause | Battery disconnected |
---|---|---|
•• | Two flashes, 4s pause | Low battery voltage |
••• | Three flashes, 4s pause | Charge board fault |
•••• | Four flashes, 4s pause | AC/DC transfer fault |
••••• | Five flashes, 4s pause | LED lamp fault |
Button Test
Press test button once | run a 30s duration test |
---|---|
Press test button twice within 2s | run a 3mins duration test |
Press test button 3 times within 2s | run a 30mins duration test |
Press test button 4 times within 2s | run a 2H duration test |
Status indication for Self-Testing
System status is indicated by a bi-colour LED and by a DALI status flag.
**LED indication**
| **Status| Commentary
---|---|---
** Permanent green| System OK|
Fast flashing green(0.1 sec. on – 0.1 sec. off)| Function test underway|
Slow flashing green(1 sec. on – 1 sec. off)| Duration test|
Red LED on| Load failure| Open circuit / Short circuit /
LED failure
Slow flashing red(1 sec. on – 1 sec. off)| Battery failure| Battery
failed the duration test or function test/ Battery is defect / Incorrect
battery voltage
Fast flashing red(0.1 sec. on – 0.1 sec. off)| Charging failure|
Incorrect charging current
Double pulsing green| Inhibit mode| Switching into inhibit
mode via controller
Binary transmission of address via green/red LED| Address
identification| During address identification mode
Green and red off| Emergency mode| Battery operation (Emergency
mode)
Free Call: 1800 909 306