Installation and Maintenance Manual
Air Cooled Thermo Con for Rack Mount
HECR Series
Original Instructions
Read Before Using
Thank you for purchasing SMC’s Thermo-con (hereinafter referred to as the “product”). This “Installation and Maintenance Manual” (hereinafter referred to as “this manual”) briefly explains the essential safety instruction procedures to start and stop the product and reset its alarms. Read this manual before using.
Safety Instructions
This manual contains essential information for the protection of users and others from possible injury and/or equipment damage.
- Read this manual before using the product, to ensure correct handling, and read the manuals of related apparatus before use.
- Keep this manual in a safe place for future reference.
- These instructions indicate the level of potential hazard by label of “Caution”, “Warning” or “Danger”, followed by important safety information which must be carefully followed.
- To ensure safety of personnel and equipment the safety instructions in this manual and the product catalogue must be observed, along with other relevant safety practices.
Caution| If instructions are not followed there is a possibility of injury or equipment damage.
---|---
Warning| If instructions are not followed there is a possibility of serious injury or loss of life.
Danger| In extreme conditions, there is a possibility of serious injury or loss of life. - This manual provides the following symbols in addition to “Danger”, “Warning”, and “Caution” to present warning details in an easy-tounderstand manner.
| This symbol warns you of potential electrical shock.
---|---
| This symbol warns you of potential burns.
Danger
- During operation or maintenance of the product, do not disable the interlock function of any device. Otherwise unexpected personnel injury or damage to the product may occur.
- When turning on/off the power observe the procedure. Otherwise unexpected malfunction or danger may occur.
- When maintaining, cleaning or in case of emergency, turn off the power source.
- After identifying a problem be sure to check the cause and take necessary countermeasures before turning on the power.
- The product is operated at high voltage.
Warning
-
The compatibility of equipment is the responsibility of the person who designs the system or decides its specifications. Since the products specified here can be used in various operating conditions, their compatibility with the specific system must be based on specifications or after analysis and/or tests to meet specific requirements.
-
Only trained personnel should handle or operate the product. Transportation, installation and maintenance of the product can be dangerous and should be done by persons who have full knowledge and experience on the product and system. Cover panels of the product should be opened only by qualified service technicians or qualified personnel.
-
Do not modify or reconstruct the unit.
-
Read all warning and caution labels carefully and keep them in mind.
Do not peel off or rub alert warning and caution labels. Confirm locations of alert warning and caution labels. -
Do not service machinery/equipment or attempt to remove components until safety is confirmed.
- Inspection and maintenance of machinery/equipment should only be performed after confirmation of safe locked-out positions.
- When equipment is to be removed, confirm the safety process as mentioned above. Switch off electrical supplies and ensure any high temperature parts have cooled to ambient temperature.
- Before machinery/equipment is re-started, ensure all safety measures are taken so the product and system can be started in a safe manner.
- Do not use this product outdoor (indoor use).
- Do not use this product outside of the specifications. Contact SMC if it is to be used in any of the following conditions.
- Conditions and environments beyond the given specifications.
- Installations in conjunction with atomic energy, railway, air navigation, vehicles, medical equipment, food and beverage, recreation equipment, emergency stop circuits, press applications, or safety equipment.
- If abnormal conditions occur, such as abnormal noise or smoke, or water leakage, take the following actions。
- Shut down power.
- Contact an authorised SMC dealer for repair.
Caution
- After shutting down the power supply, ensure a time interval at least 3sec between ON and OFF. Restarting the product within that interval may cause it to malfunction.
- Do not use devices that generate electromagnetic radiation such as cellular phones near the product. There is a possibility that this can cause the product to malfunction.
- This unit has several interlock functions, which activate when a dangerous operation or condition occurs to stop the product and make it safe. This is a function to protect personnel and restrict operation that may cause damage to the product or facility, and to remove dangers related to safety.
- When dispose the product, contact an industrial waste disposal company for disposal of the product. To minimize the risk, drain the fluid from the product when it is scrapped. If the fluid is left inside, an accident and damage can result during transportation.
Specifications
3.1 General Description and Intended Use
This product uses a built in pump to circulate liquid (water or 20% EG) at a
constant temperature, controlled by Thermo-Electric (Peltier) Modules. This
circulating fluid cools parts of the customer’s machine that generates heat.
3.2 General Specifications
Item | Spec. |
---|---|
Model No. | HECR002 HECR004 HECR006 |
Operation temp. range | 10.0 to 60.0 °C (No dew condensation) |
Indication temp. range | -9.9 to 80.0 °C |
Ambient environment | Temp: 10 to 35 °C |
Humidity : 35 to 80%RH
Altitude : up to 1000m
Environment : No corrosive gas, solvent such as thinner and flammable gas
Storage environment| Temp :40 to 70 °C (No dew condensation and icing)
Humidity : 5 to 95%RH
Environment : No corrosive gas, solvent such as thinner and flammable gas
Accuracy related to temp| Indication accuracy: +/- 0.2 °C. Temperature drift:
+/- 0.2°C Stability: +1- 0.01 to 0.03 °C
(Circulating fluid OUT is directly connected with IN)
Cooling capacity
(Set temperature 25t and ambient temperature 25t)| Approx. 200W
(Flow rate 3Umin)| Approx. 400W
(Flow rate 3L/min)| Approx. 510W
(Flow rate 3Umin)| Approx. 800W
(Flow rate 41Jmin)| Approx. 1000W
(Flow rate 41Jmin)
Circulating fluid| Water, Ethylene glycol solution up to 20%
Tank capacity| Approx.1.3L
Pump capacity| Refer to performance chart.
Port size| IN/OUT: Rc1/4| IN/OUT: Rc3/8| IN/OUT: Rc3/8
Drain: CPC PLCD16004
Wetted materials| Stainless steel, EPDM, NBR, Ceramic, PPE, PPS, Carbon,
Polyethylene, POM
Power supply| Single phase AC100 to 240V(+/- 10%), 50/60Hz| Single phase
AC200 to 240V
(+/- 10%), 50/60Hz
Current consumption| Max.5A(100V)
Max.2.5A(240V)| Max.9A(100V)
Max.4A(240V)| Max.10A(100V)
Max.4A(240V)| Max.8A (200V)
Inrush current| 50A or less
Over current protection| 10A
circuit protector| 14A
circuit protector
Voltage interruptions| 20ms or less
Insulation resistance| 50MQ or more (DC500V)
Over voltage category| Category II
Pollution degree| Pollution degree II
Limitation of hazardous substance| RoHS compliant products
Item Model No.| Spec.
HECR002 HECR004 HECR006 HECR008 HECR010
---|---
Acoustic noise| 54 to 62dBA 55 to 64dBA 54 to 65dBA
49dBA
(variable fan speed control)
Cooling method| Air cooled
Main functions| Auto tuning, Off set function, Learning control function,
External tuning control function, Temperature sensor fine control function,
Setting value memory function, Upper / lower temperature limit alarm function,
Output shut off alarm, Communication,
Fan speed control(HECR004,HECR006,HECR008,HECR010)
Input operation and indications| Membrane key sheet
LCD display panel (with back light) Output shut off alarm,
Upper / lower temperature limit alarm : Relay contact specification
DC30V, 2A (Resistance load) DC30V, 1A (Induction load)
Communications| RS-232C / RS-485
Communications:
Setting of target temperature, Reading of the value detected by temperature
sensor,
Reading of warning status, Setting and of off-set value, Setting and reading
of control operation, Setting and reading of PID values, Reading of output
ratio.
For operation by communication, it is necessary to order
“Communication Manual’.
Use shielded cable for serial communications.
Temp. sensor| Resistance thermometer sensor (Pt10012, 3-wire, class A, 1mA)
(Both internal sensor and external sensor)
Painting color| Urban white
Mass (at dry)| Approx 14kg| I Approx 18kg| I Approx 21kg| I Approx 31kg| I
Approx 33kg
Option| With flow switch Low flow rate alarm occurs at less than 0.71/min NPT
fitting: Fluid IN/OUT fittings
With foot and no rack bracket
High head pump
Contents of package| Thermo-con 1pc
Installation and Maintenance Manual 1pc Power supply connector 1pc
3.3 Performance Charts
Values on the performance charts are not guaranteed values but representative
values. Allow margins for safety when selecting the model.
3.3.1 Cooling Capacity
HECR002
*Cooling capacity decrease about 20W when high head pump option selected.
HECR004
*Cooling capacity decrease about 50W when high head pump option selected.
HECR006
*Cooling capacity decrease about 50W when high head pump option selected.
HECR008
*Cooling capacity decrease about 50W when high head pump option selected.
HECR010
*Cooling capacity decrease about 50W when high head pump option selected.
3.3.2 Heating Capacity
HECR002
HECR004
HECR006
HECR008
HECR010
3.3.3 Pump Capacity
HECR002
HECR004
HECR006
HECR008/HECR010
3.4 Connector Specifications
Description | No. | Signal | Style and Part No. |
---|
Power supply
connector
(IEC60320,C14)| | HECR002 HECR004 HECR006 HECR008| HECR010|
N| AC100 to 240V| AC200 to 240V
L| AC100 to 240V| AC200 to 240V
E| | PE
Communication
connector
Note: Always
use shielded
cable connected
to this connector.| | RS-232C| RS-485| D-sub 9 pin (socket type)
Fixed screw: M2.6
1| Unused| BUS +
2| RXD (RD)| Unused
3| TXD (SD)| Unused
4| Unused| Unused
5| SG| SG
6-8| Unused| Unused
9| Unused| BUS –
Signal –
External
temperature
sensor
connector
Note: Always
use shielded
cable connected
to this connector.| 1-2| Unused| D-sub 15 pin (Socket type)
Fixed screw: M2.6
RTD wiring
3-5| PT-RTD
6| Output Cutoff Alarm a contact
(OPEN During Alarm)
7| Output Cutoff Alarm Common
8| Output Cutoff Alarm b contact
(CLOSE During Alarm)
9| Temperature Alarm a contact
(OPEN During Alarm)
10| Temperature Alarm Common
11| Temperature Alarm b contact
(CLOSE During Alarm)
12-14| Unused
15| FG
3.5 Model number of product
The product can be ordered with the model number configured as shown below.
HECR
3.6 Product Serial Number Code
The production serial number code printed on the label indicates the year and
month of production as per the following table:
Month/Year| 2015| 2016| 2017| ….| 2021|
2022| 2023| ….
---|---|---|---|---|---|---|---|---
T| U| V| ..| Z| A| |
Jan| o| To| Uo| Vo| ..| Zo| Ao| Bo| .
Feb| P| TP| UP| VP| ..| ZP| AP| BP| .
Mar| Q| TQ| UQ| VQ| ..| ZQ| AQ| BQ| ..
Apr| R| TR| UR| VR| ..| ZR| AR| BR| ….
May| S| TS| US| VS| ..| ZS| AS| BS| ..
Jun| T| TT| UT| VT| ..| ZT| AT| BT| ..
Jul| U| TU| UU| VU| ..| ZU| AU| BU| ….
Aug| V| TV| UV| VV| ..| ZV| AV| BV| ..
Sep| W| TW| UW| VW| ..| ZW| AW| BW| ..
Oct| X| TX| UX| VX| ..| ZX| AX| BX| .
Nov| y| Ty| Uy| Vy| ..| Zy| Ay| By| ..
Dec| Z| Tz| UZ| VZ| ..| ZZ| AZ| BZ| .
Special Features
- Auto tuning
This function sets the values necessary for the control system such as PID (proportional band, integral time, derivative time and ratio of cooling/heating gain) automatically.
If the controlled temperature fluctuates constantly after reaching the target temperature, perform auto tuning. Controller calculates optimum control PID and set automatically. Auto tuning may require time depending on the conditions.
- Select “2” in control operation.
- Pressing [AT] key to light “AT” indicator and start auto tuning.
- Pressing [AT] key stops auto tuning. (“AT” indicator turns off)
- ”AT” indicator turns off when auto tuning is complete. If not completed after 20min. [ERR19] (AT abnormal) occurs.
-
Offset function
This function controls the temperature slide by an offset value from set point temperature. When the circulating fluid travels to the target object, a certain deviation occurs between the temperature just before the object and the set temperature of the product due to the influence of ambient temperature on the piping. In this case, if the deviation is input as the offset value, the temperature of the circulating fluid just before the object can match with the setting value. Internal sensor value for the alarm does not include the offset value. For example, if -0.15 °C is set here, the actual reference temperature for control is lower than the indicated SV by 0.15 °C. Internal sensor value for the alarm does not include the offset value. -
Learning control function
This function lets the product measure the temperature of circulating fluid flowing before temperature target object by an external temperature sensor and adjusts the offset function automatically to the set value at a certain sampling interval. The external temperature sensor needs to be prepared separately by the customer.
- Install an external temperature sensor to the target object.
- Select “3” in control operation.
- Thermo-con controls the external sensor value to the set point.
- When the temperature is not stable, then set the sampling interval larger.
- External tuning control function
This function makes the temperature of circulating fluid consistent to the external (ambient) temperature all times. This function lets the product measure the temperature from a temperature sensor mounted in the customer preferred location, then it adjust the temperature of the fluid automatically to the temperature detected by the sensor. The separate temperature sensor needs to be prepared separately by the customer.
- Install an external temperature sensor to the room.
- Select “4” in control operation.
- Thermo-con controls the fluid temperature to the ambient temperature.
- When the temperature is not stable, then set the sampling interval larger.
-
Temperature sensor fine control function
This is a function to finely control the measurement temperature of the control sensor within the range of -9.99 to 9.99 °C separate from offset function. Control sensor can be corrected by inputting difference (calibration value) between temperature of standard and that of control sensor. For example, if -0.15 °C is set here, the actual reference temperature for control is lower than the indicated SV by 0.15 °C.
Internal sensor value for alarm = Internal sensor value – Fine control value -
Setting value memory function
Even if the power is turned off the set values are saved and will be restored at power on. -
Upper / Lower temperature limit alarm function
This function raises an alarm when temperature of the circulating fluid is out of allowable upper and lower range. When the alarm is raised, WRN is indicated on LCD. If circulating fluid temperature returns to within allowable upper/ lower range, this alarm is automatically cancelled. The allowable upper and lower range of temperature can be set between 0.1 and 10 °C. -
Output shut off alarm function
The product has a self-check function that can detect faults with the product and interrupts the output to the thermo modules, stopping operation (However, operation continues with ERR 15 and ERR 18). This function gives an alarm if a critical error happens, the display shows ERR and an alarm number. At the same time, the warning output connector gives an output through a relay contact. This warning cannot be removed unless the power is cycled. When the power is being cycled leave at least 3 seconds between turning the power off and turning the power back on.
Installation
5.1 Installation
- Pay special attention to the safety of all personnel when installing andtransporting the product.
- Do not install the product unless the safety instructions have been readand understood.
- The product is heavy, be careful when installing or moving the product.
- Always transport the product using both handles.
- Leakage from the product may damage peripheral equipment. Install adrain pan under the product to capture leakage. Furthermore, mountdevices like a leak sensor on the installed drain pan to detect leakage sothat it can alert operators around the area.
- Install the product above 0.6m from the floor.
5.2 Environment
- Do not use in an environment where the product is directly exposed to water, oil, corrosive gases, chemicals, salt water or steam.
- The product should be installed upright on a stable base.
- Do not install the product in a location where the air inlet and air outlet vents are blocked. Also do not use the product in a sealed enclosure.
- Do not use in an explosive atmosphere.
- Do not mount the product in a location where it can be exposed to prolonged sunlight. Use a protective cover.
- Do not mount the product in a location where it is subject to strong vibrations and/or shock. Check the product specifications.
- Do not use the product where it can be exposed to strong electrical or magnetic emissions.
- Do not mount the product in a location where it is exposed to noise sources (such as discharging equipment, large relay and thyristor).
5.3 Mounting
- When mounting the product to a cabinet, use a design which shall hold the weight at the bottom. Ensure safety with transportation test if the product is to be installed on a transportation device such as a trailer.
- Mount the product using the fixing holes in the front of the product. Use M5,M6 screws (bolts) or equivalent to the fix the product.
- Be sure to correctly tighten all screws to the required torque. (M5:3.0Nm, M6:5.2Nm)
5.4 Piping
- Ensure that the power source and the power supply of the product is turned off (or the power plug must come off )
- Ensure the flow rate of the circulating fluid is as high as possible to maintain the temperature stability. Therefore, the length of the external piping should be minimized and internal diameter should be as large as possible. Piping must have sufficient strength for the maximum discharge pressure of the circulating circuit.
- Likewise, if a tube is bent or multiple elbow fittings are used, the piping resistance will increase and the flow rate will decrease. If the flow rate falls, the temperature stability will decrease.
- If installing a tank externally, only a sealed tank should be used. Do not use an open tank.
5.5 Wiring
- Ensure that the power source and the power supply of the product is turned off before connecting the various connectors and power supply cable.
- Supply disconnecting device according to IEC60974-1 and IEC60947-3 for the product must be provided in the end system.
- Do not install the disconnecting device in the place where the operation is difficult. And also the switch of the disconnecting device must comply with the direction of the switch specified by IEC60447.
- Preparation and wiring of power supply cable
- Strip the sheath from both ends of the cable.
- Disassemble the power supply connector. Crimp one end of the cable to L, N, E inside of the connector, then reassemble the power supply connector.
- Connect the other end of the cable to a plug or terminals (e.g. crimped
terminal).
- Ensure that there is enough space between the power supply cable and the communication cable of the product and power cables of other equipment.
- Ensure the power supply and ground connections are made correctly.
- Be sure to provide the grounding. The PE line of the power supply cable is available for grounding. Do not connect the ground in common with the ones for equipment that generates strong electromagnetic noise or high frequency.
- When an external temperature sensor is connected, connect the sensor with a shield cable. Use a platinum resistant temperature sensor (Pt100ohm, 3-wiring type, class A, 1mA).
- Connect the host to this unit with a twisted pair shield cable when applying communication function or external sensor and alarm output function.
- When using the Communication connector and Signal/External temperature sensor, connect the circuit separated from the mains circuit by reinforced insulation.
- Ensure that external instruments connecting to this product provide the enclosure complied with UL61010-1 and use the cable which provide flame resistance (over VW-1).
5.6 Filling the product
-
Ensure that the power source and the power supply of the product is turned off (or the power plug must come off).
-
Remove the reservoir cap.
(When setting the product again, confirm the level of fluid does not exceed the “H” mark) -
If using Ethylene Glycol, refer to the suppliers Material Safety Data Sheet (MSDS) and wear Personal Protective Equipment (PPE) as appropriate.
-
Fill the circulating fluid into the reservoir. Stop filling once the level of fluid reaches the “H” mark.
-
Turn on the power switch to fill the piping with the fluid.
-
When the piping is filled with the circulating fluid, the level of the reservoir decreases and low fluid level alarm (ERR20) arises accordingly. Then, turn off the power supply once again.
-
Repeat the step from 4 to 6 until ERR20 alarm doesn’t appear anymore.
-
Then, replace the cap on the reservoir and tighten it securely.
-
Keep the fluid level between H and L of the level indicator.
Operation
6.1 Power Up
When power is turned on, the software version is indicated on display panel
for approx. 1 second.
6.2 Operation
The product begins operation immediately after the power is turned on.
The pump and heat exchanger will be running and the product will begin
temperature control.
The display can show the following information during operation.
6.3 Settings
Three different levels of settings are available depending on the content,
which needs to be set.
Level 1: Used in normal operation e.g. setting of target temperature and
offset.
Level 2: Used at maintenance and initial setting for setting of
controller/PID.
Level 3: Used at initial setting for the communication function.
The key functions are as follows:
[SEL]: Used to show the item that needs to be changed in selected mode level.
[▽△]: Used to change the value of the item selected.
[RET]: Used to fix the value changed by [▽△] key.
Press again to return to current temperature indication. [AT]: Used to start
auto tuning in auto tuning mode
(This function works when the control operation mode is 2 in level setting 1)
When pressed during auto tuning, the auto tuning is stopped.
- When no input is made within 1 minute regardless of setting mode, the display returns to the current temperature indication.
- The data input is written to FRAM and memorized after the power supply is turned off.
- To return all of the setting values to default: Turn on the power supply while pressing [SEL] and [RET] keys.
6.3.1 Level 1-Settings
No.| Modes| Setting contents| Setting e rang
(Min. increment)| Default
---|---|---|---|---
1| Target Temp.
(No indication on
display)| Sets target temp. for control.| 10.0 to 60.0°C
(0.1°C)| 25.0
2| Control Operation| Selects control operation mode from those shown below.
0: Pump stop (No control)
1:Normal operation
2:AT(auto tuning)
3:Learn (learning control)
4:External (external tune control)
5:SeriRem (Serial remote) 5:Serial remote is displayed when choose the Modbus
communication.| 0,1,2,3,4,5|
3| External Sensor Sampling Cycle| Sets sampling cycle for learning control or
external tune control.| 10 to 999sec
(1sec)| 60
4| Offset Value| Indicates the offset value of the circulating fluid
temperature used as reference value by the
controller (SV + Offset).| -9.99 to 9.99°C
(0.01°C)| 0.00
5| Allowable Upper Temp. Range| Sets upper limit of temp. range which causes a
warning to occur.| 0.1 to 10.0°C
(0.1°C)| 2.
6| Allowable Lower Temp. Range| Sets lower limit of temp. range which causes a
warning to occur.| 0.1 to 10.0°C
(0.1°C)| 2.
7| High Temp. Cutoff| Sets upper limit of temp.
measured by the internal temp. sensor and stops operation of the product.|
11.0 to 70.0°C
(0.1°C)| 70.0
8| Low Temp. Cutoff| Sets lower limit of temp. measured by the internal temp.
sensor and stops operation of the product.| 0.0 to 59.0°C
(0.1°C)| 0.0
6.3.2 Level 2-Settings
No
1| Modes
Fine Control of
Internal Sensor| Setting contents| Setting range
(Min. increment)
-9.99 to 9.99°C
(0.01°C)| Default
0.00
---|---|---|---|---
Sets the fine adjusting value to calibrate the internal temp. sensor
2| Fine Control of
External Sensor| Sets the fine adjusting value to calibrate the external temp.
sensor available optionally.| -9.99 to 9.99°C
(0.01°C)| 0.00
3| PB Range| Sets PB (Proportional Band) range used for PID control.| 0.3 to
9.9°C
(0.1°C)| 6.0
4| I Constant| Sets integral time used for PID control.| 1 to 999sec
(1sec)| 18
5| D Constant| Sets differential time used for PID control.
When 0 is set, differential operation is not made.| 0.0 to 99.9sec
(0.1sec)| 0.0
---|---|---|---|---
6| Heatin g/Cooling
Ratio| Sets output ratio of cooling to heating to compensate difference of
gain between them.| 10 to 999%
(1%)| 300
7| Overload Judging
Temp. Rang| Sets the temp. range for judgment of overload (accompanying
abnormal output alarm ERR15).| 0.1 to 9.9°C
(0.1 sec| 0.2
8| Overload Judging
Time| Sets time for judgment of overload (accompanying abnormal output alarm
ERR15). When 0 is set, the alarm doesn’t arise.| 0 to 99min
(1 min)| 10
9| Output Ratio| Shows output ratio of thermo module by 1%. The prefix symbol
“- stands for cooling and no prefix stands for heating.| -100 to 100%
(1%)| –
10| Upper/Lower
Temp. Alarm
Sequence| Determines whether or not temp.
upper/lower limit alarm is output when power is turned on.
On : Output
Off : Not output| On, Off| Off
Outline Dimensions (mm)
HECR002
HECR002-A5-E(option)
HECR004
HECR004-A5-E(option)
HECR006
HECR008
HECR010
Key Parts
HECR002 / HECR004 / HECR006
A | Power switch | G | Power supply connector |
---|---|---|---|
B | Display/Operation panel | H | Communication connector |
C | Reservoir Cap | I | External sensor/Alarm output connector |
D | Level gauge | J | Circulating fluid OUT |
E | Handle | K | Circulating fluid IN |
F | Model No. label | L | Dain port |
Maintenance
9.1 Daily Check
- Indication of display panel: Check temperature condition and confirm whether or not an alarm has occurred.
- Confirm that the heat sink and panel are free from dust. A large amount of dust may impair the performance.
- Confirm there is no leakage of circulating fluid and check the condition of the piping (e.g. no tight bends or crushed pipes).
- Confirm there is no abnormal sound, smell or heating from the product.
Caution
- When cleaning the panel or heat sink use a vacuum cleaner to remove the dust. Do not use water or steam since it leads to rusting of the frame.
9.2 General Maintenance
Replace the circulating fluid regularly to avoid any problems due to algae or
contamination.
-
Drain circulating fluid from the Fluid IN.
Loosen the reservoir cap to help draining. (Do not remove the cap) -
To drain from the piping, blow air (0.1MPa, about 1 minute) from Fluid OUT to Fluid IN. Close the reservoir cap while blowing.
HECR008 / HECR010
-
Drain circulating fluid from the Drain port.
Loosen the reservoir cap to help draining. (Do not remove the cap) -
To drain from the piping, blow air (0.1MPa, about 1 minute) from Fluid OUT to Drain port. Close the reservoir cap and Fluid IN while blowing.
Caution
- The repair and maintenance services of this unit are performed only at SMC factory. SMC does not provide on-site repair or maintenance service in a national or overseas situation.
- It is recommended to prepare spare units to minimize downtime due to those repair and maintenance services.
- Drain the fluid from the product when it is returned for the repair and maintenance service. If the fluid is left inside, an accident and damage can result during transportation.
- Do not make any modification to the product.
- Do not disassemble the product, unless required by installation instructions.
- If fluid other than water is used, wash the circulating fluid circuit with water or DI water before returning the product to SMC. Products that have not been washed may not be accepted at the factory.
Troubleshooting
10.1 How to reset the alarm
Code | Description | Manner of reset |
---|---|---|
ERRO1 | System error 1 | Restart the power supply. In the case the alarm can’t |
be reset by above manner, repair is required.
ERRO2| System error 2
ERRO3| Back-up data error| Initialization of FRAM or stop and restart of power
supply In the case the alarm can’t be reset by above manner, repair is
required.
WRN| Temp. upper/lower limit
alarm| The unit continues controlling and recovers normal condition at any
time.
Others| Remove a possible cause and restart. In the case the alarm can’t be
reset by above manner, repair is required.
10.2 Product alarm codes
Code
WRN| Description
Temp.
upper/lower limit| Operation
status| Reason for alarm
setting| Cause / Measure
Product is reaching target temperature.
Wait for the temperature to stabilize, then the WRN should disappear.
---|---|---|---|---
Continue| Fluid temperature is
out of limit range.
ERRO1| System error 1| Stop| The wire inside the
Thermo-con was
broken due to
vibration during
transport.| In the case the alarm can’t be reset by above manner, repair is
required.
ERRO2| System error 2| Stop| The FRAM data was
destroyed by high-
level noise.| Move the product to an environment with little noise, turn ON
the power supply. If there is no alarm, it was caused by noise.
Please consult with SMC.
ERRO3| Back-up data
error| Stop| The memory data was destroyed by high-level noise.| Move the
product to an environment with little noise, turn ON the power supply. If
there is no alarm, it was caused by noise.
Please consult with SMC.
Declaration of Conformity
Below is a sample Declaration of Conformity(DoC) used for this product.
An actual DoC will be supplied with each product.
Revision history
Rev.G:Apr.2022
SMC Corporation
4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021 JAPAN