CAMDEN DOOR CONTROLS CX-DE1200 Delayed Egress Electro Magnetic Lock Instruction Manual
- June 10, 2024
- CAMDEN DOOR CONTROLS
Table of Contents
- CX-DE1200 Delayed Egress Electra Magnetic Lock
- DESCRIPTION
- SPECIFICATIONS
- DIMENSIONS
- FEATURES
- INSTALLATION CONCEPT AND ACCESSORIES
- ARMATURE MOUNTING INSTRUCTIONS
- CONFIGURATION
- PARTS REPLACEMENT
- ACCESSORIES WIRING
- COMPLETE WIRING OPTIONS AND FUNCTIONS
- Read User Manual Online (PDF format)
- Download This Manual (PDF format)
Electrified Locks, Relays and Timers
CX-DE1200
Delayed Egress Electra Magnetic Lock Special Locking Arrangement
INSTALLATION INSTRUCTIONS
CX-DE1200 Delayed Egress Electra Magnetic Lock
Building & Fire Life Safety Code Compliant:
IBC International Building Code
NFPA 101 Life Safety Code
NFPA 1, UFC Uniform Fire Code
CBC California Building Code
BOCA National Building Code
Chicago Building Code
THIS PACKAGE INCLUDES
1- CX-DE1200 Electra Magnetic Lock Housing assemble with main controller PCB &
Magnetic Plate
1- Mounting Template
4- Adhesive door signage
1- Installation Instructions & Wiring Diagrams
1- Armature Plate Assembled Housing & Proxy Trigger
1- Electra Magnetic Lock Screw Packaging
THIS PRODUCT MUST BE CONNECTED INTO A FIRE ALARM SYSTEM PER NAPA CODE OR OTHER
REGULATIONS SO THAT, IN THE EVENT OF FIRE, THE TIME DELAY WILL BE BYPASSED.
CONTACT YOUR LOCAL CODE AUTHORITY TO REIFY COMPLIANCE WITH FIRE AND BUILDING
CODES. THE DELAYED EGRESS DEVICE SHOULD BE ROUTINELY CHECKED FOR PROPER
OPERATION AND COMPLIANCE WITH FIRE AND BUILDING CODES.
DESCRIPTION
Intended for use in an Indoor location – Out Swing.
When an unauthorized exit is trigger, the delays exit through the door for a
period of 15 or 30 seconds. An LED bar segment display countdown by seconds
and voice messages to inform the person planning to exit with the remaining
times to unlock.
In the meantime, the person exiting must wait to allow time for security
personnel or staff to respond. The door will eventually unlock after the 15 or
30 seconds delay time has passed, permitting the exit. During an emergency, a
signal from the fire/life safety system will release the lock promptly.
SPECIFICATIONS
Voltage| 12/24V DC +/- 10% (Auto Sensing) Power Suplly must be UL 294 or
UL 603 Listed with a Class 2, power limited output
---|---
Current Draw| 600mA / 350mA
Lock Output| 12/24 VDC, 1A
Lock Status Relay Rating Max. | 30 VDC, 2A, 1 pF
Alarm Output Rating Max. | 30 VDC, 2A, 1 pF
DPS Rating Max. | 30 VDC, 0.1A, 1 pF
Bond Sensor Rating Max. | 30 VDC, 2A, 1 pF
**ATS Rating Max. *| 30 VAC / 42.4 VDC, 5A, 1 pF
Operating Temperature| 0~55°C (32~131°F)
Operating Humidity| 0~95% (non-condensing)
Dimensions (Lock)| 11” H x 3” W x 3” D (280mm x 76mm x 74.5mm)
Dimensions (Armature Plate)**| 11” H x 2-5/8” W x 1” D (280mm x 68mm x
23.5mm)
PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS.| PUSH UNTIL ALARM
SOUNDS. DOOR CAN BE OPENED IN 30 SECONDS.
---|---
KEEP PUSHING. THIS DOOR WILL OPEN IN 15 SECONDS. ALARM WILL SOUND.| KEEP
PUSHING. THIS DOOR WILL OPEN IN 30 SECONDS. ALARM WILL SOUND.
DIMENSIONS
UL 294 Access Control Performance Levels: | Levels: |
---|---|
Access Control Line Security | Level I |
Destructive Attack | Level I |
Endurance | Level IV |
Standby Power | Level I |
FEATURES
-
Holding Force up to 1200 Lbs. (Not validated by UL)
-
Field selectable exit delay time 15 or 30 seconds
-
Nuisance Delay period either 1, 2 or 3 seconds
-
75dB Buzzing Tone with LED segment bar display time seconds & field selectable voice alerts
-
Choice of sensor to be activated:
– Door Motion
– Door Exit Device with momentary normally open contact
– Push Bar with momentary normally open contact -
Auto Start Up:
– Occurs when power supply is restored and/or the fire panel is restored (When allowed by Building & Fire Life Safety Code) -
Manual Start Up:
– This is a California & UBC Building Code Compliant Feature.
Only after power supply restoration and fire panel reset may the lock be Reset manual at the opening. This lock can be reset with the built-in reset key switch or an external key switch or a reset switch connected to the door -
Vandal resistant Proximity Trigger Sensor
-
Auto Sensing Voltage Power Input 12/24 VDC
-
Reverse power protection:
If someone hooks power up backwards, the board simply does not turn on, protecting it from damage -
Optional Connection for Auxiliary Lock, CX-DE1201 (Double Leaf Door)
-
Hall Effect Sensor Monitoring Output
-
Tamper Switch Output
-
Tailgating Prevention – door will re-lock as soon as it closes
-
Anti-Pass Back / Auto re-lock:
If door doesn’t open after the count down, the door will automatically re- lock.
INSTALLATION CONCEPT AND ACCESSORIES
Seven configuration versions are available to be compliant to regional jurisdictions.
Models| Delay Release Time (Seconds)| Nuisance
Delay (Seconds)| Reset After Alarm| Lock Status on
Power-Up
---|---|---|---|---
Fixed| Selectable| Fixed| Selectable| Selectable|
Fixed| Fixed| Selectable
CX-DE1200-N1| | 15 or 30| | 1 or 2| | Manual| | Locked / Unlocked
CX-DE1200-N2| 15| | | 0 or 1| | Manual| | Locked / Unlocked
CX-DE1200-N3| 30| | | 0 or 1| | Manual| | Locked / Unlocked
CX-DE1200-N4| 15| | | 0 or 1| | Manual| Unlocked|
CX-DE1200-B1| 15| | | 0 or 3| Auto / Manual| | | Locked / Unlocked
CX-DE1200-B2| 30| | | 0 or 3| Auto / Manual| | | Locked / Unlocked
CX-DE1200-B3| 15| | 0| | Auto / Manual| | | Locked / Unlocked
N# = NFPA Compliance
B# = BOCA Compliance
BOCA Compliance
Manual Reset: Is achieved by authorized personnel closing the door after an
alarm and actuating the integral reset key switch or by momentarily closing a
contact connected to the remote RESET terminal.
Automatic Reset: Reset will automatically be initiated once the door has
been opened, then closed and remains closed for 30 consecutive seconds.
Dip Switch Settings
WARNING!
Contact authority having jurisdiction for approval prior to selecting release
time, nuisance time and start-up settings.
this J10 jumper only if Fire Panel or Smoke Detection system is connected to
the (Fire P) terminal.
NOTE:
- all field-wiring to the unit shall not exceed 30 m (98.5 ft)in length.
- all external power sources shall be UL Listed with Class 2,power-limited output.
Display Mode
Jumper J10 (Fire Panel Input) Jumper Settings
Installed: Factory default setting
Uninstalled: Only if a dry contact (NC) from afire alarm panel or smoke
detector system is connected to the “Fire P” terminals.
ARMATURE MOUNTING INSTRUCTIONS
Step 1: Close the door, position the EM lock mounting location as close to the upper corner of the door with a minimum gap 1″.
Step 2: Place the template against the door and frame and drill holes according to template indications.
Step 3: Place the mounting plate against the door frame and screw in according to the template holes position.
Step 4: Place the armature housing against the door and screw in according to the template holes position
Step 5: Slot in the electromagnet lock unit through the shoulder screw
into the EZ mounting plate as shown in Figure 1-2 below.
CAUTION: The lock unit must be held in place until secured with fixing
screws.
Step 6: Align the lock unit with the mounting plate. Fix the lock unit to
the mounting plate with the allen key given through fixing the screw.
Carefully screw into the mounting plate to avoid stripping the threads. Check
and confirm the alignment and mating surface between the armature plate and
lock unit.
NOTICE: Loosen screw #1 or #2 to re-align the mounting plate and position
the lock unit mating surface to fully attach with the armature plate. Re-
tighten screw #1, #2 and screw-in the balance screw holes of mounting plate
and armature housing.
Step 7: Pull the wires through the door frame, mounting plate and into the electromagnetic lock unit casing. Fix the electromagnet lock unit to the mounting plate with the fixing screw. Make sure to fully tighten the fixing screw with the proper tool (eg. “T” Handle Allen Key).
Step 8
After the lock unit has been mounted to the door and frame as per the provided
template, route the wires through the access hole and out to the controller
board. Re-mount the lock front cover onto the lock. Make sure the proxy sensor
is aligned with the hole on
the cover. The sensor height is factory default which slightly projected out
from the surface cover.
CAUTION: Do not attempt to adjust the proxy sensor height, as this will
result in damage to the sensor and void the warranty.
Step 9
Make all wiring connections to the lock controller board. Special precaution
on the polarity of the input power terminals. This lock has auto sensing
voltage feature which automatically configures itself for 12 VDC or 24 VDC
operation. Correct power supply voltage must be used for proper lock
operation.
NOTE: The length of wiring to all field-wiring terminals shall not exceed
98.5 ft (30 m)
CAUTION: Input terminals for R-Exit, Reset & Ex-Trig must only be
connected to a normally open momentary dry contact switch. Connection to a
voltage or “wet” output may damage the lock and void the warranty.
Step 10
Slowly swing the door closed and visually check the position of the proxy
trigger as it approaches the proxy sensor on the lock. The proxy trigger &
sensor should align between one another either horizontally or vertically, if
the installation was done perfectly using the provided mounting template. The
LED at the back of the proxy sensor will light on when the proxy trigger is
detected.
IMPORTANT NOTICE: Standard operation of the lock depends on the proxy
sensor being able to detect the proxy trigger when the door is swing closed. A
minor adjustment can be made to the proxy sensor height for fine tuning.
Step 11
Fine Tuning Proxy Sensor Height:
- Turning proxy sensor holder clockwise (CW) will increase the height of the proxy sensor from the front cover surface; hence decreasing the gap between the sensor and proxy trigger.
- Turning proxy sensor holder counterclockwise (CCW) will decrease the height of the proxy sensor from the front cover surface; hence increasing the gap between the sensor and proxy trigger.
Step 12
Fine Tuning Door Movement Detection Sensitivity:
The proxy trigger is spring loaded and can be screwed in or out from the proxy
trigger ABS housing using the provided Allen key M5.
Hence, increase or decrease the gap between the sensor and proxy trigger.
IMPORTANT NOTICE: Standard installation of the proxy sensor and proxy
trigger does not have to touch each other physically to operate correctly.
Release Time:
The Release time can be selectable either 15 or 30 seconds. The Nuisance time
delay is included in the door Release cycle and the total time to unlock the
door remain the same as per setting once sensor is triggered.
Nuisance Time:
The Nuisance time feature is a warning time delay that commences when pressure
is applied to outward swinging doors. Releasing the door before the end of the
nuisance time, will turn off the warning alarm buzzer and reset nuisance time
to origin. Nuisance
time is field selectable for 1, 2 or 3 seconds. Triggering the proxy sensor
beyond the nuisance time will start the irreversible Release cycle time. The
Nuisance time is included in the lock Release time cycle.
R-Exit Time:
The Request Exit (R-Exit) time is field selectable for 1, 15, 20, or 30
seconds. The R-Exit time is the duration for the lock that will remain
Unlocked (Bypass), after a remote normally open contact switch is momentarily
activated. When activated with an access
control system, the R-Exit time cycle will start after the access control
relay open time expires. The door will automatically re-lock if the door is
opened, then closed during the R-Exit time cycle.
Trigger Type:
The trigger type is field selectable either EXTERNAL or INTERNAL. Selecting
INTERNAL mode uses the built-in proxy sensor and EXTRIG terminal to trigger
the Release Time cycle. Selecting External mode will disable the INTERNAL mode
sensor; activation of the Release Time cycle is triggered by an external
egress device equipped with a normally open contact switch.
Start-Up State:
The Start-Up selection, imply the state of lock during restoration of power
up. It is field selectable either be LOCKED or UNLOCKED.
In the LOCKED mode, the lock will be reset to secure mode. In the UNLOCKED
mode, the lock will remain unlocked and the LED Bar display will indicate as
per By-Pass mode. To reset the lock; a momentarily normally open contact to
the RESET signal will re-lock the door. This feature selection is to comply
with building code requirements in jurisdictions that require manual reset or
re-lock upon loss and restoration of system power supply.
Warning Type:
The warning type is field selectable either TONE or VOICE. In secure status,
the LED Bar displays a 15 segment or 30 segment LED light. Each segment
represents. Upon activation of the irreversible Release Time cycle, the LED
Bar segment display begins to turn off one by one. In VOICE mode, the
countdown will be counted along with verbal exit guidance. When the LED bar
display reaches zero, the lock will release. The verbal voice guidance changes
to a continuous verbal instruction announcing, “Door nlocked”. In TONE ONLY
mode, the countdown will be accompanied with a beeping tone only, and a
continuous tone is heard once the Release time cycle ends.
Languages:
The voice message can be in 3 languages which are field selectable. The
languages are English (Default), French and Spanish.
Voice Type:
For English only, the voice type is field selectable for either a male or
female voice.
Examples:
- 15 seconds Mode: “Door will unlock in 15 seconds; Door will unlock in 5 seconds; Door unlocked…” (Both messages repeat “Door unlocked” until the lock is reset).
- 30 seconds Mode: “Door will unlock in 30 seconds; Door will unlock in 20 seconds; Door will unlock in 10 seconds; Door will unlock in 5 seconds; Door unlocked…” (Both messages repeat “Door unlocked” until the lock is reset).
Door POS Alarm (DPA):
- DPA Active: The lock will enter alarm mode when the door is held open past the R-Exit time period triggering a buzzing tone or alarm voice and the DPA can be Reset by the built-in key switch or remote reset.
- DPA Inactive: The lock will enter stand-by mode which will remain unlocked if the door is held open past the R-Exit time set. No warning sound is emitted. The Lock can re-lock upon closure of the door.
Anti-Pass Back
If door doesn’t open after the count down, the door will re-lock after a set
time frame: 1 or 5 seconds.
Dip Switch Position
CONFIGURATION
Configuration Options
| Delay Release| Nuisance Delay| ****
Request to Exit Period
| Trigger Type| Power-Up State| Door Prop Open|
Anti-Pass Back| Reset After ALARM
---|---|---|---|---|---|---|---|---
Switch 1| Switch 2| Switch| 3| 4| Switch
5| Switch 6| Switch 7| Switch 8|
**N1| ** 15| OFF| 1| OFF| 1 Sec| ON|
ON| Internal| OFF| Unlocked| OFF| Stand- by|
OFF| 5| OFF| **** Fixed Manual
| 30| ON| 2| ON| 15 Sec| OFF| OFF| External| ON| Locked| ON| Alarm| ON| 1| ON
All options selectable
| 20 Sec| ON| OFF| | | | | | | | |
30 Sec| OFF| ON| | | | | | | |
**N2**| 15| Not Used| 0| OFF| 1 Sec| ON| ON| Internal| OFF| Unlocked|
OFF| Stand- by| OFF| 5| OFF| Fixed Manual
| 15| 1| ON| 15 Sec| OFF| OFF| External| ON| Locked| ON| Alarm| ON| 1| ON
NFPA Compliant
| 20 Sec| ON| OFF| | | | | | | | |
30 Sec| OFF| ON| | | | | | | |
N3| 30| Not Used| 0| OFF| 1 Sec| ON| ON| Internal| OFF| Unlocked| OFF|
Stand- by| OFF| 5| OFF| Fixed Manual
| 30| 1| ON| 15 Sec| OFF| OFF| External| ON| Locked| ON| Alarm| ON| 1| ON
NFPA Compliant
| 20 Sec| ON| OFF| | | | | | | | |
30 Sec| OFF| ON| | | | | | | |
N4| 15| Not Used| 0| OFF| 1 Sec| ON| ON| Internal| OFF| Unlocked| Not
Used| Stand- by| OFF| 5| OFF| Fixed Manual
| 15| 1| ON| 15 Sec| OFF| OFF| External| ON| Unlocked| Alarm| ON| 1| ON
NFPA/OSHPD Compliant. Power Up
unlocked and manual reset is fixed.
| 20 Sec| ON| OFF| | | | | | | | |
30 Sec| OFF| ON| | | | | | | |
| | Not Used| Switch 8
B1| 15| Not Used| 0| OFF| 1 Sec| ON| ON| Internal| OFF| Unlocked| OFF|
Stand- by| OFF| | Manual| OFF
| 15| 3| ON| 15 Sec| OFF| OFF| External| ON| Locked| ON| Alarm| ON| Auto| ON
BOCA Compliant. Automatic alarm reset after 30 continuous
seconds
from door closure.
| 20 Sec| ON| OFF| | | | | | |
30 Sec| OFF| ON| | | | | |
B2| 30| Not Used| 0| OFF| 1 Sec| ON| ON| Internal| OFF| Unlocked| OFF|
Stand- by| OFF| | Manual| Off
| 30| 3| ON| 15 Sec| OFF| OFF| External| ON| Locked| ON| Alarm| ON| Auto| ON
BOCA Compliant. Automatic alarm reset after 30 continuous
seconds from door closure.| 20 Sec| ON| OFF| | | | | | |
30 Sec| OFF| ON| | | | | |
B3| 15| Not Used| 0| Not Used| 1 Sec| ON| ON| Internal| OFF| Unlocked|
OFF
| Stand- by| OFF| | Manual| OFF
| 15| 0| 15 Sec| OFF| OFF| External| ON| Locked| ON| Alarm| ON| Auto| ON
BOCA/Chicago Compliant. 0 sec nuisance. Automatic alarm
reset after 30 continuous seconds from door
closure.| 20 Sec| ON| OFF| | | | | | |
30 Sec| OFF| ON| | | | | |
PARTS REPLACEMENT
ITEM NUMBER | QTY | DESCRIPTION |
---|---|---|
1 | 1 | MOUNTING PLATE |
2 | 1 | ELECTRO MAGNETIC LOCK SCREW PACKAGING |
ACCESSORIES WIRING
COMPLETE WIRING OPTIONS AND FUNCTIONS
WARNING: Improper installation, maintenance, inspection or usage of the product or any related accessories or parts may cause the electromagnetic lock, armature plate and associated hardware to disengage and fall, causing serious bodily injury and property damage. Camden will not be liable to the installer, purchaser, end user or anyone else for damage or injury to person or property due to improper installation, care, storage, handling, maintenance, inspection, abuse, misuse or act of God or nature involving this product or any related accessories or parts. The delayed egress device should be routinely checked for proper operation and compliance with fire and building codes. Refer to maintenance document #40-82B292 for additional information.
Opening New Doors to
Innovation, Quality and Support!
Call: 1.877.226.3369 / 905.366.3377
Visit: www.camdencontrols.com
Certified ISO 9001:2008
File: CX-DE1200_Manual_R4.indd
Rev/Date: 04/Aug. 9, 2022
Part no.: 40-82B236