WARNING
IMPORTANT : Read carefully before installing product. Retain for future reference.
DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for
damages or losses of any kind that may arise from the improper, careless,
or negligent installation, handling or use of this product.
NOTICE : Product may become damaged and/or unstable if not installed
properly.
ATTENTION Receiving Department: Note actual product description of any
shortage or noticeable damage on delivery receipt. File claim for common
carrier (LTL) directly with carrier. Claims for concealed damage must be filed
within 15 days of delivery. All damaged material, complete with original
packing must be retained.
Note : Specifications and dimensions subject to change without notice.
NOTICE : Designed for indoor installation and use only. Wet location
listed.
Must not exceed 20 drivers connected to a single Tilemount sensor dimming
wires.
Must not exceed 70 °C operating environment.
Blue wire switches to Line voltage. Do not handle while powered.
Dimming luminaires should not connect 0-10V wires from different line powered
circuits.
Failure to comply with these instructions may result in death, serious bodily
injury and property damage.
Warranties and Limitation of Liability
Please refer to www.cooperlighting.com for our terms and conditions.
FCC Statement
Note : This equipment has been tested and found to comply with the limits
for a Class B digital device, pursuant to part 15 of the FCC Rules. These
limits are designed to provide reasonable protection against harmful
interference in a residential installation. This equipment generates, uses,
and can radiate radio frequency energy and, if not installed and used in
accordance with the instructions, may cause harmful interference to radio
communications. However, there is no guarantee that interference will not
occur in a particular installation.
If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the
user is encouraged to try to correct the interference by one or more of the
following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
FCC Part 15 Clause 15.21 Changes or modifications not expressly approved
by the party responsible for compliance could void the user’s authority to
operate the equipment.
FCC Part 15.19a This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1) This device may not
cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
FCC 2.1091/RSS-102 In order to comply with FCC/ISED RF Exposure
requirements, this device must be installed to provide at least 20 cm
separation from the human body at all times.
ISED RSS
This device complies with Industry Canada’s licence-exempt RSSs. Operation is
subject to the following two conditions:
(1) This device may not cause interference; and (2) This device must accept
any interference, including interference that may cause undesired operation of
the device. CAN ICES-3 (B)/NMB-3(B)
General Information
Overview
The industrial high bay sensor is an integral part of the WaveLinx Lite system
and offer passive infrared (PIR) occupancy and a photocell for closed loop
daylighting. WaveLinx Lite industrial sensors offer installation heights up to
40 feet and have coverage patterns up to 5000 square feet (see sensor
specifications – field of view). When part of the WaveLinx Lite system, the
sensor operates on a wireless mesh network based on IEEE 802.15.1 standards.
The sensors offer simple tool-less integration into WaveLinx Lite industrial
light fixtures equipped with the 4-pin Zhaga Book 18 compliant socket. Once
installed, sensors receive power from their co-located light fixture with no
batteries to replace. The sensor in combination with the WaveLinx Lite Mobile
application allows you to gain considerable energy savings from occupancy and
daylight sensing lighting control.
The WaveLinx Lite Mobile application allows you to map the sensor to any area
or control zone, select occupancy or vacancy, occupied and unoccupied light
levels and set the hold time.
Installation
De-energize electrical circuit prior to work
- Install the control module inside the fixture
- Insert and secure the sidecar housing
- Wire per the electrical diagram
- Install the sensor (twist to lock)
Specifications
Technology : WaveLinx Lite industrial sidecar sensor for fixture control based on IEEE 802.15.1 (Bluetooth). Compatible only with Cooper Lighting Solutions Lighting WaveLinx Lite System.
Wiring Diagram
Out-of-the-box functionality (if connected to loads)
Fixture operates via the onboard occupancy sensor.
- Occupancy turns fixture ON to 100%
- Fixture will dim to 10% within 20 minutes when space is vacant
Wireless setup
- Upon power up, the WaveLinx Lite Industrial Sidecar Sensor Kit will power connected luminaires to 100% when occupied.
- When the WaveLinx Lite Industrial Sidecar Sensor Kit is provisioned to a WaveLinx Lite wireless network, the connected luminaires will dim to 10% (DEFAULT) (if using 0-10V wiring)
- This feature is used to visually inspect which sensors successfully join the wireless network.
- Industrial sidecar sensors that did not pair correctly will remain at 100%.
- When the provisioning is complete all industrial sidecar sensors become part of the default (or any if others are added) zone and default (or any if others are added) occupancy set.
Note : Please refer to WaveLinx Lite manual to complete configuration.
Troubleshooting
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
www.cooperlighting.com
For service or technical
assistance:
1-800-553-3879
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2022 Cooper Lighting Solutions
All Rights Reserved
Printed in Mexico
Publication No. IB50342822
June 2022
Cooper Lighting Solutions is a registered trademark.
All trademarks are property of their respective owners.
Product availability, specifications, and compliances are subject to change
without notice.
Read User Manual Online (PDF format)
Read User Manual Online (PDF format) >>