COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit Instruction Manual

June 10, 2024
COOPER Lighting

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit Instruction Manual

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit
Instruction Manual

www.cooperlighting.com

WARNING

IMPORTANT : Read carefully before installing product. Retain for future reference.

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit -
WARNING

DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise from the improper, careless, or negligent installation, handling or use of this product.
NOTICE : Product may become damaged and/or unstable if not installed properly.
ATTENTION Receiving Department: Note actual product description of any shortage or noticeable damage on delivery receipt. File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be filed within 15 days of delivery. All damaged material, complete with original packing must be retained.

Note : Specifications and dimensions subject to change without notice.
NOTICE : Designed for indoor installation and use only. Wet location listed.
Must not exceed 20 drivers connected to a single Tilemount sensor dimming wires.
Must not exceed 70 °C operating environment.
Blue wire switches to Line voltage. Do not handle while powered.
Dimming luminaires should not connect 0-10V wires from different line powered circuits.
Failure to comply with these instructions may result in death, serious bodily injury and property damage.

Warranties and Limitation of Liability

Please refer to www.cooperlighting.com for our terms and conditions.

FCC Statement

Note : This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation.
If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:

  • Reorient or relocate the receiving antenna.
  • Increase the separation between the equipment and receiver.
  • Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
  • Consult the dealer or an experienced radio/TV technician for help.

FCC Part 15 Clause 15.21 Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate the equipment.
FCC Part 15.19a This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
FCC 2.1091/RSS-102 In order to comply with FCC/ISED RF Exposure requirements, this device must be installed to provide at least 20 cm separation from the human body at all times.

ISED RSS
This device complies with Industry Canada’s licence-exempt RSSs. Operation is subject to the following two conditions:
(1) This device may not cause interference; and (2) This device must accept any interference, including interference that may cause undesired operation of the device. CAN ICES-3 (B)/NMB-3(B)

General Information

Overview

The industrial high bay sensor is an integral part of the WaveLinx Lite system and offer passive infrared (PIR) occupancy and a photocell for closed loop daylighting. WaveLinx Lite industrial sensors offer installation heights up to 40 feet and have coverage patterns up to 5000 square feet (see sensor specifications – field of view). When part of the WaveLinx Lite system, the sensor operates on a wireless mesh network based on IEEE 802.15.1 standards.
The sensors offer simple tool-less integration into WaveLinx Lite industrial light fixtures equipped with the 4-pin Zhaga Book 18 compliant socket. Once installed, sensors receive power from their co-located light fixture with no batteries to replace. The sensor in combination with the WaveLinx Lite Mobile application allows you to gain considerable energy savings from occupancy and daylight sensing lighting control.
The WaveLinx Lite Mobile application allows you to map the sensor to any area or control zone, select occupancy or vacancy, occupied and unoccupied light levels and set the hold time.

Installation

De-energize electrical circuit prior to work

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit -
Installation

  1. Install the control module inside the fixture
  2. Insert and secure the sidecar housing
  3. Wire per the electrical diagram
  4. Install the sensor (twist to lock)

Specifications

Technology : WaveLinx Lite industrial sidecar sensor for fixture control based on IEEE 802.15.1 (Bluetooth). Compatible only with Cooper Lighting Solutions Lighting WaveLinx Lite System.

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit -
Specifications

Wiring Diagram

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit -
Wiring Diagram

Out-of-the-box functionality (if connected to loads)

Fixture operates via the onboard occupancy sensor.

  • Occupancy turns fixture ON to 100%
  • Fixture will dim to 10% within 20 minutes when space is vacant

Wireless setup

  1. Upon power up, the WaveLinx Lite Industrial Sidecar Sensor Kit will power connected luminaires to 100% when occupied.
  2. When the WaveLinx Lite Industrial Sidecar Sensor Kit is provisioned to a WaveLinx Lite wireless network, the connected luminaires will dim to 10% (DEFAULT) (if using 0-10V wiring)
  3. This feature is used to visually inspect which sensors successfully join the wireless network.
  4. Industrial sidecar sensors that did not pair correctly will remain at 100%.
  5. When the provisioning is complete all industrial sidecar sensors become part of the default (or any if others are added) zone and default (or any if others are added) occupancy set.
    Note : Please refer to WaveLinx Lite manual to complete configuration.

Troubleshooting

COOPER LIGHTING WIM-WH-SKIT WaveLinx Lite Industrial Sidecar Sensor Kit -
Troubleshooting

Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
www.cooperlighting.com
For service or technical
assistance:
1-800-553-3879

Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172

© 2022 Cooper Lighting Solutions
All Rights Reserved
Printed in Mexico
Publication No. IB50342822
June 2022

Cooper Lighting Solutions is a registered trademark.
All trademarks are property of their respective owners.
Product availability, specifications, and compliances are subject to change without notice.